Summary
B0400663
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW COMMERCIAL
FULL PERMIT BLDG E
04/20/2004
07/21/2004
01/17/2005
04/21/2005
Locations
Contacts
ACI BOLAND, Address:11229 NALL SUITE 140  
JE DUNN CONSTRUCTION CO., Address:929 HOLMES  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/17/2004 10/29/2010
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

Fire Department: Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators, and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Documentation shall be provided of the pressure test of at least 150 psi for a minimum of 24 hours on installers letterhead.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department: Medical Gas Storage Room (114). A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by not less than 1-hour-rated fire-resistance rated construction. Openings between the room or enclosure and interior spaces shall be self-closing smoke and draft-control assemblies having a fire protection rating of not less than 1-hour. Rooms shall have at least one exterior wall which is provided with at least two vents. Each vent shall not be less than 36 square inches in area. One vent shall be within 6 inches of the floor and one shall be within 6 inches of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire. IFC 3006.2.1
Correction

CA - The door numbers are not shown on the floor plans.
Correction

CA - 2000 IBC 407.3 - Corridor walls. Corridor walls shall form a barrier to limit the transfer of smoke. The walls shall extend from the floor to the underside of the floor or roof deck above or to the underside of the ceiling above where the ceiling membrane is constructed to limit the transfer of smoke. Corridor walls shall be constructed of materials consistent with the building type of construction and form a barrier to limit the transfer of smoke.
Correction

CA - 2000 IBC 407.3.1 Corridor doors. Corridor doors, other than those in a wall required to be rated by Section 302.1.1 or for the enclosure of a vertical opening or an exit, shall not have a required fire protection rating and shall not be required to be equipped with self-closing or automatic-closing devices, but shall provide an effective barrier to limit the transfer of smoke and shall be equipped with postive latching. Roller latches are not permitted. Other doors shall conform to Section 714.2.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

CA - 2000 IBC 407.4.1 - Refuge area. At least 30 net square feet per patient shall be provided within the aggregate area of corridors, patient rooms, treatment rooms, lounge or dining areas and other other low-hazard areas on each side of each smoke barrier. On floors not houseing patients confined to a bed or litter, at least 6 net square feet per occupant shall be provided on each side of each smoke barrier for the total number of occupants in adjoining smoke compartment.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - The ratings of the doors on the schedule uses a letter designation rather than a minute rating.
Correction

CA - Provide a copy of the comments for the mechanical, electrical and plumbing work from the consultants.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

St. Lukes - A Proprtionate Share of the Total Road Contribution shall be made to the City at or before the time a certificate of occupancy is issued by the City for a building constructed by, or by a building contractor on behalf of, the Developer on the Property, excluding the medical office buildings.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 715.2 - Installation. Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling dampers located in air distribution and smoke-control systems shall be installed in accordance with the requirements of this section, the manufacturer's installation instructions and listings.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

