Permit Application Status

B0400677


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0400677
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
LEE'S SUMMIT CITY HALL FULL BUILDING PERMIT
04/21/2004
12/10/2004
06/08/2005
04/04/2008
Locations
Contacts
SHAUGHNESSY FICKEL AND SCOTT ARCHITECTS, Address:1150 GRAND BLVD SUITE 400  
TITAN CONSTRUCTION ORGANIZATION, Address:11865 S CONLEY  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/02/2005 10/29/2010
Correction

A note should be provided indicating a Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water supply line for make-up water to boilers.
Correction

A note should be provided indicating the sump pump should discharge to daylight not into a floor sink connected to a sanitary sewer line.
Correction

Fire Department- IFC 1008.1.2 Exit doors shall swing in the direction of travel where serving an occupant load of 50 or greater.
Correction

Fire Department- The occupant load shall be posted at a conspicuous location near the main door of the Council Chamber.
Correction

Fire Department- The loading dock and dumpster enclosure shall be protected by the automatic sprinkler system. The sprinkler system shall be designed to provide all-season protection for the level of hazard present.
Correction

Codes Administration - 2003 IBC 302.1.1.1 - Separation. Where Table 302.1.1 requires a fire-resistance-rated separation, the incidental use area shall be separated from the remainder of the building with a fire barrier. Where Table 302.1.1 permits an automatic fire-extinguishing system without a fire barrier, the incidental use area shall be separated by construction capable of resisting the passage of smoke. The partitions shall extend from the floor to the underside of the fire-resistance-rated floor/ceiling assembl or fire-resistance-rated roof/ceiling assembly or to the underside of the floor or roof deck above. Doors shall be self-closing or automatic-closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permitted in accordance with NFPA 80.
Correction

Codes Administration - Detail 14 on Sheet A1.7 does not clearly indicate that the fire partition is continuous at the angled section of the wall connecting the east/west and north/south walls.
Correction

Codes Administration - 2003 IBC 3006.4 - Machine rooms and machinery spaces. Elavator machine rooms and machinery spaces shall be inclosed with construction having a fire-resistance rating not less than the required rating of the hoistway enclosure served by the machinery. Openings shall be protected with assemblies having a fire-resistance rating not less than that required for the hoistway enclosure doors.
Correction

Codes Administration - 2003 IBC 3006.6 - Plumbing systems. Plumbing systems shall not be located in elevator equipment rooms.
Correction

Codes Administration - 2003 IBC 707.2 - Shaft enclosure required. Openings through a floor/ceiling assembly shall be protected by a shaft enclosure complying with this section.
Correction

Codes Administration - 2003 IBC 711.4 - Continuity. Assemblies shall be continuous without openings, penetrations or joints except as permitted by this section and Sections 707.2, 712.4 and 713. Skylights and other penetrations through a fire-resistance-rated roof deck are permitted to be unprotected, provided that the structural integrity of the fire-resistance-rated roof construction is maintained. Unprotected skylights shall not be permitted in roof construction required to be fire-resistance rated in accordance with Section 704.10. The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported.
Correction

Codes Administration - 2003 IBC 711.5 - Penetrations. Penetrations through fire-resistance-rated horizontal assemblies shall comply with Section 712.
Correction

Codes Administration - 2003 IBC 711.7 - Ducts and air transfer openings. Penetrations by ducts and air transfer openings shall comply with Sections 712 and 716.
Correction

Codes Administration - 2003 IBC 713.1 - General. Joints installed in or between fire-resistance-rated walls, floor or floor/ceiling assemblies and roofs or roof/ceiling assemblies shall be protected by an approved fire-resistant joint system designed to resist the passage of fire for a time period not less than the required fire-resistance rating of the wall, floor or roof in or between which it is installed. Fire-resistant joint systems shall be tested in accordance with Section 713.3. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 713.4.
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2003 IBC 706.7 - Openings. Openings in a fire barrier wall shall be protected in accordance with Section 715. Openings shall be limited to a maximum aggregate width of 25 percent of the length of the wall, and the maximum area of any single opening shall not exceed 120 square feet. Openings in exit enclosures shall also comply with Section 1019.1.1.
Correction

Codes Administration - 2003 IBC 2407.1 - Materials. Glass used as structural balustrade panels in railings shall be constructed of either single fully tempered glass, laminated fully tempered glass or laminated heat-strengthened glass. Glazing in railing in-fill panels shall be of an approved safety glazing material that conforms to the provisions of Section 2406.1.1. For all glazing types, the minimum nominal thickness shall be 0.25 inch. Fully tempered glass and laminated glass shall comply with Category II of CPSC 16 CFR 1201, listed in Chapter 35.
Correction

Codes Administration - 2003 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficent for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in an occupancy in Group I-2 used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2003 IBC1008.1.2 - Door Swing. Egress door shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy.
Correction

Codes Administration - 2003 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 1010.2 - Slope. Ramps used as part of the means of egress shall have a running slope not steeper than one unit vertical in 12 units horizontal. The slope of other ramps shall not be steeper than one unit vertical in eight units horizontal.
Correction

Codes Administration - Placement of required exit signage and emergency lighting is subject to onsite inspection.
Correction

Codes Administration - 2003 IBC 1009.3 - Stair treads and risers. Stair riser heights shall be 7 inches maximum and 4 inches minimum. Stair tread depths shall be 11 inches minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 0.375 inch. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at right angle to the tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 0.375 inch. Winder treads shall have a minimum tread depth of 11 inches measured at a right angle to the tread's leading edge at a point 12 inches from the side where the treads are narrower and minimum tread depth of 10 inches. The greatest winder tread depth at the 12 inch walk line within any flight of stairs shall not exceed the smallest by more than 0.375 inch.
Correction

Codes Administration - 2003 IBC 1009.11.4 - Handrail-gripping surfaces shall be continuous, without interruption by newel posts or other obstructions.
Correction

Codes Administration - Information has not been provided for signage to be installed within the building.
Correction

Codes Administration - 2003 IBC 2405.1 - Scope. This section applies to the installation of glass and other transparent, translucent or opaque glazing material installed at a slope more than 15 degrees from the vertical plane, including glazing materials in skylights, roofs and sloped walls.
Correction

Codes Administration - The specification books have not been completed.
Correction

Codes Administration - Provide one copy of the full size plan set and one copy of the half size plan set once the plans have been approved.
Correction

Codes Adminstration - 2002 NEC 110.26(B) - Clear spaces. Working space required by this section shall not be used for storage. When normally enclosed live parts are exposed for inspection or servicing, the working space, if in a passageway or general open space, shall be suitably guarded.
Correction

Codes Administration - 2003 IMC 602.2.1 - Materials exposed within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials exposed within plenums shall be noncumbustible or shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and the occupant load or other parameters as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined from the maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

Codes Administration - Information on the elevators to be installed has not been provided.
Correction

Codes Administration - 2003 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected b an accessible route, the onl toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible.
Correction

Codes Adminsitration - ASM A117.1 2000 - 2.2.4 Access to pits. Safe and convenient access shall be provided to all pits, and shall conform to 2.2.4.1 through 2.2.4.4.
Correction

Fire Department- The transformer pad located on the northwest corner of the alley way shall not encroach on the the underground fuel storage tanks (two) located south of the east driveway to the fire department and the east/west alley.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative.
Correction

CA - Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration Department prior to the state insection so that a member of the staff can witness the inspection.
Correction

NOTE: The contractor must contact the Missouri Department of Natural Resources at 1-800-361-4827 prior to starting the demolition.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

