Summary
B0400596
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
LEES SUMMIT PARENTS AS TEACHERS BUILDING
04/12/2004
06/24/2004
12/21/2004
05/26/2005
Locations
Contacts
TURNER CONSTRUCTION COMPANY, Address:2345 GRAND BOULDVARD  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/09/2004 10/29/2010
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

CA - 2000 IMC 403.3 - Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and the occupant load or other perameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less then the number determined from the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

CA - 2000 IBC 1003.2.2.5 - Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

CA - 2000 IBC 1003.2.10 - Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visable to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible exit sign.
Correction

CA - 2000 IBC 1704.1.2 - Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and the registered design professional in responsible charge prior to the completion of that phase of the work. A final report of inspections documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted periodically at a frequency agreed upon by the permit applicant and the building official prior to the start of work.
Correction

CA - 2000 IBC 1704.1.1 - The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with Section 106.1 as a condition for permit issuance. This statement shall include a complete list of materials and work requiring special inspections by this section, the inspections to be performed and a list of the individuals, approved agencies or firms intended to be retained for conducting such inspections.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - 2000 IBC 603.1 - Allowable uses. Combustible materials are permitted in buildings of Type I and Type II construction in the following applications: 1. Fire-retardent-treated wood shall be permitted in: 1.3. Roof construction as permitted in Table 601, Note c, Item 3.
Correction

CA - Specifications on the kitchen hood system to be installed was not provided at the time of application.
Correction

CA - 2000 IBC 302.1.1.1 - Separation. Where Table 302.1.1 requires a fire-resistance-rated separation, the incidental use area shall be separatd from the remainder of the building with a fire barrier. Where Table 302.1.1 permits an automatic fire-extinguishing system without a fire barrier, the incidential use area shall be separated by construction capable of resisting the passage of smoke. The partitions shall extend from the underside of the fire-resistance-rated floor/ceiling assembly or fire-resistance-rated roof/ceiling assembly or to the underside of the floor or roof deck above. Doors shall be self-closing or automatic-closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permitted in accordance with NFPA 80.
Correction

CA - The occupant load of the multi-purpose room is being calculated at 1:15. It is possible that the space can be set up with chairs only and is actually shown that way on some sheets. This would require the occupant load to be calculated at 1:7.
Correction

Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior to any point of use.
Correction

CA - 2000 IPC 708.3.2 - Building sewers shall be provided with cleanouts located not more than 100 feet apart measured fron the upstream entrance of the cleanout. For building sewers 8 inches and larger, manholes shall be provided and located at each change in direction and at intervals of not more than 400 feet of developed length of the drainage piping.
Correction

CA - 2000 IMC 602.2.1 - Except as required by Section 602.2.1.1 through 602.2.1.4, materials exposed within plenumbs shall be noncombustible or shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
Correction

CA - 2000 IPC 802.1.1 - Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an inderect waste pipe by means of an air gap.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

A double check detector check valve assembly is required on the fire service line.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $13,052.00 $13,052.00 Paid 06/24/2004
24 BLDG Plan Check Fees $237.50 $237.50 Paid 06/24/2004
25 Electrical Permit Fee $867.47 $867.47 Paid 06/24/2004
25 Mechanical Permit Fees $509.50 $509.50 Paid 06/24/2004
25 Plumbing Permit Fees $241.00 $241.00 Paid 06/24/2004
89 Sewer Tap Fees $2,130.00 $2,130.00 Paid 06/24/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection - Commercial Request Complete 7/14/2004 7/14/2004 07/14/2004
Sewer Service Inspection Partial 07/15/2004
Correction
Partial Correction
07/15/2004
None 150 FT 6IN SDR
Sewer Service Inspection - Commercial Request Complete 7/15/2004 7/15/2004 07/15/2004
Underslab Plumbing Inspection - Commercial Partial 07/28/2004
Correction
Partial Correction
07/28/2004
None SHEET P1.1 - LINE A. 8 (4") FROM LINE 5 TO 8 COVERED - UNABLE TO INSPECT. CHECK WITH PUBLIC WORKS INSPECTIONS (4") LINE A FROM LINE 8 TO NE CORNER - APPROVED (4") LINE ON EAST SIDE OF BUILDING FROM LINE A TO S - APPROVED
Underslab Plumbing Inspection - Commercial Partial 07/29/2004
Correction
Partial Correction
07/29/2004
None SHEET P1.1 & P1.3- LINE A. 8 (4") FROM LINE 5 TO 8 COVERED - SEE E-MAIL FROM MIKE WEISENBORN DATED 29 JULY 2004. (4") LINE A FROM LINE 8 TO NE CORNER - APPROVED (4") LINE ON EAST SIDE OF BUILDING FROM LINE A TO S - APPROVED
Correction
Partial Correction
07/29/2004
None SHEETS P1.1 & 1.3 - LINE 2.3 FROM LINE C TO SOUTH END OF BUILDING.