St. Lukes - The City shall not issue any temporary or final Certificate of Occupancy for any structure in the Developerment until a Certificate of Substantial Completion for the Road Improvements has been issued by MoDOT.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - 2000 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $15,476.05 $15,476.05 Paid 07/21/2004
24 BLDG Plan Check Fees $277.90 $277.90 Paid 07/21/2004
25 Electrical Permit Fee $1,299.25 $1,299.25 Paid 07/21/2004
25 Mechanical Permit Fees $259.00 $259.00 Paid 07/21/2004
25 Plumbing Permit Fees $274.00 $274.00 Paid 07/21/2004
84 Water Meters $2,325.24 $2,325.24 Paid 07/21/2004
85 Water Taps $27,285.00 $27,285.00 Paid 07/21/2004
89 Sewer Tap Fees $1,410.00 $1,410.00 Paid 07/21/2004
Road and Bridge Escrow $6,257.40 $6,257.40 Paid 02/01/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Framing Inspection - Commercial Partial 07/14/2004
Correction
Partial Correction
07/14/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL E/5; ENSURE RE-BAR COVERAGE D/3; D/4; D/5; E/3; E/4;
Rough Framing Inspection - Commercial Partial 07/15/2004
Correction
Partial Correction
07/15/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL E/5; D/2; D/3; ENSURE RE-BAR COVERAGE D/3; D/4; D/5; E/3; E/4;
Rough Framing Inspection - Commercial Partial 07/16/2004
Correction
Partial Correction
07/16/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 07/21/2004
Correction
Partial Correction
07/21/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 07/26/2004
Correction
Partial Correction
07/26/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 07/27/2004
Correction
Partial Correction
07/27/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 07/28/2004
Correction
Partial Correction
07/28/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; G/3; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 07/29/2004
Correction
Partial Correction
07/29/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; G/3; A/4; A/5; B/5; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 08/02/2004
Correction
Partial Correction
08/02/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; G/3; A/4; A/5; B/5; B/6; D.6/7; D.9/7; E/6; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 08/05/2004
Correction
Partial Correction
08/05/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; G/3; A/4; A/5; B/5; B/6; D.6/7; D.9/7; E/6; D/6; F/4; F/5; H/6; H/7 ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 08/06/2004
Correction
Partial Correction
08/06/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL D/3; D/4; D/5; E/3; E/4; E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; G/3; A/4; A/5; B/5; B/6; D.6/7; D.9/7; E/6; D/6; F/4; F/5; H/6; H/7; F/6; F/7; G/6; G/7; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 08/09/2004
Correction
Partial Correction
08/09/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; G/3; A/4; A/5; B/5; B/6; D.6/7; D.9/7; E/6; D/6; F/4; F/5; H/6; H/7; F/6; F/7; G/6; G/7; D.9/8; E.3/8; F/7.8; OK TO POUR WHEN READY D/3; D/4; D/5; E/3; E/4
Rough Framing Inspection - Commercial Partial 08/10/2004
Correction
Partial Correction
08/10/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; G/3; A/4; A/5; B/5; B/6; D.6/7; D.9/7; E/6; D/6; F/4; F/5; H/6; H/7; F/6; F/7; G/6; G/7; D.9/8; E.3/8; F/7.8; C/6; OK TO POUR WHEN READY D/3; D/4; D/5; E/3; E/4
