Permit Application Status

B0302183


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0302183
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
LEGACY PARK MAINTENANCE BUILDING
11/04/2003
05/11/2005
11/07/2005
08/13/2007
Locations
Contacts
HOLLIS & MILLER GROUP INC, Address:220 NW EXECUTIVE WAY  
CITY OF LEE'S SUMMIT PARKS AND REC., Address:GARY WELTY  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/19/2005 10/29/2010
Correction

Fire Department- The Owners Statement of Intended Use and submitted plans incicate that the building will be used for automotive service (S1) and wood working operations. Atomotive repair in non-separated buildings in excess of 3,000 square feet shall be provided with an automatic fire sprinkler system. Likewise, wood working operations in fire areas exceeding 2,500 square feet shall also be provided with an automatic fire sprinkler system or rated separation below 2,500 sq. feet. Provide rated separation between the areas or provide an automatic fire sprinkler system.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - Complete mechanical plans were not provided.
Correction

CA - Complete electrical plans were not provided.
Correction

CA - Complete plumbing plans were not provided.
Correction

CA - We can not perform a complete plan review until additional information is provided outlining the use of the spaces.
Correction

CA - A code analysis has not been provided.
Correction

CA - The location of the building sewer intrance is not the same on both Sheet C100 and M200.
Correction

CA - Copies of the engineered building package were not provided at the time of permit application.
Correction

CA - Information on the boiler system was not provided at the time of permit application.
Correction

Fire Department- A hydrant shall be provided within 100 feet of the fire department connection.
Correction

Fire Department- Indicate where the water for the sprinkler system will be coming from.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1108.4 - Where kitchen, kitchenettes and wet bars are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC/ANSI A117.1.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

CA - 2000 IBC 1202.2 - Attic spaces. Enclosed attics and enclosed rafter spaces formed where ceiling are applied directly to the underside of roof framing member shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain and snow. Blocking and bridging shall be arranged so as not to interfere with the movement of air. A minimum of 1 inch of air space shall be provided between the insulation and the roof sheathing. The net free ventilating area shll not be less than 1/150 of the area of the space ventilated, with 50 percent of the required ventilating area provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet above the eave or cornice vents with the balance of the required ventilation provided by eave or cornice vents.
Correction

Fire Department- Installation and use of fuel dispensers shall be in accordance with 2000 IFC, Sections 2203 through 2206.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; An approved lock shall be installed on gates or similar barriers when required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department; Buildings other than one- and two-family dwellings. The minimum fire flow and flow duration for buildings otherthan one- and two-family dwellings shall be as specified in Table B105.1.
Correction

CA - 2000 IMC 403.3 - Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and the occupant load or other perameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less then the number determined from the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

CA - 2000 IMC 304.8 - Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade or shall be suspended a minimum of 6 inches (152 mm) aboave adjoining grade.
Correction

CA - 2000 IPC 708.3.2 - Building sewers shall be provided with cleanouts located not more than 100 feet apart measured fron the upstream entrance of the cleanout. For building sewers 8 inches and larger, manholes shall be provided and located at each change in direction and at intervals of not more than 400 feet of developed length of the drainage piping.
Correction

