Permit Application Status

B0400068


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0400068
Building Permit - Commercial
Final Completion
CABRA PROPERTIES LLC
NEW COMMERCIAL
BUILDING A DOUGLAS STATION MINI STORAGE
01/13/2004
03/17/2004
09/13/2004
09/24/2004
Locations
Contacts
DAVIDSON DESIGN GROUP, Address:11301STRANG LINE ROAD  
TOUCHMARK CONSTRUCTION, Address:PO BOX 528  
CABRA PROPERTIES LLC, Address:13613 S US 71 HWY  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/11/2004 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - The plans indicate that the construction type for this project is Type V-B and we have determined the occupancy type type be S-1 (combustible storage). The basic allowable area for this combination is 9,000 square feet. The area of this building is 16,450 square feet.
Correction

Fire Department- The fire hydrant next to this building shall be provided with Bollards for vehicle protection. The hydrant shall not be obstructed by landscaping (ref. L-1.1).
Correction

CA - 2000 IBC 1107.6 - Self-service storage facilities. Self-service storage facilities shall provide accessible individual self-storage spaces in accordance with Table 1107.6.
Correction

CA - 2000 IBC 1107.6.1 - Dispersion. Accessible individual self-service storage spaces shall be dispersed throughout the various classes of spaces provided. Where more classes of spaces are provided than the number of required accessible spaces, the number of accessible spaces shall not be required to exceed that required by Table 1107.6. Accessible spaces are permitted to be dispersed in a single building of a multibuilding facility.
Correction

CA - Information was not provided on the materials to be used for the mechanical and electrical installation.
Correction

CA - Provide the construction cost of this building.
Correction

CA - I am unclear as to the type of insulated panel being used.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - Placement of required exit signage and emergency lighting is subject to onsite inspection.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1003.2.10 - Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visable to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible exit sign.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; An approved lock shall be installed on gates or similar barriers when required by the code official.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $731.00 $731.00 Paid 03/17/2004
24 BLDG Plan Check Fees $32.15 $32.15 Paid 03/17/2004
25 Electrical Permit Fee $80.00 $80.00 Paid 03/17/2004
25 Mechanical Permit Fees $85.00 $85.00 Paid 03/17/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Foundation Inspection - Commercial Partial 02/26/2004
Correction
Partial Correction
02/26/2004
FOUNDATION WALL EAST 120' OF N WALL
Foundation Inspection - Commercial Passed 02/27/2004
Correction
Resolved
02/27/2004
FOUNDATION WALL NOW COMPLETE COMBO RETAINING WALL PER SHTS 2& 3 SECT 3/2
Rough Framing Inspection - Commercial Partial 05/11/2004
Correction
Partial Correction
05/11/2004
STEEL FRAMING & SIDING SHEET ONE SIDE OK TO COVER WHEN READY
Rated Assembly Inspection Failed 07/08/2004
Correction
Corrective Action Required
07/08/2004
GYPSUM WALLBOARD @ 3-HR FIREWALL RECOMMEND GC CALL TO DISCUSS NOT PER DRAWING NOT PER UL SYSTEM 435
Rough Framing Inspection - Commercial Passed 07/08/2004
Correction
Resolved
07/08/2004
STEEL FRAMING & SIDING SHEET ONE SIDE
Rated Assembly Inspection Failed 07/19/2004
Correction
Corrective Action Required
07/19/2004
GYPSUM WALLBOARD @ 3-HR FIREWALL EXAMPLE: N & S ENDS OF E FACE. SEE UL DESIGN #435 DESCRIPTION ATTACHED FOR REQUIREMENTS FOR 2ND & 3RD LAYERS. NOT ALL EDGES OF ALL SHEETS/PIECES ARE SCREWED
Rated Assembly Inspection Partial 07/28/2004
Correction
Partial Correction
07/28/2004
GYPSUM WALLBOARD @ 3-HR FIREWALL ON 3RD LAYER STAGGER JOINTS PER U.L. SCREW EDGES @ 8" MAX & FIELD @ 12" MAX 2ND GWB LAYER APPROVED OK TO COVER WHEN READY
Rated Assembly Inspection Passed 08/02/2004
Correction
Resolved
08/02/2004
GYPSUM WALLBOARD @ 3-HR FIREWALL 3RD LAYER APPROVED OK TO COVER WHEN READY
Final Inspection - Commercial Passed 09/23/2004
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home