All proposed hose bibb connections must have an approved (vacuum breaker) backflow preventer.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $35,102.00 $35,102.00 Paid 12/10/2004
24 BLDG Plan Check Fees $605.00 $605.00 Paid 12/10/2004
25 Electrical Permit Fee $1,390.00 $1,390.00 Paid 12/10/2004
25 Mechanical Permit Fees $721.50 $721.50 Paid 12/10/2004
25 Plumbing Permit Fees $414.00 $414.00 Paid 12/10/2004
84 Water Meters $625.00 $625.00 Paid 12/10/2004
85 Water Taps $5,468.00 $5,468.00 Paid 12/10/2004
89 Sewer Tap Fees $2,340.00 $2,340.00 Paid 12/10/2004
Right of Way Permit $35.00 $35.00 Paid 12/10/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 11/03/2004
Rough Framing Inspection - Commercial Partial 11/19/2004
Correction
Partial Correction
11/19/2004
C.I.P. CONCRETE WALLS @ SOUTH ENTRANCE ENSURE 1-1/2" COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 12/01/2004
Correction
Resolved
12/01/2004
C.I.P. CONCRETE WALLS @ SOUTH ENTRANCE
Correction
Partial Correction
12/01/2004
CONCRETE ARCH ABOVE S ENTRANCE PER DETAIL SECT 2/S4.6 ENSURE 1-1/2" COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 02/17/2005
Correction
Resolved
02/17/2005
CONCRETE ARCH ABOVE S ENTRANCE PER DETAIL SECT 2/S4.6
Correction
Partial Correction
02/17/2005
C.I.P. CONCRETE NORTH ENTRANCE ARCH WALL POUR PREP PER 7/S4.6 & 2/S4.6; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 03/18/2005
Correction
Partial Correction
03/18/2005
CLOCK TOWER WALL TO ELEVATION 109'-10"; PER SHEET S6.1 OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 03/28/2005
Correction
Resolved
03/28/2005
C.I.P. CONCRETE NORTH ENTRANCE ARCH WALL POUR PREP PER 7/S4.6 & 2/S4.6; ARCH POUR PREP PER (2) ON S4.6 ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/04/2005
Correction
Resolved
04/04/2005
C.I.P. CONCRETE NORTH ENTRANCE ARCH ARCH POUR PREP PER (2) ON S4.6 PER 7/S4.6 & 2/S4.6 WALL POUR PREP +
Correction
Partial Correction
04/04/2005
CLOCK TOWER WALL TO ELEVATION 109'-10"; PER SHEET S6.1
Correction
Partial Correction
04/04/2005
CLOCK TOWER SUSPENDED SLAB PLACEMENT OF HAIRPINS AT BRICK LEDGE EMBEDS IN PROGRESS. PER (7) & (12) ON S6.1 OK TO POUR WHEN READY
Suspended Slab Inspection Partial 04/06/2005
Correction
Partial Correction
04/06/2005
PREP FOR SLAB-ON-STEEL DECK POUR -- 2ND FLOOR FROM (1) TO (5.5) AFTER METAL DECK IS CLEANED AND RE-MESH IS PROPERLY PLACED; SUBJECT TO TERRACON INSP OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/08/2005
Correction
Partial Correction
04/08/2005
CLOCK TOWER WALL TO ELEVATION 109'-10"; TO ELEVATION 127'-10" (CAST-IN INSERTS YET TO BE PLACED BEFORE/WITH FORM COMPLETION); PER SHEET S6.1
Rough Framing Inspection - Commercial Failed 04/15/2005
Correction
Corrective Action Required
04/15/2005
LIGHT-GUAGE STEEL FRAMING -- EXTERIOR WALLS & PARAPET 1) SOME FLANGES NOT SCREWED TO BOTTOM TRACK @ WEST WALL 2) CLIP ANGLES FROM TOP OF STUDS TO CONT STEEL ANGLE: a.COMPLETE OR CLARIFY SPACING; b.C/O/C ATTACHMENT @ STUD; c.C/O/C ATTACHMENT @ ANGLE; REF A/E DRWGS INCL S4.XX + REF APP'D SHOP DRWGS
Rough Framing Inspection - Commercial Request Complete 4/14/2005 4/15/2005 04/15/2005
Rough Framing Inspection - Commercial Partial 04/19/2005
Correction
Partial Correction
04/19/2005
LIGHT-GUAGE STEEL FRAMING -- EXTERIOR WALLS & PARAPET ON (4.8) FROM (C) TO (F.5); ON (C) FROM (4.8) TO (1.0); ON (1.0) FROM (C) TO (F); ON (F) FROM (1.0) TO (3.1); ON (G) FROM (1.0) TO (3.1); ON (1.0) FROM (G) TO (J); ON (J) FROM (1.0) TO (9.0); OK TO COVER WHEN READY WALL SEGMENTS LISTEDBELOW
Correction
Corrective Action Required
04/19/2005
PREREQUISITE TO APPROVAL OF STRUCTURAL SYSTEM INFORMATION ON SYSTEMS FOR PROTECTING THE COLUMNS SUPPORTING THE HORIZONTAL ASSEMBLY MUST BE PROVIDED PRIOR TO INSPECTION OF SYSTEMS. REQUIRED BY PLAN REVIEW NOT SUMITTED TO DATE
Underground Electrical Inspection - Commercial Request Complete 4/18/2005 4/19/2005 04/19/2005
Rough Framing Inspection - Commercial Request Complete 4/18/2005 4/19/2005 04/19/2005
Suspended Slab Inspection Failed 04/20/2005
Correction
Partial Correction
04/20/2005
None 2ND FLOOR FROM (5.75 TO 11.25) INSTALED PER S4.4
Rough Framing Inspection - Commercial Partial 04/25/2005
Correction
Resolved
04/25/2005
CLOCK TOWER WALL TO ELEVATION 109'-10"; TO ELEVATION 127'-10"; TO ELEVATION 132' PER SHEET S6.1 CONTINGENT ON TERRACON
Suspended Slab Inspection Partial 04/25/2005
Correction
Resolved
04/25/2005
None
Correction
Partial Correction
04/25/2005
2ND FLOOR CONCRETE SLAB POURED ON STEEL DECK 2ND FLOOR FROM (1.0) TO (11.25) PER S4.4; FROM (11.25) TO (16.0); OK TO POUR WHEN READY AREAS DESCRIBED BELOW:
Suspended Slab Inspection Passed 05/09/2005
Correction
Resolved
05/09/2005
2ND FLOOR CONCRETE SLAB POURED ON STEEL DECK 2ND FLOOR FROM (1.0) TO (11.25) PER S4.4; FROM (11.25) TO (16.0); N OF (16) & EAST OF (G) OK TO POUR WHEN READY AREAS DESCRIBED BELOW:
Rough Plumbing Inspection - Commercial Failed 05/23/2005
Correction
Resolved
05/23/2005
1ST FLOOR WASTE & VENT
Correction
Corrective Action Required
05/23/2005
1ST FLOOR ROOF DRAINS & OVERFLOW PROVIDE CLEANOUTS FOR CHANGES IN DIRECTION GREATER THAN 45 DEGREES PER IPC 708.3.3 NOTE: CLEANOUTS ON 2ND FLOOR FOR THIS SYSTEM W/IN 40 FT. OF THE CHANGE IN DIRECTION ARE SUITABLE.
Electrical Service Inspection Passed 05/23/2005
Correction
Resolved
05/23/2005
GROIUNDING ELECTRODE CONDUCTOR RELEASE MAIN SERVICE
Rough Framing Inspection - Commercial Not Ready 05/24/2005
Correction
Resolved
05/24/2005
CLOCK TOWER SUSPENDED SLAB PER (7) & (12) ON S6.1
Correction
Partial Correction
05/24/2005
LIGHT-GUAGE STEEL FRAMING -- EXTERIOR WALLS & PARAPET ON (4.8) FROM (C) TO (F.5); ON (C) FROM (4.8) TO (1.0); ON (1.0) FROM (C) TO (F); ON (F) FROM (1.0) TO (3.1); ON (G) FROM (1.0) TO (3.1); ON (1.0) FROM (G) TO (J); ON (J) FROM (1.0) TO (9.0); OK TO COVER WHEN READY WALL SEGMENTS LISTEDBELOW
Correction
Corrective Action Required
05/24/2005
READINESS FOR INSPECTION IBC 109.1 WORK REQUESTED FOR INSP ALREADY COVERED
Rough Framing Inspection - Commercial Request Complete 5/23/2005 5/24/2005 05/24/2005
Rough Framing Inspection - Commercial Partial 05/25/2005
Correction
Resolved
05/25/2005
LIGHT-GUAGE STEEL FRAMING -- EXTERIOR WALLS & PARAPET ON (4.8) FRM (C) TO (F.5); ON (C) FRM (4.8) TO (1.0); ON (1.0) FRM (C) TO (F); ON (F) FRM (1.0) TO (3.1); ON (G) FRM (1.0) TO (3.1); ON (1.0) FROM (G) TO (J); ON (J) FROM (1.0) TO (12.5); (16) COMPLETE; UPPER WALL @ (G) FROM (1) TO (12.5) + (15) TO (16); WALL SEGMENTS LISTEDBELOW
