Summary
B0400130
Building Permit - Commercial
Certificate of Occupancy
BANK OF AMERICA NA
NEW COMMERCIAL
FULL BUILDING PERMIT
01/26/2004
04/23/2004
10/20/2004
11/17/2004
Locations
Contacts
SCHWEIGER CONSTRUCTION CO, Address:8300 TROOST  
SITE DEVELOPMENT ENG. INC., Address:STEVE RUSH  
BANK OF AMERICA NA, Address:101 N TRYON ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/24/2004 10/29/2010
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Raintree 150 Center - The Developer shall design, engineer and construct the Road Improvements. The City shall issue no temporary or final Certificate of Occupancy for any of the Development until the City or MoDot, as appropriate, has issued a Certificate of Substantial Completion for each of the Road Improvements.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Fire Derpartment; When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - 2000 IPC 403.6 - Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. Public toilet facilities shall be located not more than one story above or below the space required to be provided with public toilet facilites and the path of travel to such facilities shall not exceed a distance of 500 feet.
Correction

CA - 2000 IPC 312.1 - Required tests. The permit holder shall make the applicable test prescribed in Sections 312.2 through 312.9 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the code official when the plumbing work is ready for tests. The equipment, material, power and labor necessary for the inspection and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. All plumbing system piping shall be tested with either water or air. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be submitted to final tests. The code official shall require the removal of any cleanouts if necessary to ascertain if the pressure has reached all parts of the system. Note: Testing of the plumbing system is not required to be witnessed by the Codes Administration Staff with the exception of gas piping.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $3,167.00 $3,167.00 Paid 04/23/2004
24 BLDG Plan Check Fees $72.75 $72.75 Paid 04/23/2004
25 Electrical Permit Fee $266.78 $266.78 Paid 04/23/2004
25 Mechanical Permit Fees $157.50 $157.50 Paid 04/23/2004
25 Plumbing Permit Fees $69.50 $69.50 Paid 04/23/2004
84 Water Meters $600.00 $600.00 Paid 04/23/2004
85 Water Taps $6,835.00 $6,835.00 Paid 04/23/2004
89 Sewer Tap Fees $240.00 $240.00 Paid 04/23/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 04/14/2004
Correction
Resolved
04/14/2004
None COLUMN PILASTERS AND GRADE BEAM FOR CANOPY
Underground Electrical Inspection - Commercial Passed 04/26/2004
Correction
Resolved
04/26/2004
None UNDERGROUND CONDUIT TO THE NORTH FOR THE SIGN AND UNDERGROUND CONDUIT FROM SE CORNER OF THE BUILDING OUT APPROXIMATELY 20'
Underground Electrical Inspection - Commercial Request Complete 4/23/2004 4/26/2004 04/26/2004
Underground Electrical Inspection - Commercial Passed 04/27/2004
Correction
Resolved
04/27/2004
None ADDITIONAL UNDER GROUND CONDUIT TO CANOPY STRUCTURE
Sewer Service Inspection Passed 04/27/2004
Correction
Resolved
04/27/2004
None INSERT-A-TEE USED AT MAIN/APPROVED BY SHAWN WITH PUBLIC WORKS
Sewer Service Inspection - Commercial Request Complete 4/26/2004 4/27/2004 04/27/2004
Underground Electrical Inspection - Commercial Request Complete 4/26/2004 4/27/2004 04/27/2004
Underground Plumbing Inspection - Commercial Passed 04/28/2004
Correction
Resolved
04/28/2004
None UNDERGROUND ROOF DRAINAGE
Underslab Electrical Inspection - Commercial Passed 04/28/2004
Correction
Resolved
04/28/2004
None
Underground Plumbing Inspection - Commercial Request Complete 4/27/2004 4/28/2004 04/28/2004
Underground Electrical Inspection - Commercial Request Complete 4/28/2004 4/28/2004 04/28/2004
Underground Electrical Inspection - Commercial Passed 04/29/2004
Correction
Resolved
04/29/2004
None SECONDARY TO TRANSFORMER
Underground Electrical Inspection - Commercial Request Complete 4/28/2004 4/29/2004 04/29/2004
Underslab Electrical Inspection - Commercial Passed 05/04/2004
Correction
Resolved
05/04/2004
None UNDERGROUND CONDUIT FOR LIGHT POLES ON THE WEST AND NORTH SIDE OF THE BUILDING