CA - 2000 IPC 708.3.5 - Building drain and building sewer junction. There shall be a cleanout near the junction of the building drain and the building sewer. The cleanout shall be either inside or outside the building wall and shall be brought up to the finished ground level or the basement floor level. An approved two-way cleanout is allowed to be used at this location to serve as a required cleanout for both the building drain and building sewer. The cleanout at the junction of the building drain and building sewer shall not be required if the cleanout on a 3-inch (76 mm) or larger diameter soil stack is located within a developed length of 10 feet (3048 mm) of the building drain and building sewer connection.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $722.00 $722.00 Paid 05/11/2005
24 BLDG Plan Check Fees $32.00 $32.00 Paid 05/11/2005
25 Electrical Permit Fee $214.00 $214.00 Paid 05/11/2005
25 Mechanical Permit Fees $58.50 $58.50 Paid 05/11/2005
25 Plumbing Permit Fees $86.00 $86.00 Paid 05/11/2005
89 Sewer Tap Fees $450.00 $450.00 Paid 05/11/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Passed 06/01/2005
Footing Inspection - Commercial Passed 06/01/2005
Correction
Resolved
06/01/2005
None FOOTING APPROVED PER PLANS
Erosion Control Inspection Residential Passed 06/06/2005
Correction
Resolved
06/06/2005
None
Underslab Plumbing Inspection - Commercial Not Ready 06/06/2005
Correction
Corrective Action Required
06/06/2005
Not Ready
Correction
Corrective Action Required
06/06/2005
See Comment NOT READY DUE NOT CALL FOR REINSPECTION UNTIL GROUND ROUGH IS COMPLETED. ENSURE CITY APPROVED PLANS ARE ON SITE.
Underslab Plumbing Inspection - Commercial Passed 06/07/2005
Correction
Resolved
06/07/2005
Not Ready
Correction
Resolved
06/07/2005
See Comment NOT READY DUE NOT CALL FOR REINSPECTION UNTIL GROUND ROUGH IS COMPLETED. ENSURE CITY APPROVED PLANS ARE ON SITE.
Correction
Resolved
06/07/2005
None REPLACE THREE (3) FERNCO-TYPE FITTINGS PRIOR TO COVERING NOTE: SEWER LINE TO MAIN MOVED FROM WEST SIDE TO SOUTH SIDE
Water Service Inspection Passed 06/07/2005
Correction
Resolved
06/07/2005
None
All Rough Inspection - Commercial Not Ready 08/17/2005
Correction
Corrective Action Required
08/17/2005
See Comment NO INTERIOR FRAMING, ELECTRICAL, MECHANICAL OR PLUMBING STARTED. NO PLANS FOR EXTERIOR WALLS OR TRUSS PACKAGE ON SITE.
All Rough Inspection - Commercial Not Ready 09/01/2005
Correction
Corrective Action Required
09/01/2005
See Comment NO INTERIOR FRAMING, ELECTRICAL, MECHANICAL OR PLUMBING STARTED. NO PLANS FOR EXTERIOR WALLS OR TRUSS PACKAGE ON SITE.
Correction
Corrective Action Required
09/01/2005
Approved Plans THIS IS THE 2nd REQUESTED INSPECTION WITHOT THE APPROVED PLANS ON SITE. PLANS THAT WERE PROVIDED ARE FOR A DIFFERENT BUILDING. $30.00 REINSPECTION ADDED
All Rough Inspection - Commercial Partial 09/06/2005
Correction
Resolved
09/06/2005
See Comment NO INTERIOR FRAMING, ELECTRICAL, MECHANICAL OR PLUMBING STARTED. NO PLANS FOR EXTERIOR WALLS OR TRUSS PACKAGE ON SITE.
Correction
Resolved
09/06/2005
Approved Plans THIS IS THE 2nd REQUESTED INSPECTION WITHOT THE APPROVED PLANS ON SITE. PLANS THAT WERE PROVIDED ARE FOR A DIFFERENT BUILDING. $30.00 REINSPECTION ADDED
Correction
Partial Correction
09/06/2005
See Comment ROOF & EXTERIOR WALLS AS PER PLANS INTERIOR WALLS WALLS AND TRADES INCOMPLETE
Rough Framing Inspection - Commercial Request Complete 9/1/2005 9/6/2005 09/06/2005
Electrical Service Inspection Passed 09/26/2005
Correction
Resolved
09/26/2005
None 600 AMP, 600 VOLT SERVICE. RELEASE METER