Water Service Inspection Partial 07/30/2004
Correction
Resolved
07/30/2004
See Comment SERVICE LINE FROM METER TO BUILDING - CHANGED FOM 2 1/2" COPPER K TO 4" DOCTILE. CHANGED APPROVED BY BREDSON & ASSOC. & PLANS EXAMINER.
Correction
Partial Correction
07/30/2004
None SHEET P1.0 - LOCATION OF WATER METER CHANGED BY DISTRICT 13. NEW SITE APPROX. 40` WEST OF ORIGINAL SITE. A 20` SECTION APPROXIMATELY 20` FROM NEW METER SITE INSTALLED. COVER AT OWN RISK
Water Service Inspection Partial 08/05/2004
Correction
Partial Correction
08/05/2004
None SHEET P1.0 - LOCATION OF WATER METER CHANGED BY DISTRICT 13. NEW SITE APPROX. 40` WEST OF ORIGINAL SITE. A 20` SECTION APPROXIMATELY 20` FROM NEW METER SITE INSTALLED. COVER AT OWN RISK
Correction
Partial Correction
08/05/2004
None FROM PREVIOUS POINT - APPROVED 80` EAST
Water Service Inspection - Commercial Request Complete 8/5/2004 8/5/2004 08/05/2004
Water Service Inspection - Commercial Request Complete 8/6/2004 8/6/2004 08/06/2004
Footing Inspection - Commercial Partial 08/10/2004
Correction
Partial Correction
08/10/2004
None SHEET 2.0 - LINE 12.2 FROM LINE B.8 TO LINE G.4
Piers/Caissons Inspection - Commercial Partial 08/11/2004
Correction
Partial Correction
08/11/2004
None BALANCE OF PIERS 1.8 LINE TO X X LINE TO 6.3
Footing Inspection - Commercial Partial 08/11/2004
Correction
Resolved
08/11/2004
None SHEET 2.0 - LINE 12.2 FROM LINE B.8 TO LINE G.4
Correction
Partial Correction
08/11/2004
None A LINE 9.8 TO 12.2 B8 12.1 G LINE THRU J TO 15 LINE N
Piers/Caissons Inspection - Commercial Partial 08/11/2004
Correction
Partial Correction
08/11/2004
None SHEET 2.0 PIERS AT LINE 1.5 FROM K TO T SHEET 2.1 PIERS AT LINE 1.5 FROM T TO V.6
Footing Inspection - Commercial Partial 08/11/2004
Correction
Partial Correction
08/11/2004
None SHEET S2.0 LINE 9.6 FROM B.2 TO G.5 LINE B.5 & G.5 FROM LINESW 9.6 TO 12.2
Footing Inspection - Commercial Partial 08/12/2004
Correction
Partial Correction
08/12/2004
PERIMETER SPREAD FOOTING FROM A7.6 TO G1; J13 TO S13 OK TO POUR WHEN READY
Footing Inspection - Commercial Partial 08/13/2004
Correction
Partial Correction
08/13/2004
None SHEET S2.0 LINE S FROM 9.5 TO13
Piers/Caissons Inspection - Commercial Partial 08/13/2004
Correction
Partial Correction
08/13/2004
None SHEET S2.0 PIER AT LINES L BY 4, AT LINE M BY 5 & 7, AT LINE 7 BY J SHEET S2.1 PIERS AT LINES 5 & 6 FROM LINES T TO W
Underslab Plumbing Inspection - Commercial Partial 08/13/2004
Correction
Resolved
08/13/2004
None ROOMS 132, 133, 137A
Footing Inspection - Commercial Partial 08/16/2004
Correction
Resolved
08/16/2004
None A LINE 9.8 TO 12.2 B8 12.1 G LINE THRU J TO 15 LINE N
Correction
Resolved
08/16/2004
PERIMETER SPREAD FOOTING SHEET 2.0 FROM A7.6 TO G1; J13 TO S13
Correction
Resolved
08/16/2004
None SHEET S2.0 LINE S FROM 9.5 TO13
Correction
Partial Correction
08/16/2004
None SHEET 2.0 FROMJ9.5 TO S9.5
Correction
Resolved
08/16/2004
None SHEET S2.0 LINE 7.4 FROM M TO T
Footing Inspection - Commercial Partial 08/17/2004
Correction
Partial Correction
08/17/2004
None SHEET S2.1 LINE W.9 FROM 1.8 TO 7.4 LINE 1.8 FROM LINE T TO W.9
Underslab Plumbing Inspection - Commercial Partial 08/18/2004
Correction
Resolved
08/18/2004
None SHEETS P1.1 & 1.3 - LINE 2.3 FROM LINE C TO SOUTH END OF BUILDING.
