Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/10/2004 10/29/2010
Correction

CA - This is a renewal of permit 97-438. All previous conditions apply.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $248.00 $248.00 Paid 04/13/2004
24 BLDG Plan Check Fees $18.20 $18.20 Paid 04/13/2004
25 Electrical Permit Fee $90.35 $90.35 Paid 04/13/2004
25 Mechanical Permit Fees $64.00 $64.00 Paid 04/13/2004
25 Plumbing Permit Fees $35.00 $35.00 Paid 04/13/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Service Inspection Passed 05/04/2004
Correction
Resolved
05/04/2004
WATER SERVICE INSTALLATION TAP; METER COMPLETE SVC LINE TO BLDG ENTRY
Final Plumbing Inspection - Commercial Passed 05/04/2004
Water Service Inspection - Commercial Request Complete 5/3/2004 5/4/2004 05/04/2004
Electrical Service Inspection Passed 05/26/2004
Correction
Resolved
05/26/2004
READINESS FOR INSPECTION
Correction
Resolved
05/26/2004
ELECTRICAL SERVICE INSTALLATION WORKMANSHIP
Correction
Resolved
05/26/2004
ELECTRICAL SERVICE INSTALLATION LABEL ALL CABINETS & LABEL ALL CIRCUIT BREAKERS RELEASE SERVICE PRIOR TO FINAL INSPECTION
Rough Electrical Inspection - Commercial Passed 07/02/2004
Correction
Resolved
07/02/2004
IN-WALL SYSTEMS ROUGH OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 09/08/2004
Correction
Corrective Action Required
09/08/2004
Receive Fire Department approval
Correction
Corrective Action Required
09/08/2004
Receive Planning & Development Approval
Correction
Corrective Action Required
09/08/2004
Receive Public Works Approval
Correction
Corrective Action Required
09/08/2004
Receive Water Utilities Approval
Correction
Corrective Action Required
09/08/2004
FIXTURES @ HANDICAPPED ACCESSIBLE RESTROOM EXAMPLES: SEE WC-1 & L-2 ON FIXTURE SCHEDULE NOT PER DRAWINGS/ADA NOT ACCESSIBLE TYPE
Correction
Corrective Action Required
09/08/2004
HANDICAPPED ACCESSIBLE RESTROOM SIGN NOT IN PLACE UNISEX, WITH BRAILLE PAD
Correction
Corrective Action Required
09/08/2004
LABELING OF ELECTRICAL CIRCUIT BREAKERS NEC 110-22; 384-13; IRC E36O6.2. EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. LABEL SPARES AS SUCH. SERVICE PANELS ENSURE ALL ARE LABELED
Above Ceiling Inspection Failed 09/08/2004
Correction
Corrective Action Required
09/08/2004
SUPPORT OF HVAC FLEXIBLE DUCT AND NOT MORE THAN 10' ON CENTER. NOT TO BE SUPPORTED BY OTHER MEP TRADES. SUPPORT AT INTERVALS PER MFGRS INSTRUCTIONS
Correction
Corrective Action Required
09/08/2004
ELECTRICAL JUNCTION BOXES @ N END OF OFFICE AREA NOT SECURE TO STRUCTURE + NOT CLOSED
Correction
Corrective Action Required
09/08/2004
PLUMBING VENT TO ROOF INCOMPLETE PER DRAWING
Above Ceiling Inspection Passed 11/16/2004
Correction
Resolved
11/16/2004
SUPPORT OF HVAC FLEXIBLE DUCT PER MFGRS INSTRUCTIONS AND NOT MORE THAN 10' ON CENTER. NOT TO BE SUPPORTED BY OTHER MEP TRADES. ENSURE SUPPORT AT INTERVALS
Correction
Resolved
11/16/2004
ELECTRICAL JUNCTION BOXES @ N END OF OFFICE AREA ENSURE ALL ARE SECURED TO STRUCTURE AND ARE CLOSED
Correction
Resolved
11/16/2004
PLUMBING VENT TO ROOF VENTED THROUGH SIDE WALL
Occupancy Inspection - Codes Commercial Failed 11/16/2004
Correction
Resolved
11/16/2004
Receive Planning & Development Approval NO ISSUES PRESENTED
Correction
Resolved
11/16/2004
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
11/16/2004
FIXTURES @ HANDICAPPED ACCESSIBLE RESTROOM
Correction
Resolved
11/16/2004
HANDICAPPED ACCESSIBLE RESTROOM SIGN
Correction
Resolved
11/16/2004
LABELING OF ELECTRICAL CIRCUIT BREAKERS
Occupancy Inspection - Codes Commercial Passed 11/18/2004
Correction
Resolved
11/18/2004
Receive Fire Department approval PER N ULLERY 11/18/04
Correction
Resolved
11/18/2004
Receive Public Works Approval PER M WEISENBORN 11/18/04
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home