Correction
Resolved
05/25/2005
PREREQUISITE TO APPROVAL OF STRUCTURAL SYSTEM UL DESIGN #X536 APP'D FOR COUNCIL CHAMBER COLUMNS
Correction
Resolved
05/25/2005
READINESS FOR INSPECTION
Correction
Partial Correction
05/25/2005
LIGHT-GUAGE STEEL FRAMING -- EXT WALLS / PARAPET EAST (ARC) WALL OF COUNCIL CHAMBER; (15.3) FROM (A) TO (E.1); (F) FROM (15) TO (16); NOT APPROVED: (H.6) FROM (12.4) TO (16); OK TO COVER WHEN READY WALL SEGMENTS LISTEDBELOW
Rough Framing Inspection - Commercial Partial 06/01/2005
Correction
Partial Correction
06/01/2005
LIGHT-GUAGE STEEL FRAMING -- EXT WALLS / PARAPET EAST (ARC) WALL OF COUNCIL CHAMBER; (15.3) FROM (A) TO (E.1); (F) FROM (15) TO (16); (H.6) FROM (12.4) TO (16); (J) FROM (12.5) TO (16); OK TO COVER WHEN READY WALL SEGMENTS LISTEDBELOW
Rough Framing Inspection - Commercial Request Complete 5/31/2005 6/1/2005 06/01/2005
Rough Mechanical Inspection - Commercial Failed 06/03/2005
Correction
Corrective Action Required
06/03/2005
USE OF RADIUS HEEL HVAC DUCT ELBOW W/ SQUARE THROAT AIR FLOW DESIGN REQUIREMENTS AND CALCULATIONS. PROVIDE WRITTEN DOCUMENTATION. OBTAIN A/E CONFIRMATION FITTING COMPLIES WITH
All Rough Inspection - Commercial Failed 06/13/2005
Correction
Corrective Action Required
06/13/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR (16) TO (8) x (J) TO (G) FRAMING + ELECTRICAL ONLY READY FOR INSPECTION; PLUMBING INCOMPLETE: ENSURE ALL ELECTRICAL CONDUIT COUPLING NUTS ARE TIGHTENED; NO FRAMING ISSUES
Rough Plumbing Inspection - Commercial Partial 06/16/2005
Correction
Partial Correction
06/16/2005
ROOF DRAIN & OVERFLOW PIPING SUBSYSTEMS APPROVED: ALL FROM (1) TO (8): VISUAL + PRESSURE TEST ROOF DOWN TO 1ST FLOOR
Rough Framing Inspection - Commercial Request Complete 6/28/2005 6/29/2005 06/29/2005
All Rough Inspection - Commercial Partial 06/30/2005
Correction
Partial Correction
06/30/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR (16) TO (8) x (J) TO (G) FRAMING + ELECTRICAL ONLY READY FOR INSPECTION; PLUMBING INCOMPLETE: ENSURE ALL ELECTRICAL CONDUIT COUPLING NUTS ARE TIGHTENED; NO FRAMING ISSUES; STEEL FRAMING + PLMBG @ ENTRANCE ARCHES VEST 1.100 & 1.106;
Rough Framing Inspection - Commercial Request Complete 6/29/2005 6/30/2005 06/30/2005
Rough Plumbing Inspection - Commercial Passed 07/01/2005
Correction
Resolved
07/01/2005
1ST FLOOR WASTE & VENT VISUAL & PRESSURE TEST
Correction
Resolved
07/01/2005
1ST FLOOR ROOF DRAINS & OVERFLOW
Correction
Resolved
07/01/2005
ROOF DRAIN & OVERFLOW PIPING
Correction
Resolved
07/01/2005
2ND FLOOR WASTE & VENT PIPING VISUAL & PRESSURE TEST
Rough Plumbing Inspection - Commercial Passed 07/06/2005
Correction
Resolved
07/06/2005
ROOF DRAIN & OVERFLOW PIPING ALL PREVIOUS; EAST OF (F) x NORTH OF (12) VISUAL + PRESSURE TEST SUBSYSTEMS LISTED BELOW
Gas Piping Inspection - Commercial Partial 07/08/2005
Correction
Partial Correction
07/08/2005
FEEDER PIPING FROM METER @ FIRE DEPT HQ TO EAST EMERGENCY GENSET OK TO COVER & CONNECT WHEN READY PRESSURE TEST HELD STEADY AT >= 60 PSI FOR >=30 MIN
Rough Plumbing Inspection - Commercial Partial 07/15/2005
Correction
Partial Correction
07/15/2005
ROOF DRAIN & OVERFLOW PIPING ALL PREVIOUS; EAST OF (F) x NORTH OF (12); RD + O/F DOWN @ 1ST FLR J/15.1; RD DOWN @ 1ST FLR J/11.1; O/F DOWN @ 1ST FLR G.8/9.5; VISUAL + PRESSURE TEST SUBSYSTEMS LISTED BELOW
All Rough Inspection - Commercial Partial 08/03/2005
Correction
Partial Correction
08/03/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR (16) TO (8) x (J) TO (G) FRAMING + ELECTRICAL ONLY-- PLUMBING INCOMPLETE: ENSURE ALL ELECTRICAL CONDUIT COUPLING NUTS ARE TIGHTENED; NO FRAMING ISSUES; STEEL FRAMING + PLMBG @ ENTRANCE ARCHES VEST 1.100 & 1.106; COLUMNS @ (G) FROM (3) TO (14); OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Correction
Partial Correction
08/03/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR COLUMNS @ (G) FROM (3) TO (14); OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Rough Framing Inspection - Commercial Request Complete 8/2/2005 8/3/2005 08/03/2005
All Rough Inspection - Commercial Partial 08/26/2005
Correction
Partial Correction
08/26/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR (16) TO (8) x (J) TO (G) FRAMING + ELECTRICAL ONLY-- PLUMBING INCOMPLETE: ENSURE ALL ELECTRICAL CONDUIT COUPLING NUTS ARE TIGHTENED; NO FRAMING ISSUES; STEEL FRAMING + PLMBG @ ENTRANCE ARCHES VEST 1.100 & 1.106; COLUMNS @ (G) FROM (3) TO (14); OK TO COVER WHEN READY COMPONENTS LISTED BELOW
All Rough Inspection - Commercial Partial 08/30/2005
Correction
Partial Correction
08/30/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR (16) TO (8) x (J) TO (G); STEEL FRAMING + PLMBG @ ENTRANCE ARCHES VEST 1.100 & 1.106; COLUMNS @ (G) FROM (3) TO (14); ALL WEST OF (H.7); 1.198 W,S,E WALLS; 1.200; ALONG (G) OK TO GWB E FACE TOP DOWN TO SOFFIT ELEV + OK TO SHEATH FASCIA; OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Rated Assembly Inspection Partial 08/30/2005
Correction
Partial Correction
08/30/2005
ELEVATOR SHAFTS ELEV #1 & #2 OK TO GWB INSIDE FACE OF SHAFT WALLS; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 08/31/2005
Correction
Resolved
08/31/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR (16) TO (8) x (J) TO (G); STEEL FRAMING + PLMBG @ ENTRANCE ARCHES VEST 1.100 & 1.106; COLUMNS @ (G) FROM (3) TO (14); ALL WEST OF (H.7); 1.198 W,S,E WALLS; 1.200; ALONG (G) OK TO GWB E FACE TOP DOWN TO SOFFIT ELEV + OK TO SHEATH FASCIA; OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Correction
Partial Correction
08/31/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D (C)-(F) x (1)-(4.8); RMS 1.187; 1.195; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Gas Service Inspection - Commercial Passed 09/12/2005
Correction
Resolved
09/12/2005
TEST PRESSURE LEVEL RELEASE GAS SERVICE HELD STEADY AT 60 PSI FOR >=120 MIN
Rough Framing Inspection - Commercial Not Ready 09/14/2005
Correction
Corrective Action Required
09/14/2005
ROOFTOP MECHANICAL UNIT ENCLOSURES PARTIALLY COVERED. AT LOCATIONS NOT COVERED STUD FLANGES ARE NOT COMPLETELY SCREWED TO TRACKS. FRAMING NOT APPROVED NOT READY FOR INSPECTION
Rough Framing Inspection - Commercial Passed 09/15/2005