Correction
Resolved
08/18/2004
None SHEET P1.1 4" STORM LINE AT DE.1 FROM 9.8 TO 10.8
Correction
Partial Correction
08/18/2004
None SHEET P1.1 ROOMS 143, 144, 146, ROOMS 140, 139 WILL NOT HOLD PRESSURE
Correction
Resolved
08/18/2004
None SHEET P1.1 & P1.3- LINE A. 8 (4") FROM LINE 5 TO 8 COVERED - SEE E-MAIL FROM MIKE WEISENBORN DATED 29 JULY 2004. (4") LINE A FROM LINE 8 TO NE CORNER - APPROVED (4") LINE ON EAST SIDE OF BUILDING FROM LINE A TO S - APPROVED
Footing Inspection - Commercial Partial 08/18/2004
Correction
Resolved
08/18/2004
None SHEET 2.0 FROMJ9.5 TO S9.5
Correction
Resolved
08/18/2004
None SHEET S2.1 LINE W.9 FROM 1.8 TO 7.4 LINE 1.8 FROM LINE T TO W.9
Correction
Partial Correction
08/18/2004
None SHEET S2.0 LINE 7.5 FROM M.1 TO T
Correction
Resolved
08/18/2004
None SHEET S2.0 LINE RUNNING FROM J TO M AT LINES 7.5 TO 7.8
Piers/Caissons Inspection - Commercial Partial 08/18/2004
Correction
Resolved
08/18/2004
None SHEET S2.0 LINE 11 BY J, P, Q, R LINE 12 BY J, N, Q, R
Underslab Plumbing Inspection - Commercial Partial 08/19/2004
Correction
Resolved
08/19/2004
None SHEET P1.1 ROOMS 143, 144, 146, ROOMS 140, 139 WILL NOT HOLD PRESSURE
Correction
Partial Correction
08/19/2004
None SHEET P1.1 ROOMS 149, 150, 154, 155
Piers/Caissons Inspection - Commercial Partial 08/19/2004
Correction
Resolved
08/19/2004
None BALANCE OF PIERS 1.8 LINE TO X X LINE TO 6.3
Correction
Resolved
08/19/2004
None SHEET S2.0 PIER AT LINES L BY 4, AT LINE M BY 5 & 7, AT LINE 7 BY J SHEET S2.1 PIERS AT LINES 5 & 6 FROM LINES T TO W
Correction
Partial Correction
08/19/2004
None SHEET 2.0 LINE 7 BY LINES C, D, G, H LINE 3 BY LINE E
Footing Inspection - Commercial Partial 08/19/2004
Correction
Resolved
08/19/2004
None SHEET S2.0 LINE 7.5 FROM M.1 TO T
Correction
Partial Correction
08/19/2004
None SHEET S2.0 LINE 1.0 TO LINE 1.8 AT LINE G TO K
Underslab Plumbing Inspection - Commercial Partial 08/20/2004
Correction
Resolved
08/20/2004
None SHEET P1.1 ROOMS 149, 150, 154, 155
Correction
Partial Correction
08/20/2004
None SHEET P1.3 ROOM 181 - NORTH LATERALS NOT GRAVELED - DO NOT COVER LINE V.5 FROM 4.4 TO 6.8 - OKAY TO COVER PRESSURED TEST OKAY
Underslab Plumbing Inspection - Commercial Partial 08/26/2004
Correction
Resolved
08/26/2004
None SHEET P1.3 ROOM 181 - NORTH LATERALS NOT GRAVELED - DO NOT COVER LINE V.5 FROM 4.4 TO 6.8 - OKAY TO COVER PRESSURED TEST OKAY
Correction
Partial Correction
08/26/2004
None SHEET P1.3 RESTROOMS IN ROOMS 180 & 184
Footing Inspection - Commercial Partial 08/27/2004
Correction
Partial Correction
08/27/2004
None SHEET S2.0 A LINE FROM 7 TO 9.8
Correction
Resolved
08/27/2004
None SHEET S2.0 LINE 7.4 FROM M TO T
Correction
Resolved
08/27/2004
None SHEET 2.0 FROM J9.5 TO S9.5
Correction
Resolved
08/27/2004
None SHEET S2.0 LINE S FROM 9.5 TO13
Correction
Resolved
08/27/2004
PERIMETER SPREAD FOOTING SHEET 2.0 FROM A7.6 TO G1; J13 TO S13
Correction
Resolved
08/27/2004
None A LINE 9.8 TO 12.2 B8 12.1 G LINE THRU J TO 15 LINE N
Correction
Resolved
08/27/2004
None SHEET 2.0 - LINE 12.2 FROM LINE B.8 TO LINE G.4
Correction
Resolved
08/27/2004
None SHEET S2.0 LINE 1.0 TO LINE 1.8 AT LINE G TO K
Correction
Resolved
08/27/2004
None SHEET S2.0 LINE RUNNING FROM J TO M AT LINES 7.5 TO 7.8
Correction
Resolved
08/27/2004
None SHEET S2.0 LINE 7.5 FROM M.1 TO T
Correction
Resolved
08/27/2004