Suspended Slab Inspection Partial 08/17/2004
Correction
Partial Correction
08/17/2004
PAN SLAB CONCRETE FLOOR DECK - 2ND LEVEL W OF (D.5); CONTINGENT ON SEA INSPECT OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 08/19/2004
Correction
Partial Correction
08/19/2004
C.I.P. CONC COLUMNS - ROOF LEVEL EXTENSION BARS + COUPLERS IN PLACE: D.6/7; D.9/7; F/7; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Correction
Resolved
08/19/2004
C.I.P. CONC CLOUMNS - 1ST LEVEL E/5; D/2; D/3; C/2; C/3; B.6/4; C/5; G/2.7; G/4; G/5; H/2.7; H/3; C/1; D/1; E/1; F/1; F/2; F/3; A/3; B/1; B/2; B/3; B/4; H/4; H/5; G/3; A/4; A/5; B/5; B/6; D.6/7; D.9/7; E/6; D/6; F/4; F/5; H/6; H/7; F/6; F/7; G/6; G/7; D.9/8; E.3/8; F/7.8; C/6; D/3; D/4; D/5; E/3; E/4
Rough Framing Inspection - Commercial Passed 08/20/2004
Correction
Resolved
08/20/2004
C.I.P. CONC COLUMNS - ROOF LEVEL EXTENSION BARS + COUPLERS IN PLACE: D.6/7; D.9/7; F/7; D.9/8; E.3/8; F/7.6 ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Passed 08/27/2004
Correction
Resolved
08/27/2004
C.I.P. CONC COLUMNS - ROOF LEVEL EXTENSION BARS + COUPLERS IN PLACE: D.6/7; D.9/7; F/7; D.9/8; E.3/8; F/7.6; STUB COLUMNS TO TOP OF COUPLERS ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Plumbing Inspection - Commercial Partial 09/22/2004
Correction
Partial Correction
09/22/2004
PRESSURE TEST ROOF DRAIN PIPING PRESSURE TEST OK @ RISER W/ R.D. @: (B.6)/(2.7); (B.6)/(5.3); (D.9)/(5.3); (D.9)/(2.9); SUBJECT TO VISUAL INSP THROUGH FINAL INSPECTION
Correction
Partial Correction
09/22/2004
PRESSURE TEST DWV PLUMBING GROUPS PRESSURE TEST OK @ GROUP W/ VTR @: (C.3)/(5.8); (D.2)/(5.1); (E.1)/(4.3); (G.9)/(3.4); (G.9)/(5.6); OK EXCEPT LEAKING NIPPLES @ LAB SINKS: (B)/(2.4); (A.3)/(3.8); SUBJECT TO VISUAL INSP DURING IN-WALL INSPECTION
Rough Plumbing Inspection - Commercial Partial 09/23/2004
Correction
Resolved
09/23/2004
PRESSURE TEST ROOF DRAIN PIPING PRESSURE TEST OK @ RISER W/ R.D. @: (B.6)/(2.7); (B.6)/(5.3); (D.9)/(5.3); (D.9)/(2.9); (F.9)/(4.9); (F.9)/(5.6) SUBJECT TO VISUAL INSP THROUGH FINAL INSPECTION
Correction
Partial Correction
09/23/2004
PRESSURE TEST DWV PLUMBING GROUPS PRESSURE TEST OK @ GROUP W/ VTR @: (C.3)/(5.8); (D.2)/(5.1); (E.1)/(4.3); (G.9)/(3.4); (G.9)/(5.6); (E.8)/(2.2); (C.9)/(3.3); (D.9)/(3.3); (E.2)/(4.3); (E.8)/(4.3); (E.4)/(4.9); OK EXCEPT LEAKING NIPPLES @ LAB SINKS: (B)/(2.4); (A.3)/(3.8); SUBJECT TO VISUAL INSP DURING IN-WALL INSPECTION
Rough Plumbing Inspection - Commercial Passed 09/24/2004
Correction
Resolved
09/24/2004
PRESSURE TEST DWV PLUMBING GROUPS PRESSURE TEST OK @ GROUP W/ VTR @: (C.3)/(5.8); (D.2)/(5.1); (E.1)/(4.3); (G.9)/(3.4); (G.9)/(5.6); (E.8)/(2.2); (C.9)/(3.3); (D.9)/(3.3); (E.2)/(4.3); (E.8)/(4.3); (E.4)/(4.9); (B)/(2.4); (A.3)/(3.8); (D.3)/(2.4); (C.7)/(4.3) SUBJECT TO VISUAL INSP DURING IN-WALL INSPECTION
All Rough Inspection - Commercial Partial 10/11/2004
Correction
Partial Correction
10/11/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH RMS 165; 166; OK TO COVER WHEN READY
Electrical Service Inspection Partial 10/11/2004
Correction
Partial Correction
10/11/2004
TEMPORARY ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE
All Rough Inspection - Commercial Partial 10/13/2004
Correction
Partial Correction
10/13/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH RMS 165; 166 OK TO COVER WHEN READY; PROTECT COPPER PIPE @ STUD PENETRATIONS, REINFORCE WEAKENED STUDS, COMPLETE CONDUIT, CHECK BOX STAND-OFF'S: RMS 106; 107; 108; 109; 110; 112; 114; 115; 116; 117; 118; 119; 135; 136; 137; 138; 163; 164;