Correction
Resolved
09/15/2005
LIGHT-GUAGE STEEL FRAMING -- EXT WALLS / PARAPET EAST (ARC) WALL OF COUNCIL CHAMBER; (15.3) FROM (A) TO (E.1); (F) FROM (15) TO (16); (H.6) FROM (12.4) TO (16); (J) FROM (12.5) TO (16); OK TO COVER WHEN READY WALL SEGMENTS LISTEDBELOW
Correction
Resolved
09/15/2005
ROOFTOP MECHANICAL UNIT ENCLOSURES OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 09/16/2005
Correction
Partial Correction
09/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR COLUMNS @ (G) FROM (3) TO (14); EXT WALL @ (J) FROM (9.6) TO (12.0); SPACES 2.171-2.174; 2.187-2.191; 2.201; 2.205; 2.207; 2.208; 2.210; 2.211; 2.213-2.223; OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Above Ceiling Inspection Partial 09/21/2005
Correction
Partial Correction
09/21/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR 1.188-1.193; 1.175; 1.176; NOT APPROVED: CORRIDOR PATHS IN SPACES 1.172; 1.177; 1.185; 1.194; 1.198; OK TO COVER WHEN READY AREAS LISTED BELOW:
All Rough Inspection - Commercial Partial 09/21/2005
Correction
Partial Correction
09/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR COLUMNS @ (G) FROM (3) TO (14); EXT WALL @ (J) FROM (9.6) TO (12.0); SPACES 2.171-2.174; 2.187-2.191; 2.201; 2.205; 2.207; 2.208; 2.210; 2.211; 2.213-2.223; NOT APPROVED: 2.154; CHASE @ 2.186/2.192; OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Correction
Partial Correction
09/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D (C)-(F) x (1)-(4.8); 1.165; 1.180 W WALL; 1.187; 1.195; NOT APPROVED: 1.160; 1.164; 1.166; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 09/23/2005
Correction
Partial Correction
09/23/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR 1.172; 1.175; 1.176; 1.177; 1.185; 1.188-1.193; 1.194; 1.198; ABOVE PERIMETER CORRIDOR PATH IN 1.205, 206, 228, 223, 214 (EXCLUDING NE CORNER); ROOMS 211-213; 218-222; OK TO COVER WHEN READY AREAS LISTED BELOW:
All Rough Inspection - Commercial Partial 09/23/2005
Correction
Partial Correction
09/23/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR COLUMNS @ (G) FROM (3) TO (14); EXT WALL @ (J) FROM (9.6) TO (12.0); CHASE @ 2.186/2.192; SPACES 2.154; 2.171-2.174; 2.187-2.191; 2.201; 2.205; 2.207; 2.208; 2.210; 2.211; 2.213-2.223; OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Correction
Partial Correction
09/23/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D (C)-(F) x (1)-(4.8); 1.160; 1.164; 1.165; 1.166; 1.180 W WALL; 1.187; 1.195; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 10/10/2005
Correction
Partial Correction
10/10/2005
ELEVATOR SHAFTS ELEV #1 & #2 OK TO GWB INSIDE FACE OF SHAFT WALLS; HOISTWAY EL-1 INTERIOR FACE 1ST LAYER 5/8" TYPE X GWB EXCEPT TOP 24"; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
10/10/2005
RATED WALLS @ ELEVATOR EQUIPMENT ROOMS 1.165 INSIDE FACE 5/8" TYPE X GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 10/11/2005
Correction
Partial Correction
10/11/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR ALL SPACES EXCEPT N OF (12) x E OF (G), STAIR TOWER WALLS, FREE-STANDING PARTITIONS OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Correction
Partial Correction
10/11/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D (C)-(F) x (1)-(4.8); 1.160; 1.164; 1.165; 1.166; 1.180 W WALL; 1.187; 1.195; ALL SPACES EXCEPT N OF (12) x E OF (G), STAIR TOWER WALLS, FREE-STANDING PARTITIONS, CORRIDOR 1.163, COLUMNS (H/6.5) & (H/8) OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 10/12/2005
Correction
Partial Correction
10/12/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D (C)-(F) x (1)-(4.8); 1.160; 1.164; 1.165; 1.166; 1.180 W WALL; 1.187; 1.195; ALL SPACES EXCEPT N OF (12) x E OF (G), STAIR TOWER WALLS, FREE-STANDING PARTITIONS OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 10/14/2005
Correction
Partial Correction
10/14/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR 1.172; 1.175; 1.176; 1.177; 1.185; 1.188-1.193; 1.194; 1.198; ABOVE PERIMETER CORRIDOR PATH IN 1.205, 206, 228, 223, 214 (EXCLUDING NE CORNER); ROOMS 211-213; 218-222; (1)-(4.8) x (C)-(F.5); OK TO COVER WHEN READY AREAS LISTED BELOW:
Above Ceiling Inspection Partial 10/18/2005
Correction
Partial Correction
10/18/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.171; 172; 173; 174; 187; 188; 189; 190; 191; 205; 207; ABOVE CORRIDOR PATH IN 2.167; 2.186; 2.192; 2.208; OK TO COVER WHEN READY AREAS LISTED BELOW:
Rated Assembly Inspection Partial 10/18/2005
Correction
Partial Correction
10/18/2005
RATED WALLS @ ELEVATOR EQUIPMENT ROOMS 1.165 INSIDE FACE 5/8" TYPE X GWB; 1.160 INSIDE FACE TO GWB RATED CEILING LEVEL 5/8" TYPE X GWB -- OUTSIDE FACE NOT APPROVED; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
10/18/2005
WALLS AT STAIRWELLS ROOM 2.171 N WALL ROOM FACE ONLY; OK TO COVER WHEN READY WALLS LISTED BELOW:
All Rough Inspection - Commercial Partial 10/21/2005
Correction
Partial Correction
10/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR FREE-STANDING PARTITIONS; ALL SPACES EXCEPT N OF (12) x E OF (G), STAIR TOWER WALLS OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Correction
Partial Correction
10/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D FREE-STANDING PARTITIONS; ALL SPACES EXCEPT N OF (12) x E OF (G), STAIR TOWER WALLS OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 10/21/2005
Correction
Partial Correction
10/21/2005
ELEVATOR SHAFTS ELEV #1 & #2 OK TO GWB INSIDE FACE OF SHAFT WALLS; HOISTWAY EL-1 E,N,W,S WALLS INTERIOR FACE 5/8" TYPE X GWB EXCEPT TOP 24" OK TO TAPE & MUD; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
10/21/2005
RATED WALLS @ ELEVATOR EQUIPMENT ROOMS 1.165 INSIDE FACE 5/8" TYPE X GWB; 1.160 INSIDE & OUTSIDE FACE TO GWB RATED CEILING LEVEL 5/8" TYPE X GWB OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 10/28/2005
Correction
Partial Correction
10/28/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR 1.125; 127; 128; 135; 137; 138; 172; 175; 176; 177; 180; 185; 188-193; 194; 198; ABOVE PERIMETER CORRIDOR PATH IN 1.205, 206, 228, 223, 214 (EXCLUDING NE CORNER); ROOMS 211-213; 218-222; (1)-(4.8) x (C)-(F.5); 227; OK TO COVER WHEN READY AREAS LISTED BELOW:
Correction
Partial Correction
10/28/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.171; 172; 173; 174; 187; 188; 189; 190; 191; 198; 200; 205; 207; ABOVE CORRIDOR PATH IN 2.167; 2.186; 2.192; 2.208; OK TO COVER WHEN READY AREAS LISTED BELOW:
All Rough Inspection - Commercial Partial 11/04/2005
Correction
Partial Correction
11/04/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR FREE-STANDING PARTITIONS; ALL SPACES S OF (12); ALL SPACES W OF (G); 104-114; 115 EXCEPT E WALL; 116-119; 121; 123; STAIR WELL WALLS NOT YET INSPECTED OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Correction
Partial Correction
11/04/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D FREE-STANDING PARTITIONS; ALL SPACES S OF (12); ALL SPACES W OF (G); STAIR WELL WALLS NOT YET INSPECTED OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 11/04/2005
Correction
Partial Correction
11/04/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR SPACES: 1.125; 127; 128; 135; 137; 138; 164; 165; 172; 175; 176; 177; 180; 185; 188-193; 194; 198; ABOVE PERIMETER CORRIDOR PATH IN 1.205, 206, 228, 223, 214 (EXCLUDING NE CORNER); ROOMS 211-213; 218-222; (1)-(4.8) x (C)-(F.5); 227; AND GWB CEILING AREAS OK TO COVER WHEN READY
Correction
Partial Correction
11/04/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.136-138; 142; 143; 167; 171-174; 185; 186-192; 193; 197; 198; 199; 200; 205; 207; 208; 209; 210; AND GWB CEILING AREAS OK TO COVER WHEN READY
Above Ceiling Inspection Partial 11/08/2005
Correction
Partial Correction
11/08/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR SPACES: 1.125; 127; 128; 135; 137; 138; 164; 165; 175; 176; 177; 180; 183; 185; 188-193; 194; 198; 203-204; 205-206; 211-213; 214 (EXCL NE CORNER); 218-223; (1)-(4.8) x (C)-(F.5); 227; 228; AND GWB CEILING AREAS OK TO COVER WHEN READY
Correction
Partial Correction
11/08/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.114; 126; 127-131; 136-138; 142-143; 167; 171-174; 185-193; 195; 197-200; 205; 207-210; AND GWB CEILING AREAS OK TO COVER WHEN READY
Above Ceiling Inspection Partial 11/15/2005
Correction
Partial Correction
11/15/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR SPACES: 1.117; 125; 126; 127; 128; 132; 133; 135; 136; 137; 138; 164; 165; 172; 173; 175; 176; 177; 180; 183; 185; 188-193; 194; 198; 203-204; 205-206; 211-213; 214 (EXCL NE CORNER); 218-223; (1)-(4.8) x (C)-(F.5); 227; 228; AND GWB CEILING AREAS OK TO COVER WHEN READY
Correction
Partial Correction
11/15/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.114; 126-131; 132; 135; 136-138; 142-143; 147; 148; 167; 171-174; 178; 182; 185-193; 195; 197-200; 205; 207-210; AND GWB CEILING AREAS OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 11/15/2005
Correction
Partial Correction
11/15/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D FREE-STANDING PARTITIONS; ALL SPACES S OF (12); ALL SPACES W OF (G); (F)-(G) x (12)-(16); STAIR WELL WALLS NOT YET INSPECTED OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 11/15/2005
Correction
Resolved
11/15/2005
FLOOR-TO-FLOOR FIRE SAFING + FIRE-CAULKING PER STI N216503JL SYSTEM -- CAT CUT PROVIDED AT COUNCIL CHAMBER EXTERIOR WALLS
Above Ceiling Inspection Partial 11/23/2005
Correction
Partial Correction
11/23/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.114; 126-132; 135; 136-138; 142-143; 144-146; 147-148; 149; 159; 163; 165; 167; 171-174; 178; 182; 185-193; 195; 197-200; 205; 207-210; AND GWB CEILING AREAS OK TO COVER WHEN READY
Rough Framing Inspection - Commercial Passed 12/01/2005
Correction
Resolved
12/01/2005
FALSE WALL HIGH ALONG (G) PER DETAIL 6/2.1 OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/01/2005
Correction
Partial Correction
12/01/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR SPACES: 1.117; 125-128; 132-133; 135-138; 144; 145; 164-165; 167; 172-173; 175-177; 180; 183; 185; 188-194; 198; 202; 203-206; 208; 209; 211; 212-214 (EXCL NE CORNER); 218-223; (1)-(4.8) x (C)-(F.5); 227-228; AND GWB CEILING AREAS OK TO COVER WHEN READY
Rated Assembly Inspection Partial 12/01/2005
Correction
Partial Correction
12/01/2005
RATED WALL FROM (F/12) TO (F/15) OK TO TAPE, MUD, & FIRE-SEAL EXCEPT WINDOW WALL AREA 5/8" TYPE X GWB
All Rough Inspection - Commercial Partial 12/01/2005
Correction
Partial Correction
12/01/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR FREE-STANDING PARTITIONS; ALL SPACES S OF (12); ALL SPACES W OF (G); 104-114; 115 EXCEPT E WALL; 116-119; 121; 123; OK TO COVER WHEN READY COMPONENTS LISTED BELOW
Correction
Partial Correction
12/01/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D FREE-STANDING PARTITIONS; ALL SPACES S OF (12); ALL SPACES W OF (G); (F)-(G) x (12)-(16); OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
12/01/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH @ STAIRWELLS CLEAN ALL CAVITIES / DEAD SPACES; ENSURE THERMAL INSULATION IS IN PLACE & FOIL FACE IS INTACT OK TO COVER WHEN READY ST-1; ST-2; ST-3
Rated Assembly Inspection Partial 12/12/2005
Correction
Partial Correction
12/12/2005
FASTENING SCHEDULE OK TO TAPE & MUD INSIDE OF STAIRWELL AT ST-3 (2ND FLOOR) FASTENING REQUIRED AT CORR. 2.161 - BEHIND MECHANICAL PIPING STAIRS @ ST-3, 2.161 2ND FLOOR
Above Ceiling Inspection Partial 12/12/2005
Correction
Corrective Action Required
12/12/2005
SOFFIT AREAS 2.116, 2.119, 2.123, 2.117, CORR. 2.101 REQUESTING THAT FIRE SPRINKLER SYSTEM BE COMPLETE BEFOREABOVE CEILING MAY BE COVERED SOFFIT FRAMING & UTILITIE OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/16/2005
Correction
Partial Correction
12/16/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR SPACES: 1.117; 125-128; 132-133; 135-138; 144; 145; 164-165; 167; 172-173; 175-177; 180; 183; 185; 188-194; 198; 202; 203-205; 206; 208; 209; 211; 212-214 (EXCL NE CORNER); 218-223; (1)-(4.8) x (C)-(F.5); 227-228; HIGH CEILINGS ABOVE LOBBIES 101 & 105; AND GWB CEILING AREAS OK TO COVER WHEN READY
Correction
Partial Correction
12/16/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.101; 114; 116; 117; 119; 123; 126-132; 135-138; 142-149; 159; 160; 163; 165; 167; 171-174; 178; 182; 185-193; 195; 197-200; 205; 207-210; HIGH SOFFIT/FASCIA @ (F):(12)-(14) + (F.5):(3)-(4.8); AND GWB CEILING AREAS OK TO COVER WHEN READY
Correction
Resolved
12/16/2005
SOFFIT AREAS OK TO PLACE GYP BOARD LID FOR ELECTRICAN TO INSTALL FIXTURES BELOW LIVERS HANDRAIL ALL LOCATIONS
Above Ceiling Inspection Partial 12/27/2005
Correction
Partial Correction