None SHEET S2.1 LINE W.9 FROM 1.8 TO 7.4 LINE 1.8 FROM LINE T TO W.9
Piers/Caissons Inspection - Commercial Partial 08/27/2004
Correction
Partial Correction
08/27/2004
None SHEET S2.0 AT LINE C BY 3 & 8 AT LINE D BY 8 AT LINE E BY 8 AT LINE G BY 4 AT LINE G.8 BY 4.5 AT LINE H BY 1.8 AT LINE H.7 BY 4.5 ALL INTERIOR PADS APPROVED
Correction
Resolved
08/27/2004
None SHEET 2.0 LINE 7 BY LINES C, D, G, H LINE 3 BY LINE E
Underslab Plumbing Inspection - Commercial Partial 08/27/2004
Correction
Partial Correction
08/27/2004
None SHEET P1.1 SINK IN ROOM 161 TO 4" DRAIN LINE IN ROOM 165 THEN EAST/WEST TO CORRIDOR 175
Correction
Resolved
08/27/2004
None SHEET P1.3 RESTROOMS IN ROOMS 180 & 184
Correction
Resolved
08/27/2004
None SHEET P1.3 ROOM 181 - NORTH LATERALS NOT GRAVELED - DO NOT COVER LINE V.5 FROM 4.4 TO 6.8 - OKAY TO COVER PRESSURED TEST OKAY
Underslab Plumbing Inspection - Commercial Partial 08/30/2004
Correction
Partial Correction
08/30/2004
None SHEET P1.1 ROOMS 164, 172, 108,113
Correction
Resolved
08/30/2004
None SHEET P1.1 SINK IN ROOM 161 TO 4" DRAIN LINE IN ROOM 165 THEN EAST/WEST TO CORRIDOR 175
Underslab Plumbing Inspection - Commercial Partial 08/31/2004
Correction
Partial Correction
08/31/2004
None SHEET P1.1 ROOMS 114, 115, 116
Correction
Resolved
08/31/2004
None SHEET P1.1 ROOMS 164, 172, 108,113
Piers/Caissons Inspection - Commercial Partial 08/31/2004
Correction
Partial Correction
08/31/2004
None SHEET S2.0 LINE 2 BY LINE B LINE J BY LINE O.6 LINE J.R BY LINE O.8
Correction
Resolved
08/31/2004
None SHEET S2.0 AT LINE C BY 3 & 8 AT LINE D BY 8 AT LINE E BY 8 AT LINE G BY 4 AT LINE G.8 BY 4.5 AT LINE H BY 1.8 AT LINE H.7 BY 4.5 ALL INTERIOR PADS APPROVED
Underslab Plumbing Inspection - Commercial Partial 09/02/2004
Correction
Partial Correction
09/02/2004
None SHEET P1.1 ROOF DRAIN LINE - LINE D FROM 1 TO 9.5 6" LINE AT LINES 4.3 BY D.1 RUNNING NORTH - SOUTH TURNING EAST TO CLEANOUT AT 4.5 BY D.8
Correction
Resolved
09/02/2004
None SHEET P1.1 ROOMS 114, 115, 116
Underslab Plumbing Inspection - Commercial Passed 09/07/2004
Correction
Resolved
09/07/2004
None SHEET P1.1 ROOF DRAIN LINE - LINE D FROM 1 TO 9.5 6" LINE AT LINES 4.3 BY D.1 RUNNING NORTH - SOUTH TURNING EAST TO CLEANOUT AT 4.5 BY D.8
Correction
Resolved
09/07/2004
None
Underground Electrical Inspection - Commercial Partial 09/07/2004
Correction
Partial Correction
09/07/2004
None FROM TRANSFORMER SITE TO MDP
Underground Electrical Inspection - Commercial Request Complete 9/3/2004 9/7/2004 09/07/2004
Underslab Electrical Inspection - Commercial Partial 09/23/2004
Correction
Partial Correction
09/23/2004
None ROOMS 140 - 152, 175 - 187
Underslab Electrical Inspection - Commercial Partial 09/27/2004
Correction
Resolved
09/27/2004
None ROOMS 140 - 152, 175 - 187
Correction
Partial Correction
09/27/2004
None ROOMS135-136, 137A, 132, 133, 138, 139 SHEET E1.2 FROM LINE H SOUTH - APPROVED SHEET E1.2 FROM LINE H NORTH - NOT READY FOR INSPECTION - DO NOT COVER
Underslab Plumbing Inspection - Commercial Passed 09/29/2004
Underslab Electrical Inspection - Commercial Partial 09/29/2004
Correction
Resolved
09/29/2004
None ROOMS135-136, 137A, 132, 133, 138, 139 SHEET E1.2 FROM LINE H SOUTH - APPROVED SHEET E1.2 FROM LINE H NORTH - NOT READY FOR INSPECTION - DO NOT COVER
Correction
Partial Correction
09/29/2004