Rated Assembly Inspection Partial 10/15/2004
Correction
Partial Correction
10/15/2004
WALL ALONG (G) E + W FACE ONE LAYER 5/8" TYPE X GWB; OK TO COVER WHEN READY FROM (3.3) TO (5.8)
Correction
Partial Correction
10/15/2004
WALL ALONG (F) E FACE 1ST LAYER 5/8" TYPE X GWB; FROM (3) TO (6) OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 10/15/2004
Correction
Partial Correction
10/15/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH OK TO COVER WHEN READY: RMS 106; 107; 108; 109; 110; 112; 114; 115; 116; 117; 118; 119; 135; 136; 138; 163; 164; 165; 166; PROTECT COPPER PIPE @ STUD PENETRATIONS @ 137
Rated Assembly Inspection Partial 10/19/2004
Correction
Partial Correction
10/19/2004
ELECT RMS 165 & 166 COMMON WALL; TYPE "A" U465 WALLS OK TO COVER WHEN READY
Rated Assembly Inspection Partial 10/20/2004
Correction
Partial Correction
10/20/2004
WALL ALONG (F) E FACE 1ST LAYER 5/8" TYPE X GWB; E FACE 2ND LAYER @ SHOWER IN RM 116; W FACE 1ST LAYER; FROM (3) TO (6) OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 10/20/2004
Correction
Partial Correction
10/20/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH OK TO COVER WHEN READY: RMS 106; 107; 108; 109; 110; 112; 114; 115; 116; 117; 118; 119; 135; 136; 138; 163; 164; 165; 166; WALLS {EXCLUDING ANY WITH PLUMBING} E OF (F) x S OF (4.8) to (6); PROTECT COPPER PIPE @ STUD PENETRATIONS @ 137
All Rough Inspection - Commercial Partial 10/29/2004
Correction
Partial Correction
10/29/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH OK TO COVER WHEN READY: RMS 106; 107; 108; 109; 110; 112; 114; 115; 116; 117; 118; 119; 135; 136; 138; 163; 164; 165; 166; WALLS E OF (F) x S OF (4.8) to (6); 140; 141; 142; 5 PRE-OP RMS @ 127 WEST; PROTECT COPPER PIPE @ STUD PENETRATIONS @ 137
All Rough Inspection - Commercial Partial 11/03/2004
Correction
Partial Correction
11/03/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH 110; 112; 114; 115; 116; 117; 118; 119; 135; 136; 138; 163; 164; 165; 166; WALLS E OF (F) x S OF (4.8) to (6); 140; 141; 142; 5 PRE-OP RMS @ 127 WEST + 2 @ EAST; 125 S 1/2; 134 N WALL; 144; OK TO COVER WHEN READY RMS 106; 107; 108; 109;
Rated Assembly Inspection Partial 11/09/2004
Correction
Partial Correction
11/09/2004
FUTURE ELEVATOR SHAFT #169 1ST LAYER; LINER BOARD APP'D 11/8/04 2 LAYERS 1/2" TYPE X GWB:
Correction
Partial Correction
11/09/2004
ROOMS 140 & 141 RM 140 BOTH FACES; TYPE A WALLS OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 11/09/2004
Correction
Partial Correction
11/09/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH 110; 112; 114; 115; 116; 117; 118; 119; 135; 136; 138; 163; 164; 165; 166; WALLS E OF (F) x S OF (4.8) to (6); 140; 141; 142; 5 PRE-OP RMS @ 127 WEST + 2 @ EAST; 125 S 1/2; 134 N WALL; 144; 126; 129; 130; 131; 132; 150; OK TO COVER WHEN READY RMS 106; 107; 108; 109;
Above Ceiling Inspection Partial 11/11/2004
Correction
Partial Correction
11/11/2004
ABOVE-CEILING SYSTEMS GWB SOFFIT AREAS IN RECEPTION 105; OK TO COVER WHEN READY
Rated Assembly Inspection Partial 11/11/2004
Correction
Resolved
11/11/2004
ROOMS 140 & 141 RMS 140 & 141 BOTH FACES TYPE A WALLS OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 11/11/2004
Correction
Resolved
11/11/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH 112; 114; 115; 116; 117; 118; 119; 135; 136; 138; 163; 164; 165; 166; WALLS E OF (F) x S OF (4.8) to (6); 140; 141; 142; 5 PRE-OP RMS @ 127 W + 2 @ E; 125 S 1/2; 134 N WALL; 144; 126; 129; 130; 131; 132; 150; 133 EAST WALL; 149 W WALL EXCL N 4'; CONT'D OK TO COVER WHEN READY 106; 107; 108; 109; 110