12/27/2005
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR SPACES: 1.117; 125-128; 132-133; 135-138; 144; 145; 164-165; 167; 172-173; 175-177; 180; 183; 185; 188-194; 198; 202; 203-205; 206; 208; 209; 211; 212-214 (EXCL NE CORNER); 218-223; (1)-(4.8) x (C)-(F.5); 227-228; HIGH CEILINGS ABOVE LOBBIES 101 & 105; AND GWB CEILING AREAS OK TO COVER WHEN READY
Correction
Resolved
12/27/2005
SOFFIT AREAS RMS - 1.109(RADIUS SOFFIT AREAS ONLY), 1.114A, 1.115, ST-1 (HARDLID APPROVED TO EDGE OF STAIRS FOR REMOVAL OF SCAFFOLDING) ST-2, 2.212 OK TO COVER HARD LIDS ONLY
Above Ceiling Inspection Partial 12/29/2005
Correction
Resolved
12/29/2005
SOFFIT AREAS RMS - 1.109(RADIUS SOFFIT AREAS ONLY), 1.114A, 1.115, ST-1 (HARDLID APPROVED TO EDGE OF STAIRS FOR REMOVAL OF SCAFFOLDING) ST-2, 2.212 OK TO COVER HARD LIDS ONLY
Correction
Resolved
12/29/2005
ABOVE CEILING RM # = 1.101A, 1.107, 1.114A, 1.114, 1.113, 1.116, 2.115, (LOBBY)1.101,1.103, 1.105 OK TO COVER HARD LID ONLY
Rough Plumbing Inspection - Commercial Passed 01/02/2006
Correction
Resolved
01/02/2006
1ST FLOOR WASTE & VENT
Correction
Resolved
01/02/2006
ROOF DRAIN & OVERFLOW PIPING
Correction
Resolved
01/02/2006
2ND FLOOR WASTE & VENT PIPING
Gas Piping Inspection - Commercial Passed 01/02/2006
Correction
Resolved
01/02/2006
FEEDER PIPING FROM METER @ FIRE DEPT HQ TO EAST EMERGENCY GENSET PRESSURE TEST HELD STEADY AT >= 60 PSI FOR >=30 MIN
Rough Mechanical Inspection - Commercial Passed 01/02/2006
Correction
Resolved
01/02/2006
USE OF RADIUS HEEL HVAC DUCT ELBOW W/ SQUARE THROAT
Rated Assembly Inspection Passed 01/02/2006
Correction
Resolved
01/02/2006
ELEVATOR SHAFTS
Correction
Resolved
01/02/2006
RATED WALLS @ ELEVATOR EQUIPMENT ROOMS
Correction
Resolved
01/02/2006
WALLS AT STAIRWELLS
Correction
Resolved
01/02/2006
FLOOR-TO-FLOOR FIRE SAFING + FIRE-CAULKING
Correction
Resolved
01/02/2006
RATED WALL FROM (F/12) TO (F/15)
Correction
Resolved
01/02/2006
FASTENING SCHEDULE
Above Ceiling Inspection Partial 01/06/2006
Correction
Partial Correction
01/06/2006
LAY-IN CEILING SPACES -- 2ND FLOOR 2.174; 188; 189; 190; 191; 194; 201; 205; 206; 207; NOT APP'D: 186/192; 187; 200; 208 OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Corrective Action Required
01/06/2006
LAY-IN CEILING SPACES -- 1ST FLOOR NOT APPROVED: (C) TO (F) x (1) TO (4.8)
Above Ceiling Inspection Partial 01/10/2006
Correction
Partial Correction
01/10/2006
GWB CEILINGS @ TOP OF STAIRWELLS STAIRWELL #3; OK TO COVER WHEN READY CEILINGS LISTED BELOW:
Above Ceiling Inspection Partial 01/11/2006
Correction
Partial Correction
01/11/2006
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR 1.117; 125-128; 132-133; 135-138; 144; 145; 164-165; 167; 172-173; 175-177; 180; 183; 185; 188-194; 198; 202; 203-205; 206; 208; 209; 211; 212-214 (EXCL NE CORNER); 218-223; (1)-(4.8) x (C)-(F.5); 227-228; HIGH CEILINGS ABOVE LOBBIES 101 & 105; CONT'D AND GWB CEILING AREAS OK TO COVER WHEN READY
Correction
Partial Correction
01/11/2006
LAY-IN CEILING SPACES -- 2ND FLOOR 2.174; 188; 189; 190; 191; 194; 201; 205; 206; 207; 186/192; 187; 200; 208; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
01/11/2006
LAY-IN CEILING SPACES -- 1ST FLOOR (1) TO (4.8) x (C) TO (F) EXCEPT ONE TILE EACH IN 221 + 216 FOR COMPLETION/CORRECTION OF SPRINKLER HEADS; OK TO COVER WHEN READY CEILING AREA LISTED BELOW
Correction
Partial Correction
01/11/2006
GWB CEILING/SOFFIT FRAMING + ABOVE CEILING SYSTEMS -- 1ST FLR, CONT'D FRAMING ONLY OK @ VESTIBULES 102 + 104; 116; BOTTOM OF STAIRWELL #3; OK TO COVER WHEN READY CEILING AREA LISTED BELOW
Above Ceiling Inspection Partial 01/12/2006
Correction
Partial Correction
01/12/2006
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.101; 114; 116; 117; 119; 123; 126-132; 135-138; 142-149; 159; 160; 163; 165; 167; 171-174; 178; 182; 185-193; 195; 197-200; 205; 207-210; HIGH SOFFIT/FASCIA @ (F):(12)-(14) + (F.5):(3)-(4.8); NOT APP'D: 166 AND GWB CEILING AREAS OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/13/2006
Correction
Corrective Action Required
01/13/2006
DRYWALL AND DROP CEILING 1ST FLOOR- RM 1.110 APPROVED TO HARD LID, MINUS CAMERA AREA DETAIL TO BE ON SIGHT FROM ARCHITECT AT REINSPECTION 2ND FLOOR - HARD LID @ 2.166 (PERIMETER OF ROOM) DROP CEILING @ 2.167, 2.168 & 2.169 1ST & 2ND FLOORS OK TO COVER
Above Ceiling Inspection Partial 01/19/2006
Correction
Partial Correction
01/19/2006
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.101; 101A; 114; 116; 117; 119; 123; 126-132; 135-138; 142-149; 159; 160; 163; 165; 167; 171-174; 178; 182; 185-193; 195; 197-200; 205; 207-210; HIGH SOFFIT/FASCIA @ (F):(12)-(14) + (F.5):(3)-(4.8); NOT APP'D: 166 AND GWB CEILING AREAS OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/20/2006
Correction
Partial Correction
01/20/2006
GWB CEILING/SOFFIT FRAMING + ABOVE CEILING SYSTEMS -- 1ST FLR, CONT'D FRAMING ONLY OK @ VESTIBULES 102 + 104; 116; BOTTOM OF STAIRWELL #3; VESTIBULES 102 & 104; OK TO COVER WHEN READY CEILING AREA LISTED BELOW
Above Ceiling Inspection Partial 01/26/2006
Correction
Partial Correction
01/26/2006
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR ROOMS 2.101; 101A; 114; 116; 117; 119; 123; 126-132; 135-138; 142-149; 159; 160; 163; 165; 167; 171-174; 178; 182; 185-193; 195; 197-200; 205; 207-210; HIGH SOFFIT/FASCIA @ (F):(12)-(14) + (F.5):(3)-(4.8); 113; NOT APP'D: 166 AND GWB CEILING AREAS OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 01/26/2006
Correction
Partial Correction
01/26/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D FREE-STANDING PARTITIONS; ALL SPACES S OF (12); ALL SPACES W OF (G); (F)-(G) x (12)-(16); KNEE WALL @ 1.183 OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rough Framing Inspection - Commercial Request Complete 1/25/2006 1/26/2006 01/26/2006
Footing Inspection - Commercial Partial 02/08/2006
Correction
Partial Correction
02/08/2006
PLANTER & BENCH WALL FOOTINGS @ COURTYARD AS REVISED BY PR-16: PLANTER WALL @ COURTYARD SOUTH; OK TO POUR WHEN READY COMPONENTS LISTED BELOW:
Footing Inspection - Commercial Partial 02/09/2006
Correction
Partial Correction
02/09/2006
PLANTER & BENCH WALL FOOTINGS @ COURTYARD AS REVISED BY PR-16: PLANTER WALL @ COURTYARD SOUTH; SW ARC PLANTER WALL; OK TO POUR WHEN READY COMPONENTS LISTED BELOW:
Footing Inspection - Commercial Partial 02/10/2006