None SHEET E1.1 ROOMS 101 - 129, 132, 133, 134, 137A
Electrical Service Inspection Partial 10/05/2004
Correction
Partial Correction
10/05/2004
None TEMPORARY SERVICE - 3 PHASE, 480 VOLTS
Underslab Electrical Inspection - Commercial Passed 10/05/2004
Correction
Resolved
10/05/2004
None MECHANICAL ROOM
Correction
Resolved
10/05/2004
None SHEET E1.1 ROOMS 101 - 129, 132, 133, 134, 137A
Rough Plumbing Inspection - Commercial Partial 10/21/2004
Correction
Partial Correction
10/21/2004
None ROOM 139
Correction
Partial Correction
10/21/2004
None ROOM 139
Rough Plumbing Inspection - Commercial Partial 12/28/2004
Correction
Resolved
12/28/2004
None ROOM 139
Correction
Resolved
12/28/2004
None ROOM 139
Correction
Partial Correction
12/28/2004
None ALL EXCEPT - ABOVE ROOM 136 ON EAST SIDE OF BUILDING AND ROOM 156 ON WEST SIDE OF ROOM Roof Drain System
Rough Plumbing Inspection - Commercial Passed 12/29/2004
Correction
Resolved
12/29/2004
None ALL EXCEPT - ABOVE ROOM 136 ON EAST SIDE OF BUILDING AND ROOM 156 ON WEST SIDE OF ROOM Roof Drain System
Correction
Resolved
12/29/2004
None Roof Drain Sytem
Rough Electrical Inspection - Commercial Partial 01/07/2005
Correction
Partial Correction
01/07/2005
None ROOMS 103 - 129
Correction
Corrective Action Required
01/07/2005
None ROOMS 103 - 129 Above Ceiling
Water Service Inspection Partial 01/07/2005
Correction
Resolved
01/07/2005
None SHEET P1.0 - LOCATION OF WATER METER CHANGED BY DISTRICT 13. NEW SITE APPROX. 40` WEST OF ORIGINAL SITE. A 20` SECTION APPROXIMATELY 20` FROM NEW METER SITE INSTALLED. COVER AT OWN RISK
Underground Electrical Inspection - Commercial Passed 01/07/2005
Correction
Resolved
01/07/2005
None FROM TRANSFORMER SITE TO MDP
Footing Inspection - Commercial Passed 01/07/2005
Correction
Resolved
01/07/2005
None SHEET S2.0 A LINE FROM 7 TO 9.8
Piers/Caissons Inspection - Commercial Passed 01/07/2005
Correction
Resolved
01/07/2005
None SHEET S2.0 LINE 2 BY LINE B LINE J BY LINE O.6 LINE J.R BY LINE O.8
Underslab Plumbing Inspection - Commercial Passed 01/07/2005
Rough Plumbing Inspection - Commercial Passed 01/18/2005
Correction
Resolved
01/18/2005
None DWV & WATER - ROOMS 132 & 133
Rough Plumbing Inspection - Commercial Passed 01/19/2005
Correction
Resolved
01/19/2005
None IN-WALL DVW & WATER APPROVED FOR ROOMS 114-117/103/108/112/161-164/172/175 AND FOR ALTERNATE BUILDING EXTENSION
Rough Framing Inspection - Commercial Passed 01/20/2005
Correction
Resolved
01/20/2005
None SHEET A2.1 DROM LINE A TO T X 1 TO 9
Rough Plumbing Inspection - Commercial Partial 01/20/2005
Correction
Partial Correction
01/20/2005
None ROOMS 140, 143, 144, 145, 146, 149, 150 ROOMS 155 -155 WATER LINES NOT COMPLETE
Rough Plumbing Inspection - Commercial Passed 01/21/2005
Correction
Resolved
01/21/2005
None ROOMS 140, 143, 144, 145, 146, 149, 150, 155
Electrical Service Inspection Partial 01/21/2005
Correction
Resolved
01/21/2005
None TEMPORARY SERVICE - 3 PHASE, 480 VOLTS
Correction
Partial Correction
01/21/2005
None 1600 AMP, 3 POLE FEED LINES FROM TRANSFORMERS INSTALLED NO LINES OUT - NO SUBPANELS Main Panel
Electrical Service Inspection Passed 01/28/2005
Correction
Resolved
01/28/2005
None 1600 AMP, 3 POLE FEED LINES FROM TRANSFORMERS INSTALLED NO LINES OUT - NO SUBPANELS Main Panel
Correction
Resolved
01/28/2005
None SHEET 6.1 SUBPANELS H1, H2, H3, LOW VOLTAGE RELAY & T.V.S.S.