Correction
Partial Correction
11/11/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D
All Rough Inspection - Commercial Partial 11/12/2004
Correction
Partial Correction
11/12/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; OK TO COVER WHEN READY
Rated Assembly Inspection Partial 11/17/2004
Correction
Resolved
11/17/2004
ROOM 143 - TYPE A WALL OK TO COVER WHEN READY 5/8 TYPE X GWB E&S WALLS BOTH FACES
Above Ceiling Inspection Partial 11/17/2004
Correction
Partial Correction
11/17/2004
ABOVE-CEILING SYSTEMS GWB SOFFIT AREAS IN RECEPTION 105; ABOVE GWB CEILINGS IN ROOMS 116, 118, 136; OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 11/17/2004
Correction
Partial Correction
11/17/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 11/22/2004
Correction
Partial Correction
11/22/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; OK TO COVER WHEN READY
Electrical Service Inspection Passed 11/23/2004
Correction
Resolved
11/23/2004
TEMPORARY ELECTRICAL SERVICE INSTALLATION
Correction
Resolved
11/23/2004
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE
Above Ceiling Inspection Partial 12/01/2004
Correction
Partial Correction
12/01/2004
ABOVE-CEILING SYSTEMS 105; 116, 118, 136; 150; OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 12/01/2004
Correction
Partial Correction
12/01/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; 145; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/02/2004
Correction
Partial Correction
12/02/2004
ABOVE-CEILING SYSTEMS 105; 116, 118, 136; 150; 144; OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 12/02/2004
Correction
Partial Correction
12/02/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; 144; 145; 151; 152; 155; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/03/2004
Correction
Partial Correction
12/03/2004
ABOVE-CEILING SYSTEMS 105; 116, 118, 136; 150; 144; 148; OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 12/06/2004
Correction
Partial Correction
12/06/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; 144; 145; 151; 152; 155; 147; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/07/2004
Correction
Corrective Action Required
12/07/2004
ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY: 105; 116, 118, 136; 150; 144; 148; {NOT APPROVED: 154; 155; 156; 157 > COMPLETE SEALING SMOKE WALLS + CLARIFY STATUS OF PULLING OF ELECT CONDUCTORS}
Above Ceiling Inspection Partial 12/08/2004
Correction
Partial Correction
12/08/2004
ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY: 105; 116, 118, 136; 150; 144; 148; 155; 157; {154; 156 OK TO INSTALL CEILING, EXCEPT LEAVE OPENING FOR REINSPECTION AFTER ALL ELECT CONDUCTORS & BOX MAKE-UP ARE COMPLETED}
All Rough Inspection - Commercial Partial 12/09/2004
Correction
Partial Correction
12/09/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; 144; 145; 151; 152; 155; 147; COLUMNS B/1 & C/1; OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 12/10/2004
Correction
Corrective Action Required
12/10/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; 144; 145; 151; 152; 155; 147; COLUMNS B/1 & C/1; NOT APPROVED: 172 SUBSTANTIALLY COVERED
Above Ceiling Inspection Partial 12/10/2004
Correction
Partial Correction
12/10/2004
ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY: 105; 116, 118, 136; 150; 144; 148; 155; 157; 141; 145; {154; 156 OK TO INSTALL CEILING, EXCEPT LEAVE OPENING FOR REINSPECTION}; NOT READY: 138; 151
All Rough Inspection - Commercial Partial 12/13/2004
Correction
Partial Correction