Correction
Partial Correction
02/10/2006
PLANTER & BENCH WALL FOOTINGS @ COURTYARD AS REVISED BY PR-16: PLANTER WALL @ COURTYARD SOUTH; SW ARC PLANTER WALL; INNER ARC PLANTER WALL; OK TO POUR WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
02/10/2006
WALL SPREAD FOOTINGS @ AMPITHEATER AS MODIFIED BY PR-1: SE WALL FOOTING; OK TO POUR WHEN READY COMPONENTS LISTED BELOW
Footing Inspection - Commercial Partial 02/14/2006
Correction
Partial Correction
02/14/2006
RETAINING WALL FOOTING @ COURTYARD EAST NORTH 72' POURED WITHOUT INSPECTION;
Above Ceiling Inspection Partial 02/15/2006
Correction
Partial Correction
02/15/2006
LAY-IN CEILING SPACES -- 1ST FLOOR 122; 124; 125; 127; 169; 172 S OF (8); 173-176; 179; 178; 177; 185-200; 205; 207-209; 211-214; 216-226; OK TO COVER WHEN READY CEILING AREA LISTED BELOW
All Rough Inspection - Commercial Partial 02/15/2006
Correction
Partial Correction
02/15/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D FREE-STANDING PARTITIONS; ALL SPACES S OF (12); ALL SPACES W OF (G); (F)-(G) x (12)-(16); KNEE WALL @ 183; KNEE WALL @ 1.206; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Footing Inspection - Commercial Partial 02/16/2006
Correction
Resolved
02/16/2006
See Comment GREEN STREET SIDE OF PROJECT - STEP FOOTING & SOUTH SECTION - RETAINING WALL DETAILS NOT ON PLANS - DETAILS INDICATED ON PR 16 AS 3 #5 REBAR IN A 2'3" TRENCH INSTALLED AS ABOVE - POUR AT OWN RISK
Footing Inspection - Commercial Passed 02/22/2006
Correction
Resolved
02/22/2006
PLANTER & BENCH WALL FOOTINGS @ COURTYARD AS REVISED BY PR-16: PLANTER WALL @ COURTYARD SOUTH; SW ARC PLANTER WALL; INNER ARC PLANTER WALL; NE PLANTER WALLS AS MODIFIED BY PR-1
Correction
Resolved
02/22/2006
WALL SPREAD FOOTINGS @ AMPITHEATER AS MODIFIED BY PR-1
Correction
Resolved
02/22/2006
RETAINING WALL FOOTING @ COURTYARD EAST
Correction
Resolved
02/22/2006
See Comment
Above Ceiling Inspection Partial 02/27/2006
Correction
Partial Correction
02/27/2006
LAY-IN CEILING SPACES -- 1ST FLOOR 122; 124; 125; 127; 169; 172 S OF (8); 173-176; 179; 178; 177; 185-200; 205; 207-209; 211-214; 216-226; OPEN AREA G-J x 3-8 EXCLUDING @ ROLLING SHUTTERS & DOOR HEATERS; OK TO COVER WHEN READY CEILING AREA LISTED BELOW
All Rough Inspection - Commercial Passed 02/27/2006
Correction
Resolved
02/27/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR
Correction
Resolved
02/27/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR
Correction
Resolved
02/27/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR, CONT'D
Correction
Resolved
02/27/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH @ STAIRWELLS
Above Ceiling Inspection Partial 03/02/2006
Correction
Partial Correction
03/02/2006
LAY-IN CEILING SPACES -- 2ND FLOOR 2.127-132; 134-138; 142-143; 150-152; 174; 188; 189; 190; 191; 194; 201; 205; 206; 207; 186/192; 187; 200; 208; OK TO COVER WHEN READY SPACES LISTED BELOW:
Issue Temporary C of O Complete 3/3/2006 3/6/2006 03/06/2006
Above Ceiling Inspection Partial 03/15/2006
Above Ceiling Inspection Partial 03/16/2006
Correction
Partial Correction
03/16/2006
GWB CEILING/SOFFIT FRAMING + ABOVE CEILING SYSTEMS -- 1ST FLR, CONT'D FRAMING ONLY OK @ VESTIBULES 102 + 104; 116; BOTTOM OF STAIRWELL #3; VESTIBULES 102 & 104; SOUTH + NORTH ENTRANCE VESTIBULES OK TO COVER WHEN READY CEILING AREA LISTED BELOW
Above Ceiling Inspection Partial 03/20/2006
Correction
Partial Correction
03/20/2006
LAY-IN CEILING SPACES -- 2ND FLOOR 2.105; 110; 111; 112; 114; 118; 124; 125; 127-132; 134-138; 142-143; 150-152; 174; 188; 189; 190; 191; 194; 201; 205; 206; 207; 186/192; 187; 200; 208; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
03/20/2006
LAY-IN CEILING SPACES -- 1ST FLOOR 109 @ (E.4/13.5); 114; 122; 124; 125; 127; 141; 144; 147; 169; 172 S OF (8); 173-176; 179; 178; 177; 185-200; 205; 207-209; 211-214; 216-226; OPEN AREA G-J x 3-8 EXCLUDING @ ROLLING SHUTTERS & DOOR HEATERS; OK TO COVER WHEN READY CEILING AREA LISTED BELOW
Occupancy Inspection - Codes Commercial Not Ready 03/24/2006
Correction
Corrective Action Required
03/24/2006
Receive Fire Department approval
Correction
Corrective Action Required
03/24/2006
Receive Planning & Development Approval
Correction
Corrective Action Required
03/24/2006
Receive Public Works Approval
Correction
Corrective Action Required
03/24/2006
Receive Water Utilities Approval
Correction
Corrective Action Required
03/24/2006
STATE ELEVATOR INSPECTION PROVIDE COPY OF REPORT WHEN INSPECTION APPROVED
Occupancy Inspection - Codes Commercial Not Ready 03/27/2006
Correction
Resolved
03/27/2006
Receive Water Utilities Approval PER BEN HASKAMP 3/24/06
Occupancy Inspection - Codes Commercial Not Ready 03/28/2006
Correction
Corrective Action Required
03/28/2006
USE OF FACILITY FOR RIBBON-CUTTING CEREMONY ACCESS TO SPECIFIED AREAS TO BE CONTROLLED BY STAFF. TO BE HELD 4/1/06 CERTAIN AREAS ONLY
Occupancy Inspection - Codes Commercial Not Ready 03/29/2006
Occupancy Inspection - Codes Commercial Not Ready 03/30/2006
Correction
Partial Correction
03/30/2006
Receive Fire Department approval INSPECTION ONGOING
Correction
Corrective Action Required
03/30/2006
Receive Planning & Development Approval NOT READY FOR INSPECTION
Correction
Corrective Action Required
03/30/2006
Receive Public Works Approval NOT READY FOR INSPECTION
Correction
Resolved
03/30/2006
USE OF FACILITY FOR RIBBON-CUTTING CEREMONY ACCESS TO SPECIFIED AREAS TO BE CONTROLLED BY CITY STAFF. OK TO BE HELD 4/1/06 CERTAIN AREAS ONLY
Occupancy Inspection - Codes Commercial Failed 04/05/2006
Correction
Resolved
04/05/2006
STATE ELEVATOR INSPECTION PROVIDE COPY OF REPORT WHEN INSPECTION APPROVED
Correction
Partial Correction
04/05/2006
Means of Egress Temporary egress paths have been installed. All temporary egress paths shall be maintained to public way, free from obstructions and tripping hazards. Temporary fence shall be maintained to prevent public access to designated construction areas.
Correction
Corrective Action Required
04/05/2006
Means of Egress Provide permanent means of egress and exit discharge per the approved plans. Exterior
Correction
Corrective Action Required
04/05/2006
Occupancy Areas Inspected: Water Utilities, ITS, Parks, Public Works, Council Chamber and conference area and Lobby. This project is subject to further violations. Other areas not listed shall be inspected prior to occupancy.