Rough Framing Inspection - Commercial Partial 02/04/2005
Correction
Partial Correction
02/04/2005
None SHEET A2.1 FROM LINE A TO T X 1 TO 9 SHEET A2.1 FROM LINE T.1 TO X 1 TO 7.5 SHEET A2.1 FROM LINE A TO S X 9.7 TO 13 PROVIDE APPROVED DETAIL FOR SMOKE PARTITIONS
Gas Piping Inspection - Commercial Failed 02/04/2005
Correction
Corrective Action Required
02/04/2005
Gas Piping Support (IRC) INSTALL CLAMPS ON SUPPORTS Roof
Gas Service Inspection - Commercial Passed 02/04/2005
Correction
Resolved
02/04/2005
None HELD 60 PSI. RELEASE METER
Rough Electrical Inspection - Commercial Partial 02/04/2005
Correction
Resolved
02/04/2005
None ROOMS 161 TO 187
Rough Electrical Inspection - Commercial Partial 02/11/2005
Correction
Resolved
02/11/2005
None ROOMS 100, 101, 149-151, 153-159
Rough Electrical Inspection - Commercial Partial 02/14/2005
Correction
Resolved
02/14/2005
None ROOMS 103 - 129
Correction
Resolved
02/14/2005
None ROOMS 161 TO 187
Correction
Resolved
02/14/2005
None ROOMS 100, 101, 149-151, 153-159, 140 - 148, 152, 130, 160, ROOM 102 ROCKED WITHOUT INSPECTION
Rough Electrical Inspection - Commercial Passed 02/25/2005
Correction
Resolved
02/25/2005
None ROOMS 103 - 129
Correction
Resolved
02/25/2005
None ROOMS 132 & 133
Electrical Service Inspection Passed 02/25/2005
Correction
Resolved
02/25/2005
None SHEET 6.1 SUBPANELS H1, H2, H3, LOW VOLTAGE RELAY & T.V.S.S. Room 137
Correction
Resolved
02/25/2005
None SUBPANELS C & L WITH TRANSFORMERS Room 107
Correction
Resolved
02/25/2005
None SUBPANELS L1 & C1 WITH TRANSFORMERS Room 158
Correction
Resolved
02/25/2005
None SUBPANELS L2 WITH TRANSFORMER & C2 Room 172
Above Ceiling Inspection Failed 02/25/2005
Correction
Corrective Action Required
02/25/2005
See Comment REMOVE SHEETROCK FROM SOFFITS ACROSS CORRIDORS 130, 130a, & 160 FOR INSPECTION. NOTE: THERE ARE NO AREAS IN THIS BUILDING THAT ARE READY FOR CEILING SHEETROCK.
Above Ceiling Inspection Partial 03/08/2005
Correction
Resolved
03/08/2005
See Comment REMOVE SHEETROCK FROM SOFFITS ACROSS CORRIDORS 130, 130a, & 160 FOR INSPECTION. NOTE: THERE ARE NO AREAS IN THIS BUILDING THAT ARE READY FOR CEILING SHEETROCK.