12/13/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; 144; 145; 151; 152; 155; 147; COLUMNS B/1 & C/1; 172; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/13/2004
Correction
Partial Correction
12/13/2004
ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY: 105; 116, 118, 136; 150; 144; 148; 155; 157; 141; 145; 126; E CANOPY; 151; 152; 146; 147; 111; {154; 156 OK EXCEPT LEAVE OPENING FOR REINSPECTION} NOT READY: 138
All Rough Inspection - Commercial Partial 12/14/2004
Correction
Partial Correction
12/14/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; 144; 145; 151; 152; 155; 147; COLUMNS B/1 & C/1; 172; 171; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/15/2004
Correction
Partial Correction
12/15/2004
ABOVE-CEILING SYSTEMS 105; 116, 118, 136; 150; 144; 148; 155; 157; 141; 145; 126; E CANOPY; 151; 152; 146; 147; 111; W CANOPY; {154; 156 OK EXCEPT LEAVE OPENING FOR REINSPECTION} NOT READY: 138 OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 12/15/2004
Correction
Partial Correction
12/15/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D RM 157; 148; 156; 154; 144; 145; 151; 152; 155; 147; COLUMNS B/1 & C/1; 172; 171; S WALLS OF 165 & 166 OK TO COVER AFTER 2 EL BOXES ARE PUTTY-PADDED; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/17/2004
Correction
Partial Correction
12/17/2004
ABOVE-CEILING SYSTEMS 103-109; 111; 112; 114-118, 120-124; 126-130; 135-137; 151; 141; 143-148; 150-152; 155; 157; E CANOPY; W CANOPY; {154; 156 OK EXCEPT LEAVE OPENING FOR REINSPECTION} NOT READY: 138; 119; 125; 131; 132; 133; 134; 139; 140; 142; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/21/2004
Correction
Partial Correction
12/21/2004
ABOVE-CEILING SYSTEMS 103-109; 111; 112; 114-118, 120-124; 126-130; 135-137; 151; 141; 143-148; 150-152; 155; 157; 131; 132; 134; 142; E CANOPY; W CANOPY; 125*; 133*; 154*; 156*; [*MEANS OK EXCEPT LEAVE OPENING FOR REINSPECTION] NOT READY: 138; 119; 125; 133; 139; 140; OK TO COVER WHEN READY
Rated Assembly Inspection Partial 01/06/2005
Correction
Resolved
01/06/2005
ELECT RMS 165 & 166 APPROVED 12/27/04 TYPE "A" U465 WALLS OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/06/2005
Correction
Partial Correction
01/06/2005
ABOVE-CEILING SYSTEMS 101; 103-109; 111; 112; 114-124; 126-132; 134-137; 141-148; 150-155; 157; 159-161; 165; 166; E&W CANOPIES; 125*; 133*; 156*; [*OK EXCEPT LEAVE OPENING FOR REINSPECTION] NOT READY: 138; 139; 140; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/10/2005
Correction
Partial Correction
01/10/2005
ABOVE-CEILING SYSTEMS 101; 102; 103-109; 111; 112; 114-124; 126-132; 134-137; 141-148; 150-155; 157; 158; 159-161; 165; 166; 168; E&W CANOPIES; 125*; 133*; 156*; [*OK EXCEPT LEAVE OPENING FOR REINSPECTION] NOT READY: 138; 139; 140; 170 OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/13/2005
Correction
Partial Correction
01/13/2005
ABOVE-CEILING SYSTEMS 101-109; 111; 112; 114-124; 126-132; 134-137; 141-148; 150-155; 157-161; 165; 166; 168; 170; 172; E&W CANOPIES; 125*; 133*; 156*; [*OK EXCEPT LEAVE OPENING FOR REINSPECTION] NOT READY: 138; 139; 140 OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/18/2005
Correction
Partial Correction
01/18/2005
ABOVE-CEILING SYSTEMS 101-109; 111; 112; 114-124; 125; 126-132; 133; 134-137; 141-148; 150-155; 156; 158; 157-161; 165; 166; 168; 170; 172; E&W CANOPIES; NOT READY: 138; 139; 140 OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/20/2005
Correction
Partial Correction
01/20/2005
ABOVE-CEILING SYSTEMS 101-109; 111; 112; 114-137; 138; 139; 140; 141-148; 150-161; 165; 166; 168; 170; 172; E&W CANOPIES OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 02/11/2005
Correction