All Rough Inspection - Commercial Failed 09/26/2005
Correction
Corrective Action Required
09/26/2005
Service Ground APPROVED PLANS CALL GROUNDING TO BUILDING STEEL. ONLY BUILDING STEEL IS THE CONCRETE EMBEDDED MOUNTS FOR WOOD BEAMS. DOES THE ENGINEER WANT PANELS GROUNDED TO THESE?
All Rough Inspection - Commercial Failed 02/07/2006
Correction
Corrective Action Required
02/07/2006
Service Ground APPROVED PLANS CALL GROUNDING TO BUILDING STEEL. ONLY BUILDING STEEL IS THE CONCRETE EMBEDDED MOUNTS FOR WOOD BEAMS. DOES THE ENGINEER WANT PANELS GROUNDED TO THESE?
Correction
Resolved
02/07/2006
Approved Plans NOT ON SITE
Gas Piping Inspection - Commercial Passed 02/07/2006
Correction
Resolved
02/07/2006
None
Gas Service Inspection - Commercial Failed 02/07/2006
Correction
Corrective Action Required
02/07/2006
Gas Test Pressure (IRC) MUST HAVE A MINIMUM OF 10 PSI FOR TEST. HELD 8 PSI.
Gas Service Inspection - Commercial Not Ready 02/10/2006
Correction
Corrective Action Required
02/10/2006
Gas Test Pressure (IRC) 1st REQUESTED INSPECTION. MUST HAVE A MINIMUM OF 10 PSI FOR TEST. HELD 8 PSI. HELD <5 PSI. THIS IS THE 2nd REQUESTED INSPECTION THAT THERE IS INSUFFICIENT PRESSURE. MUST HAV A MINIMUM OF 10 PSI.
Gas Service Inspection - Commercial Not Ready 02/16/2006
Correction
Corrective Action Required
02/16/2006
Gas Test Pressure (IRC) 1st REQUESTED INSPECTION. MUST HAVE A MINIMUM OF 10 PSI FOR TEST HELD <5 PSI. 2nd REQUESTED INSPECTION THAT THERE IS INSUFFICIENT PRESSURE. 3rd REQUESTED INSPECTION - UNABLE TO REMOVE CAP TO INSPECT GUAGE
Gas Service Inspection - Commercial Passed 03/02/2006
Correction
Resolved
03/02/2006
Gas Test Pressure (IRC) HELD 10 PSI. RELEASE METER
All Rough Inspection - Commercial Failed 11/07/2006
Correction
Corrective Action Required
11/07/2006
See Comment CEILINGS IN ALL AREAS HAVE BEEN INSTALLED. NO CEILINGS ON PLANS. SUBMIT ENGINEERED PLANS TO PLANS EXMINER
Correction
Resolved
11/07/2006
None OKAY TO INSULATE, OKAY TO ROCK
Above Ceiling Inspection Failed 02/20/2007
Correction
Corrective Action Required
02/20/2007
COMMENTS PARTIAL INSPECTION ONLY. UNABLE TO INSPECT ENTIRETY OF ATTIC.
Correction
Corrective Action Required
02/20/2007
PROVIDE TRUSS DRAWINGS AND SPECS ALSO, HAS TRUSS MANUFACTURER APPROVED ATTACHMENT OF STEEL CEILING COVER?
Correction
Corrective Action Required
02/20/2007
REQUIRED INFORMATION PROVIDE ADDITIONAL INFORMATION FROM ARCHITECT: - ARE FIRE WALLS REQUIRED TO EXTEND TO BOTTOM OF ROOF DECK? - IS PLYWOOD APPROVED MATERIAL IN PLENUM?
Correction
Corrective Action Required
02/20/2007
ATTIC ACCESS - ATTIC ACCESSES TO BE MINIMUM 20"x30" - PROVIDE PATH TO SERVICEABLE EQUIPMENT & SERVICE PLATFORM AT EQUIPMENT - PROVIDE SWITCHED LIGHTING NEAR EQUIPMENT - PROVIDE DISCONNECT SWITCHES AT UNIT HEATERS
Correction
Corrective Action Required
02/20/2007
PLENUM MATERIALS REMOVE PAPER FROM INSULATION. THROUGHOUT
Correction
Corrective Action Required
02/20/2007
DUCTWORK SUPPORT ALL FLEXIBLE DUCTWORK TO BE SUPPORTED MAX. 5' SPACING WITH MIN. 1-1/2" STRAPS THROUGHOUT
Correction
Corrective Action Required
02/20/2007
TROFFER SUPPORT PROVIDE (2) SUPPORTS AT EACH 2'X4' LIGHT FIXTURE TO STRUCTURE THROUGHOUT
Correction
Corrective Action Required
02/20/2007
PVC SUPPORT ALL PVC PIPING TO BE SUPPORTED AT 4' MAX. SPACING ATTIC
Correction
Corrective Action Required
02/20/2007
None DO NOT COVER
Sewer Service Inspection Failed 02/27/2007
Correction
Corrective Action Required
02/27/2007
See Comment NO RECORD OF INSPECTION
Above Ceiling Inspection Failed 02/27/2007
Correction
Resolved
