Permit Application Status

B0400606


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0400606
Building Permit - Commercial
Certificate of Occupancy
DOUGLAS STATION SHOPPING CENTER LLC
NEW TENANT FINISH
TENANT FINISH
04/13/2004
04/22/2004
10/19/2004
06/28/2004
Locations
Contacts
CAPITAL CONSTRUCTION SERVICES, LLC, Address:839 NE WOODS CHAPEL RD  
DAVIDSON DESIGN GROUP, Address:11301STRANG LINE ROAD  
DOUGLAS STATION SHOPPING CENTER LLC, Address:1725 NE RICE RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/10/2004 10/29/2010
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Battery calculations.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1003.2.10 - Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visable to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible exit sign.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $71.00 $71.00 Paid 04/22/2004
24 BLDG Plan Check Fees $7.75 $7.75 Paid 04/22/2004
25 Electrical Permit Fee $94.75 $94.75 Paid 04/22/2004
25 Mechanical Permit Fees $24.00 $24.00 Paid 04/22/2004
25 Plumbing Permit Fees $29.00 $29.00 Paid 04/22/2004
89 Sewer Tap Fees $180.00 $180.00 Paid 04/22/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Partial 04/27/2004
Correction
Partial Correction
04/27/2004
None OK TO COVER EAST CURTAIN WALL FRONT ENTRY
All Rough Inspection - Commercial Failed 04/29/2004
Correction
Corrective Action Required
04/29/2004
PROTECTION OF PVC PIPING IPC 305.8; IRC P2603: INSTALL SHIELD PLATES < 1-1/2" FROM FACE OF STUDS & TRACKS
Correction
Corrective Action Required
04/29/2004
GROMMETS @ COPPER WATER PIPING PENETRATIONS OF STUDS MUST BE SECURE IN PLACE
All Rough Inspection - Commercial Failed 05/03/2004
Correction
Resolved
05/03/2004
PROTECTION OF PVC PIPING
Correction
Corrective Action Required
05/03/2004
GROMMETS @ COPPER WATER PIPING PENETRATIONS OF STUDS ARE TOO SMALL FOR OPENINGS IN STUDS, AND DO NOT GRIP THE STUD MUST BE SECURE IN PLACE PLASTIC GROMMETS USED
Rough Electrical Inspection - Commercial Passed 05/05/2004
Correction
Resolved
05/05/2004
None EAST CURTAIN WALL FRONT ENTRY
All Rough Inspection - Commercial Not Ready 05/05/2004
Correction
Corrective Action Required
05/05/2004
READINESS FOR INSPECTION IBC 109.1, 109.5 PROPERTY LOCKED INTERIOR NOT ACCESSIBLE
Rough Framing Inspection - Commercial Request Complete 5/4/2004 5/5/2004 05/05/2004
All Rough Inspection - Commercial Passed 05/06/2004
Correction
Resolved
05/06/2004
GROMMETS @ COPPER WATER PIPING PENETRATIONS OF STUDS
Correction
Resolved
05/06/2004
READINESS FOR INSPECTION
Above Ceiling Inspection Passed 05/24/2004
Correction
Resolved
05/24/2004
ABOVE-CEILING SYSTEMS ROUGH OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Passed 06/25/2004
Correction
Resolved
06/25/2004
REFRIGERATION CONDENSERS @ ROOFTOP NOT SECURED TO BLOCKS ADVISE GC TO SECURE
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home