Occupancy Inspection - Codes Commercial Failed 05/15/2006
Above Ceiling Inspection Passed 06/07/2006
Correction
Resolved
06/07/2006
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 1ST FLOOR
Correction
Resolved
06/07/2006
GWB SOFFIT FRAMING + ABOVE-SOFFIT SYSTEMS ROUGH -- 2ND FLOOR
Correction
Resolved
06/07/2006
SOFFIT AREAS
Correction
Resolved
06/07/2006
SOFFIT AREAS
Correction
Resolved
06/07/2006
ABOVE CEILING
Correction
Resolved
06/07/2006
LAY-IN CEILING SPACES -- 2ND FLOOR
Correction
Resolved
06/07/2006
LAY-IN CEILING SPACES -- 1ST FLOOR
Correction
Resolved
06/07/2006
GWB CEILINGS @ TOP OF STAIRWELLS
Correction
Resolved
06/07/2006
GWB CEILING/SOFFIT FRAMING + ABOVE CEILING SYSTEMS -- 1ST FLR, CONT'D
Correction
Resolved
06/07/2006
DRYWALL AND DROP CEILING
Occupancy Inspection - Codes Commercial Failed 06/07/2006
Correction
Resolved
06/07/2006
Means of Egress
Occupancy Inspection - Codes Commercial Failed 06/09/2006
Correction
Partial Correction
06/09/2006
Means of Egress Egress approved for use. Stairs at north entrance not complete. Ramp approved.
Correction
Corrective Action Required
06/09/2006
Occupancy Areas Inspected: Water Utilities, ITS, Parks, Public Works, Council Chamber and conference area and Lobby, Codes Administration, Planning. This project is subject to further violations. Other areas not listed shall be inspected prior to occupancy.
Occupancy Inspection - Codes Commercial Failed 06/26/2006
Correction
Corrective Action Required
06/26/2006
Occupancy Areas Inspected: Water Utilities, ITS, Parks, Public Works, Council Chamber and conference area and Lobby, Codes Administration, Planning. This project is subject to further violations. Other areas not listed shall be inspected prior to occupancy.
Occupancy Inspection - Codes Commercial Failed 06/27/2006
Correction
Partial Correction
06/27/2006
Occupancy Areas Inspected: Water Utilities, ITS, Parks, Public Works, Council Chamber and conference area and Lobby, Codes Administration, Planning. This project is subject to further violations. Other areas not listed shall be inspected prior to occupancy.
Correction
Corrective Action Required
06/27/2006
SUPPORT OF FIRE PROTECTION VALVE/REGULATOR ASSEMBLIES PEDESTALS NOT SECURED TO FLOOR SLAB
Correction
Corrective Action Required
06/27/2006
INSTALLATION OF ELECTRICAL RECEPTACLES/SWITCHES NEC 380-10; 410-56(f) EXAMPLE: ADMIN AREA (POINTED OUT) SOME NOT TIGHT TO BOX
Correction
Corrective Action Required
06/27/2006
FIRE PROTECTION SPRINKLER HEAD ESCUTCHEONS ELEVATOR EQUIPMENT ROOM #1 SOME NOT IN PLACE LOCATIONS INDICATED BELOW
Correction
Corrective Action Required
06/27/2006
ELECTRICAL PANEL SCHEDULES PANEL 1L1: SLEEVE NOT INTACT PANEL 1H1: POSTION #'S NOT IDENTIFIED **CHECK ALL PANELS** INCOMPLETE / INCORRECT LOCATIONS INDICATED BELOW
Correction
Corrective Action Required
06/27/2006
SET-BACK OF ELECTRICAL RECEPTACLE/SWITCH BOXES IN WALL NEC 370-20; IRC E3806.6: 4 @ DEVELOPMENT CENTER BELOW PUBLIC COUNTER; BOXES NOT FLUSH WITH COMBUSTIBLE WALL SURFACE
Occupancy Inspection - Codes Commercial Failed 06/28/2006
Correction
Corrective Action Required
06/28/2006
ROOFTOP INSPECTION 1) LIGHTNING PROTECTION SUBJECT TO APPROVAL 2) LATCHES/LOCKS ON MECH MEZZANINE DOORS -- ADJUST 3) SEAL ALL PENETRATIONS 4) CLEAR/CLEAN ALL MATERIAL+ ISSUES LISTED BELOW:
Occupancy Inspection - Codes Commercial Failed 06/29/2006
Correction
Partial Correction
06/29/2006
Receive Fire Department approval INSPECTION ONGOING
Correction
Corrective Action Required
06/29/2006
Receive Planning & Development Approval NOT READY FOR INSPECTION
Correction
Corrective Action Required
06/29/2006
Receive Public Works Approval NOT READY FOR INSPECTION
Correction
Resolved
06/29/2006
Receive Water Utilities Approval PER BEN HASKAMP 3/24/06
Correction
Corrective Action Required
06/29/2006
STATE ELEVATOR INSPECTION PROVIDE COPY OF REPORT
Correction
Resolved
06/29/2006
USE OF FACILITY FOR RIBBON-CUTTING CEREMONY
Correction
Resolved
06/29/2006
Means of Egress
Correction
Resolved
06/29/2006
Means of Egress
Correction
Partial Correction
06/29/2006
Occupancy SEE TEMPORARY OCCUPANCY
Correction
Corrective Action Required
06/29/2006
ROOFTOP INSPECTION 1) LIGHTNING PROTECTION CONNECTIONS @ RD BASKETS NOT TIGHT 2) LATCHES/LOCKS ON MECH MEZZANINE DOORS -- ADJUST 3) SEAL ALL PENETRATIONS -- SEE M/E/P CHASE PROJECTION 4) SHEET METAL PARAPET TRIM LOOSE @ F.5/4.8 5) SCREWS LOOSE @ MCQUAY UNITS CLEAR/CLEAN ALL MATERIAL+ ISSUES LISTED BELOW:
Occupancy Inspection - Codes Commercial Failed 07/06/2006
Occupancy Inspection - Codes Commercial Failed 07/07/2006
Occupancy Inspection - Codes Commercial Failed 07/20/2006
Occupancy Inspection - Codes Commercial Failed 07/20/2006
Correction
Resolved
07/20/2006
STATE ELEVATOR INSPECTION CERTIFICATE ON-SITE
Correction
Resolved
07/20/2006
Occupancy SEE TEMPORARY OCCUPANCY
Correction
Resolved
07/20/2006
SUPPORT OF FIRE PROTECTION VALVE/REGULATOR ASSEMBLIES
Correction
Resolved
07/20/2006
INSTALLATION OF ELECTRICAL RECEPTACLES/SWITCHES
Correction
Resolved
07/20/2006
FIRE PROTECTION SPRINKLER HEAD ESCUTCHEONS
Correction
Resolved
07/20/2006
ELECTRICAL PANEL SCHEDULES
Correction
Resolved
07/20/2006
SET-BACK OF ELECTRICAL RECEPTACLE/SWITCH BOXES IN WALL
Correction
Resolved
07/20/2006
ROOFTOP INSPECTION
Occupancy Inspection - Codes Commercial Failed 08/21/2006
Correction
Resolved
08/21/2006
Receive Fire Department approval PER KEITHMARTIN ~ 8/14/06
Correction
Corrective Action Required
08/21/2006
Receive Planning & Development Approval
Correction
Corrective Action Required
08/21/2006
Receive Public Works Approval
Correction
Resolved
08/21/2006
STATE ELEVATOR INSPECTION CERTIFICATE RECEIVED
Correction
Resolved
08/21/2006
Occupancy
Occupancy Inspection - Codes Commercial Failed 10/11/2006
Occupancy Inspection - Codes Commercial Failed 10/18/2006
Correction
Resolved
10/18/2006
Receive Planning & Development Approval PER M GORECKI 10/17/06
Occupancy Inspection - Codes Commercial Failed 12/11/2007
Correction
Corrective Action Required
12/11/2007
Receive Public Works Approval U.G. AS-BUILT DRAWINGS ACCEPTANCE PENDING
Occupancy Inspection - Codes Commercial Passed 04/02/2008
Correction
Resolved
04/02/2008
Receive Public Works Approval NO REMAINING ISSUES KNOWN
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.