02/27/2007
COMMENTS PARTIAL INSPECTION ONLY. UNABLE TO INSPECT ENTIRETY OF ATTIC.
Correction
Resolved
02/27/2007
ATTIC ACCESS - ATTIC ACCESSES TO BE MINIMUM 20"x30" - PROVIDE PATH TO SERVICEABLE EQUIPMENT & SERVICE PLATFORM AT EQUIPMENT - PROVIDE SWITCHED LIGHTING NEAR EQUIPMENT - PROVIDE DISCONNECT SWITCHES AT UNIT HEATERS
Correction
Resolved
02/27/2007
PLENUM MATERIALS REMOVE PAPER FROM INSULATION. Throughout
Correction
Resolved
02/27/2007
DUCTWORK SUPPORT ALL FLEXIBLE DUCTWORK TO BE SUPPORTED MAX. 5' SPACING WITH MIN. 1-1/2" STRAPS Throughout
Correction
Corrective Action Required
02/27/2007
TROFFER SUPPORT PROVIDE (2) SUPPORTS AT EACH 2'X4' LIGHT FIXTURE TO STRUCTURE Throughout
Correction
Resolved
02/27/2007
PVC SUPPORT ALL PVC PIPING TO BE SUPPORTED AT 4' MAX. SPACING Attic
Correction
Resolved
02/27/2007
None
All Rough Inspection - Commercial Failed 02/27/2007
Correction
Resolved
02/27/2007
See Comment ROOF & EXTERIOR WALLS AS PER PLANS INTERIOR WALLS WALLS AND TRADES INCOMPLETE
Correction
Resolved
02/27/2007
Service Ground APPROVED PLANS CALL GROUNDING TO BUILDING STEEL. ONLY BUILDING STEEL IS THE CONCRETE EMBEDDED MOUNTS FOR WOOD BEAMS.
Correction
Corrective Action Required
02/27/2007
See Comment CEILINGS IN ALL AREAS HAVE BEEN INSTALLED. NO CEILINGS ON PLANS. SUBMIT ENGINEERED PLANS TO PLANS EXMINER
Correction
Resolved
02/27/2007
None OKAY TO INSULATE, OKAY TO ROCK
Occupancy Inspection - Codes Commercial Failed 02/27/2007
Correction
Corrective Action Required
02/27/2007
Receive Planning & Development Approval RECEIVED UNDER SEPARATE COVER
Correction
Resolved
02/27/2007
Receive Public Works Approval RECEIVE UNDER SEPARATE COVER
Correction
Resolved
02/27/2007
Receive Water Utilities Approval RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
02/27/2007
Receive Fire Department approval RECEIVED UNDER SEPARATE COVER
Occupancy Inspection - Codes Commercial Failed 02/28/2007
Correction
Corrective Action Required
02/28/2007
Receive Planning & Development Approval RECEIVED UNDER SEPARATE COVER 02-28-07 RECEIVED APPROVAL FOR TCO
Sewer Service Inspection Passed 04/12/2007
Correction
Resolved
04/12/2007
See Comment see e-mail from Shawn Graff to Gary Welty dated 20 Mar 07
Occupancy Inspection - Codes Commercial Failed 08/07/2007
Correction
Resolved
08/07/2007
Receive Planning & Development Approval RECEIVED UNDER SEPARATE COVER 02-28-07 RECEIVED APPROVAL FOR TCO 08-06-07 e-mail from Tom Scannell
Occupancy Inspection - Codes Commercial Passed 08/08/2007
Correction
Resolved
08/08/2007
Receive Fire Department approval RECEIVED UNDER SEPARATE COVER see e-mail from Joe Dur dated 7 Aug 07
Above Ceiling Inspection Passed 08/09/2007
Correction
Resolved
08/09/2007
PROVIDE TRUSS DRAWINGS AND SPECS ALSO, HAS TRUSS MANUFACTURER APPROVED ATTACHMENT OF STEEL CEILING COVER?
Correction
Resolved
08/09/2007
REQUIRED INFORMATION PROVIDE ADDITIONAL INFORMATION FROM ARCHITECT: - ARE FIRE WALLS REQUIRED TO EXTEND TO BOTTOM OF ROOF DECK? - IS PLYWOOD APPROVED MATERIAL IN PLENUM?
Correction
Resolved
08/09/2007
TROFFER SUPPORT PROVIDE (2) SUPPORTS AT EACH 2'X4' LIGHT FIXTURE TO STRUCTURE Throughout
All Rough Inspection - Commercial Passed 08/09/2007
Correction
Resolved
08/09/2007
See Comment CEILINGS IN ALL AREAS HAVE BEEN INSTALLED. NO CEILINGS ON PLANS. SUBMIT ENGINEERED PLANS TO PLANS EXMINER
Documents & Images
Date Uploaded File Type Document Name
07/31/2017 Legacy Park Maintenance Building Inspection
07/31/2017 Legacy Park Maintenance Building Re-Inspection
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home