Water Service Inspection Passed 05/11/2004
Correction
Resolved
05/11/2004
None APPROXIMATELY 90' OF 1-1/2" COPPER WATER LINE FROM THE MAIN TO THE METER. METER SET AND TAP COMPLETE
Water Service Inspection - Commercial Request Complete 5/10/2004 5/11/2004 05/11/2004
All Rough Inspection - Commercial Failed 06/11/2004
Correction
Corrective Action Required
06/11/2004
Water/DWV Preotection Againd Physical Damage (IRC) BREAKRM REQUIRES NAIL PLATE
Correction
Corrective Action Required
06/11/2004
INSTALL WINDOWS AND DOORS
Correction
Corrective Action Required
06/11/2004
Prevent Physical Damage (IRC) NAIL PLATE AT POST OFFICE #4 THROUGHOUT Office
Correction
Corrective Action Required
06/11/2004
Stud Drilling and Notching (IRC) STUD NOTCHING NAIL PLATE FOR PLUMBING LOBBY South
Correction
Corrective Action Required
06/11/2004
NOT FINISHED
Correction
Corrective Action Required
06/11/2004
NOT FINISHED
Correction
Corrective Action Required
06/11/2004
FASTENING OF STUD NOT FASTENED TO TOP PLATE Bathroom
Correction
Corrective Action Required
06/11/2004
None OK TO INSULATE DO NOT ROCK CALL FOR REINSPECTION
All Rough Inspection - Commercial Partial 06/15/2004
Correction
Resolved
06/15/2004
Water/DWV Preotection Againd Physical Damage (IRC) BREAKRM REQUIRES NAIL PLATE
Correction
Resolved
06/15/2004
Prevent Physical Damage (IRC) NAIL PLATE AT POST OFFICE #4 THROUGHOUT Office
Correction
Resolved
06/15/2004
Stud Drilling and Notching (IRC) STUD NOTCHING NAIL PLATE FOR PLUMBING LOBBY South
Correction
Corrective Action Required
06/15/2004
NOT FINISHED CHECK AT ABOVE CEILING PASSED FOR SHEETROCK
Correction
Corrective Action Required
06/15/2004
NOT FINISHED CHECK AT ABOVE CEILING PASSED FOR SHEETROCK
Correction
Resolved
06/15/2004
FASTENING OF STUD NOT FASTENED TO TOP PLATE Bathroom
Correction
Resolved
06/15/2004
None OK TO INSULATE OK TO ROCK
Electrical Service Inspection Passed 06/21/2004
Correction
Resolved
06/21/2004
None RELEASE 600 AMP SERVICE. 3 SEPARATE GROUNDING ELECTRODES. WATER, STRUCTURAL STEEL, AND DRIVEN GROUND ROD.
Gas Service Inspection - Commercial Passed 07/23/2004
Correction
Resolved
07/23/2004
None 26 P.S.I. HELD 10 MIN.
Gas Piping Inspection - Commercial Passed 07/23/2004
Correction
Resolved
07/23/2004
None
Above Ceiling Inspection Passed 07/28/2004
Correction
Resolved
07/28/2004
None
Occupancy Inspection - Codes Commercial Failed 08/09/2004
Correction
Corrective Action Required
08/09/2004
WATER HEATER OVERFLOW PIPE NEEDS TO EXTEND WITHIN 6 INCHES FROM FLOOR.
Correction
Corrective Action Required
08/09/2004
GAS PIPING SECURE GAS PIPING AT ROOF DECK. ROOF
Correction
Corrective Action Required
08/09/2004
Receive Public Works Approval SEPARATE COVER.
Correction
Corrective Action Required
08/09/2004
Receive Planning & Development Approval SEPARATE COVER
Correction
Corrective Action Required
08/09/2004
FIRE APPROVAL REPAIR BACK UP EXIT LIGHTING BY CUSTODIAL CLOSET. PROVIDE FIRE EXTINGUISHERS.
Correction
Corrective Action Required
08/09/2004
Receive Water Utilities Approval SUBMIT BACKFLOW TESTS TO WATER UTILITIES.
Correction
Corrective Action Required
08/09/2004
TRAFFIC OBTAIN SUBSTANTIAL COMPLETION FROM MODOT FOR TRAFFIC. REQUIRED TO OBTAIN TCO. OKAY TO OCCUPY STAFF AND STOCK. DO NOT OPEN TO PUBLIC.
Occupancy Inspection - Codes Commercial Failed 08/13/2004
Correction
Resolved
08/13/2004
TRAFFIC
Occupancy Inspection - Codes Commercial Failed 10/15/2004
Correction
Resolved
10/15/2004
WATER HEATER OVERFLOW
Correction
Resolved
10/15/2004
GAS PIPING ROOF
Correction
Resolved
10/15/2004
Receive Public Works Approval
Correction
Corrective Action Required
10/15/2004
Receive Planning & Development Approval SEPARATE COVER
Correction
Resolved
10/15/2004
Receive Water Utilities Approval
Occupancy Inspection - Codes Commercial Passed 11/16/2004
Correction
Resolved
11/16/2004
Receive Planning & Development Approval
Correction
Resolved
11/16/2004
FIRE APPROVAL
All Rough Inspection - Commercial Passed 11/17/2004
Correction
Resolved
11/17/2004
INSTALL WINDOWS AND DOORS
Correction
Resolved
11/17/2004
NOT FINISHED
Correction
Resolved
11/17/2004
NOT FINISHED
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home