Correction
Partial Correction
03/08/2005
None ROOM 101 SOFFIT AREAS ROOM 102 - SOFFIT AREA AT NORTH & WEST SIDES ROOMS 101 & 102
Rough Framing Inspection - Commercial Request Complete 3/7/2005 3/8/2005 03/08/2005
Above Ceiling Inspection Partial 03/31/2005
Correction
Resolved
03/31/2005
None ROOM 101 SOFFIT AREAS ROOM 102 - SOFFIT AREA AT NORTH & WEST SIDES SOFFITS
Correction
Partial Correction
03/31/2005
None SOFFITS IN CORRIDORS - 130, 160,141, 152 & VESTABULE 100 SOFFITS
Rough Framing Inspection - Commercial Partial 03/31/2005
Correction
Partial Correction
03/31/2005
See Comment SHEET A2.1 - SMOKE PARTITIONS - ROOMS 167, 122, 123, 125 APPROVED ROOMS - 135, 140, 158 - NOT READY
Above Ceiling Inspection Partial 04/08/2005
Correction
Resolved
04/08/2005
See Comment REMOVE SHEETROCK FROM SOFFITS ACROSS CORRIDORS 130, 130a, & 160 FOR INSPECTION. NOTE: THERE ARE NO AREAS IN THIS BUILDING THAT ARE READY FOR CEILING SHEETROCK. Soffits
Correction
Resolved
04/08/2005
None ROOM 101 SOFFIT AREAS ROOM 102 - SOFFIT AREA AT NORTH & WEST SIDES Soffits
Correction
Resolved
04/08/2005
None SOFFITS IN CORRIDORS - 130, 160,141, 152 & VESTABULE 100 Soffits
Correction
Partial Correction
04/08/2005
None ROOM 104, 105, 106, 107, 108, 109, 110, 111, 112, 113, 114, 115, 116, 117, 119, 120, 121, 122, 123, 124, 125, 126, 127, 128, 129, 161, 162, 163, 164, 165, 166, 167, 170, 171, 172, 173, 174, 176, 177, 178, 179, 180, 181, 182, 183, 184, 185, 186, 187,
Above Ceiling Inspection Partial 04/15/2005
Correction
Corrective Action Required
04/15/2005
NOT READY
Above Ceiling Inspection Partial 04/20/2005
Correction
Partial Correction
04/20/2005
None INSPECTED ALL REMAINING ROOMS, SMOKE PARTITION RMS 158/140/135, CORRIDOR/SOFFIT EXCEPT RM 138-139 (KITCHEN NOT COMPLETED)
Above Ceiling Inspection Passed 05/05/2005
Correction
Resolved
05/05/2005
None ROOM 104, 105, 106, 107, 108, 109, 110, 111, 112, 113, 114, 115, 116, 117, 119, 120, 121, 122, 123, 124, 125, 126, 127, 128, 129, 161, 162, 163, 164, 165, 166, 167, 170, 171, 172, 173, 174, 176, 177, 178, 179, 180, 181, 182, 183, 184, 185, 186, 187,
Correction
Resolved
05/05/2005
NOT READY
Correction
Resolved
05/05/2005
None INSPECTED ALL REMAINING ROOMS, SMOKE PARTITION RMS 158/140/135, CORRIDOR/SOFFIT EXCEPT RM 138-139 (KITCHEN NOT COMPLETED) ROOM 101 INSPECTED
Rough Framing Inspection - Commercial Passed 05/05/2005
Correction
Resolved
05/05/2005
None SHEET A2.1 FROM LINE A TO T X 1 TO 9 SHEET A2.1 FROM LINE T.1 TO X 1 TO 7.5 SHEET A2.1 FROM LINE A TO S X 9.7 TO 13 PROVIDE APPROVED DETAIL FOR SMOKE PARTITIONS
Correction
Resolved
05/05/2005
See Comment SHEET A2.1 - SMOKE PARTITIONS - ROOMS 167, 122, 123, 125 APPROVED ROOMS - 135, 140, 158 - NOT READY [SEE ABOVE CEILING INSPECTION DATED 20 APRIL 2005]
Gas Piping Inspection - Commercial Failed 05/05/2005
Correction
Corrective Action Required
05/05/2005
Gas Piping Support (IRC) INSTALL CLAMPS ON SUPPORTS Roof
Rough Framing Inspection - Commercial Partial 05/19/2005
Correction
Partial Correction
05/19/2005
See Comment SHEET A2.1 - SMOKE PARTITIONS - ROOMS 167, 122, 123, 125 APPROVED ROOMS - 135, 140, 158 - NOT READY [SEE ABOVE CEILING INSPECTION DATED 20 APRIL 2005]
Sewer Service Inspection Partial 05/19/2005
Water Service Inspection Partial 05/19/2005
Correction
Partial Correction
05/19/2005
None FROM PREVIOUS POINT - APPROVED 80` EAST
Electrical Service Inspection Passed 05/19/2005
Occupancy Inspection - Codes Commercial Failed 05/19/2005
Correction
Corrective Action Required
05/19/2005
Receive Fire Department approval RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
