Permit Application Status

B0400023


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0400023
Building Permit - Commercial
Certificate of Occupancy
TI SUMMIT CREST PLAZA LLC
NEW TENANT FINISH
SUNSHINE TANZ TENANT FINISH
01/06/2004
01/16/2004
07/14/2004
06/17/2005
Locations
Contacts
HIRST AND ASSOCIATES PC, Address:621 NE WOODS CHAPEL RD  
DAN REELE, Address:801 RAVEN DR  
TI SUMMIT CREST PLAZA LLC, Address:7611 STATE LINE RD STE 301  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/04/2004 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

Fire Department- Provide fire alarm notification devices in the space. Devices shall be activated by the building alarm system monitoring fire sprinkler water flow.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IMC 304.8 - Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade or shall be suspended a minimum of 6 inches (152 mm) aboave adjoining grade.
Correction

CA - 2000 IPC 308.5 - Pipe shall be supported in accordance with Table 308.5.
Correction

CA - 2000 IPC 312.1 - Required tests. The permit holder shall make the applicable test prescribed in Sections 312.2 through 312.9 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the code official when the plumbing work is ready for tests. The equipment, material, power and labor necessary for the inspection and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. All plumbing system piping shall be tested with either water or air. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be submitted to final tests. The code official shall require the removal of any cleanouts if necessary to ascertain if the pressure has reached all parts of the system. Note: Testing of the plumbing system is not required to be witnessed by the Codes Administration Staff with the exception of gas piping.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $257.00 $257.00 Paid 01/16/2004
24 BLDG Plan Check Fees $18.50 $18.50 Paid 01/16/2004
25 Electrical Permit Fee $98.96 $98.96 Paid 01/16/2004
25 Mechanical Permit Fees $41.50 $41.50 Paid 01/16/2004
25 Plumbing Permit Fees $39.00 $39.00 Paid 01/16/2004
89 Sewer Tap Fees $180.00 $180.00 Paid 01/16/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 01/30/2004
Correction
Resolved
01/30/2004
None PROVIDE CLEANOUT
All Rough Inspection - Commercial Failed 02/17/2004
Correction
Partial Correction
02/17/2004
None IN WALLS ONLY/OK TO SHEETROCK
Rough Electrical Inspection - Commercial Failed 02/26/2004
Correction
Corrective Action Required
02/26/2004
None FINISH INSTALLATION ATPANEL
Electrical Service Inspection Passed 03/04/2004
Rough Electrical Inspection - Commercial Failed 03/04/2004
Correction
Partial Correction
03/04/2004
None COMPLETE TRANSFORMER INSTALLS COMPLETE PULLED WIRE REMOVE SYSTEMS FOREIGN TO SPRINKLER LINES
Above Ceiling Inspection Failed 03/04/2004
Correction
Partial Correction
03/04/2004
SEE TEXT SET DIFFUSERS BLANK OPEN BOXES/UNUSED KO OK TO PAD--LEAVE EDGE COURSE (NOT BORDER) OPEN FOR INSPECTION
All Rough Inspection - Commercial Partial 03/04/2004
Correction
Partial Correction
03/04/2004
None
Above Ceiling Inspection Passed 03/11/2004
Correction
Resolved
03/11/2004
SEE TEXT
All Rough Inspection - Commercial Passed 03/11/2004
Correction
Resolved
03/11/2004
None
Rough Electrical Inspection - Commercial Passed 03/15/2004
Correction
Resolved
03/15/2004
None
Occupancy Inspection - Codes Commercial Failed 03/15/2004
Correction
Corrective Action Required
03/15/2004
DEMISING WALL PATCH HOLES IN DEMISING WALL/DO NOT OCCUPY/CALL FOR REINSPECTION ABOVE CELING
Correction
Corrective Action Required
03/15/2004
FLOOR DRAIN UNCOVER FLOOR DRAIN Janitor's Closet
Correction
Corrective Action Required
03/15/2004
ELECTRICAL PANELS IDENTIFY ALL CRCUITS
Correction
Corrective Action Required
03/15/2004
Receive Planning & Development Approval REQUIRE APPROVAL
Correction
Resolved
03/15/2004
Receive Public Works Approval NOT REQUIRED PER MIKE WEISENBORN
Occupancy Inspection - Codes Commercial Failed 03/16/2004
Correction
Resolved
03/16/2004
DEMISING WALL ABOVE CELING
Correction
Resolved
03/16/2004
FLOOR DRAIN Janitor's Closet
Correction
Resolved
03/16/2004
ELECTRICAL PANELS IDENTIFY ALL CRCUITS
Correction
Resolved
03/16/2004
Receive Public Works Approval NOT REQUIRED PER MIKE WEISENBORN
Occupancy Inspection - Codes Commercial Passed 06/16/2005
Correction
Resolved
06/16/2005
Receive Planning & Development Approval
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home