Corrective Action Required
02/11/2005
Receive Fire Department approval
Correction
Corrective Action Required
02/11/2005
Receive Planning & Development Approval
Correction
Corrective Action Required
02/11/2005
Receive Public Works Approval
Correction
Corrective Action Required
02/11/2005
Receive Water Utilities Approval
Correction
Corrective Action Required
02/11/2005
DEVELOPMENT AGREEMENT CONDITIONS TO BE SATISFIED
Correction
Corrective Action Required
02/11/2005
EGRESS PATH OUTSIDE SOUTH ENTRANCE ELIMINATE DROP-OFF PROVIDE CLEAR PATH
Correction
Corrective Action Required
02/11/2005
ROOFTOP INSPECTION TO BE PERFORMED
Correction
Corrective Action Required
02/11/2005
HANDICAP SIGNS @ RESTROOMS COMPLETE INSTALLATION
Correction
Corrective Action Required
02/11/2005
OCCUPANCY APPROVAL STATUS IBC 110.1 / IRC R110: UNTIL APPROVED DO NOT OCCUPY OR PLACE PERSONAL PROPERTY
Occupancy Inspection - Codes Commercial Failed 02/14/2005
Correction
Corrective Action Required
02/14/2005
ROOFTOP INSPECTION CHECK ENTIRE SYSTEM, PARTICULARLY 4 RODS DETACHED FROM E.F. BONNETS. (2) EL RECEPT AT FAR EAST END NOT HOT FOR TEST (3) SOUTH ENT PARAPET WALL INCOMPLETE (4) FINAL CLEAN ALL MATERIAL/DEBRIS (1) LIGHTNING PROT SYSTEM NOT COMPLETE
Correction
Resolved
02/14/2005
HANDICAP SIGNS @ RESTROOMS
Correction
Partial Correction
02/14/2005
DEVELOPMENT AGREEMENT CONDITIONS SEE MODOT LTR DTD 2/10/05
Occupancy Inspection - Codes Commercial Failed 02/16/2005
Correction
Resolved
02/16/2005
EGRESS PATH OUTSIDE SOUTH ENTRANCE
Correction
Corrective Action Required
02/16/2005
ROOFTOP INSPECTION (2) EL RECEPT AT FAR EAST END NOT HOT FOR TEST (3) SOUTH ENT PARAPET WALL INCOMPLETE (4) FINAL CLEAN ALL MATERIAL/DEBRIS
Correction
Corrective Action Required
02/16/2005
OCCUPANCY APPROVAL STATUS IBC 110.1 / IRC R110: UNTIL APPROVED DO NOT OCCUPY OR PLACE PERSONAL PROPERTY
Occupancy Inspection - Codes Commercial Failed 02/16/2005
Correction
Corrective Action Required
02/16/2005
ROOFTOP INSPECTION (1) EL RECEPT AT FAR EAST END NOT HOT FOR TEST (2) SOUTH ENT PARAPET WALL INCOMPLETE (3) FINAL CLEAN ALL MATERIAL/DEBRIS
Correction
Partial Correction
02/16/2005
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Suspended Slab Inspection Passed 02/16/2005
Correction
Resolved
02/16/2005
PAN SLAB CONCRETE FLOOR DECK - 2ND LEVEL
Rated Assembly Inspection Passed 02/16/2005
Correction
Resolved
02/16/2005
WALL ALONG (F)
Correction
Resolved
02/16/2005
WALL ALONG (G)
Correction
Resolved
02/16/2005
ELECT RMS 165 & 166
Correction
Resolved
02/16/2005
FUTURE ELEVATOR SHAFT #169
Correction
Resolved
02/16/2005
ROOMS 140 & 141
Correction
Resolved
02/16/2005
ROOM 143 - TYPE A WALL
Above Ceiling Inspection Passed 02/16/2005
Correction
Resolved
02/16/2005
ABOVE-CEILING SYSTEMS
All Rough Inspection - Commercial Passed 02/16/2005
Correction
Resolved
02/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Correction
Resolved
02/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH, CONT'D
Occupancy Inspection - Codes Commercial Passed 04/20/2005
Correction
Resolved
04/20/2005
Receive Fire Department approval
Correction
Resolved
04/20/2005
Receive Planning & Development Approval PER M GORECKI 4/20/05
Correction
Resolved
04/20/2005
Receive Public Works Approval PER B LYON
Correction
Resolved
04/20/2005
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
04/20/2005
DEVELOPMENT AGREEMENT CONDITIONS
Correction
Resolved
04/20/2005
ROOFTOP INSPECTION
Correction
Resolved
04/20/2005
OCCUPANCY APPROVAL STATUS
Occupancy Inspection - Codes Commercial Passed 04/21/2005
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home