05/19/2005
Receive Planning & Development Approval RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
05/19/2005
Receive Public Works Approval RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
05/19/2005
Special Inspections
Correction
Corrective Action Required
05/19/2005
Receive Water Utilities Approval RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
05/19/2005
ADA Requirements PIPE COVERS All Restrooms
Correction
Corrective Action Required
05/19/2005
Smoke Partition BLOCK PENTRATIONS IN WALL ADJACENT TO ROOM 158
Correction
Corrective Action Required
05/19/2005
Not Ready WORK NOT COMPLETED FLOORING NOT FINISHED IN CORRIDORS RESTROOMS 132 & 133 NOT FINISHED 108, 169, 102, 118, GYM
Correction
Corrective Action Required
05/19/2005
Panel Circuit Identification (IRC) SUBPANELS L, L1, L2, H1, H2, H3 - NUMBER ALL BREAKERS/BLANKS
Correction
Corrective Action Required
05/19/2005
Bathroom GFCI Receptacles (IRC) NO OUTLETS 114, 115
Correction
Corrective Action Required
05/19/2005
See Comment DO NOT OCCUPY
Water Service Inspection Partial 05/26/2005
Rough Framing Inspection - Commercial Passed 05/26/2005
Correction
Resolved
05/26/2005
See Comment SHEET A2.1 - SMOKE PARTITIONS - ROOMS 167, 122, 123, 125 APPROVED ROOMS - 135, 140, 158 - [SEE ABOVE CEILING INSPECTION DATED 20 APRIL 2005]
Gas Piping Inspection - Commercial Passed 05/26/2005
Correction
Resolved
05/26/2005
Gas Piping Support (IRC)
Sewer Service Inspection Partial 05/26/2005
Special Inspections Failed 05/26/2005
Correction
Corrective Action Required
05/26/2005
Final Report NOT RECEIVED
Occupancy Inspection - Codes Commercial Failed 05/26/2005
Correction
Resolved
05/26/2005
ADA Requirements PIPE COVERS All Restrooms 132, 133, 163,
Correction
Resolved
05/26/2005
Smoke Partition
Correction
Corrective Action Required
05/26/2005
Not Ready DOORS NOT COMPLETED 118, 169 RESTROOMS 132 & 133 NOT FINISHED ADA PIPE COVERS - 163
Correction
Resolved
05/26/2005
Bathroom GFCI Receptacles (IRC) NO OUTLETS 114, 115
Correction
Resolved
05/26/2005
See Comment
Correction
Resolved
05/26/2005
Panel Circuit Identification (IRC) SUBPANELS L, L1, L2, H1, H2, H3 - NUMBER ALL BREAKERS/BLANKS
Water Service Inspection Passed 06/10/2005
Correction
Resolved
06/10/2005
None FROM PREVIOUS POINT - APPROVED 80` EAST SEE LETTER - CRAWFORD MCHANICAL CONTRACTORS
Sewer Service Inspection Passed 06/10/2005
Correction
Resolved
06/10/2005
None 150 FT 6IN SDR SEE LETER CRAWFORD MECHANICAL CONTRACTORS
Occupancy Inspection - Codes Commercial Failed 07/18/2005
Correction
Resolved
07/18/2005
ADA Requirements
Correction
Resolved
07/18/2005
Smoke Partition
Correction
Corrective Action Required
07/18/2005
Not Ready ADA PIPE COVERS - 163
Correction
Resolved
07/18/2005
Bathroom GFCI Receptacles (IRC)
Correction
Resolved
07/18/2005
See Comment
Correction
Resolved
07/18/2005
Panel Circuit Identification (IRC)
Occupancy Inspection - Codes Commercial Failed 07/19/2005
Correction
Resolved
07/19/2005
Receive Fire Department approval see e-mail dated 7/18/05 from Neil Ullrey
Correction
Resolved
07/19/2005
Receive Public Works Approval see e-mail dated 7/18/05 from Bill Lyon
Occupancy Inspection - Codes Commercial Failed 07/20/2005
Correction
Resolved
07/20/2005
Special Inspections
Correction
Resolved
07/20/2005
Not Ready
Occupancy Inspection - Codes Commercial Passed 07/26/2005
Correction
Resolved
07/26/2005
Receive Planning & Development Approval
Correction
Resolved
07/26/2005
Receive Water Utilities Approval
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home