Building Permit - Commercial
Certificate of Occupancy
DOUGLAS STATION SHOPPING CENTER LLC
NEW TENANT FINISH
TENANT FINISH
10/30/2003
12/01/2003
05/29/2004
02/18/2004
Locations
Contacts
DINGMAM INVESTMENTS, Address:1160 NE DOUGLAS RD  
DOUGLAS STATION SHOPPING CENTER LLC, Address:1725 NE RICE RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/27/2004 10/29/2010
Correction

CA - The correct occupancy type for a restaurant is A-2. Sheet A2.1 incorrectly states that this is a B occupancy.
Correction

CA - Occupant load calculations were not shown on the plans. Calculate the occupant load per IBC Table 1003.2.2.2.
Correction

CA - 2000 IMC 506.3.13.3 Termination Location - Exhaust outlets shall be located not less than 10 feet horizontally from parts of the same or contiguous buildings, adjacent property lines and air intake openings into any building and shall be located not less than 10 feet above the adjoining grade level. Exception 2: The minimum horizontal distance between vertical discharge fans and parapet-type building structures shall be 2 feet provided that such structures are not higher than the top of the fan discharge opening.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - For the Health Department inspection contact Bob Thomas with the Jackson County Public Works Department at 816-881-4530. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1003.2.2.5 - Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

CA - 2000 IBC 1108.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, the accessible counters shall also be dispersed.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $161.00 $161.00 Paid 12/01/2003
24 BLDG Plan Check Fees $15.30 $15.30 Paid 12/01/2003
25 Electrical Permit Fee $55.00 $55.00 Paid 12/01/2003
25 Mechanical Permit Fees $57.00 $57.00 Paid 12/01/2003
25 Plumbing Permit Fees $49.00 $49.00 Paid 12/01/2003
89 Sewer Tap Fees $510.00 $510.00 Paid 12/01/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/12/2003
Correction
Resolved
12/12/2003
UNDER-SLAB DWV & WATER PIPING OK TO COVER WHEN READY EXCAVATED; LAID; JOINED DWV SLOPED TO DRAIN
All Rough Inspection - Commercial Failed 12/31/2003
Correction
Corrective Action Required
12/31/2003
PROTECTION OF PIPING IPC 305.8; IRC P2603: INSTALL SHIELD PLATES AT STUDS & PLATES DWV PIPING < 1-1/2" FROM FACE OF STUD / PLATE
All Rough Inspection - Commercial Passed 01/02/2004
Correction
Resolved
01/02/2004
PROTECTION OF PIPING DWV PIPING < 1-1/2" FROM FACE OF STUD / PLATE
Correction
Resolved
01/02/2004
None OKAY TO INSULATE, OKAY TO ROCK
Electrical Service Inspection Passed 01/27/2004
Correction
Resolved
01/27/2004
ELECTRICAL SERVICE INSTALLATION 200 AMP 3 PHASE RELEASE SERVICE
Above Ceiling Inspection Passed 02/05/2004
Correction
Resolved
02/05/2004
None
Gas Service Inspection - Commercial Passed 02/10/2004
Correction
Resolved
02/10/2004
TEST PRESSURE LEVEL RELEASE GAS SERVICE HELD STEADY AT >= 10 PSI FOR 10 MIN
Gas Piping Inspection - Commercial Failed 02/10/2004
Correction
Corrective Action Required
02/10/2004
PADS UNDER ROOFTOP PIPING BLOCKS NOT INSTALLED PER DRWGS
Correction
Corrective Action Required
02/10/2004
PIPING TO ROOFTOP MAKEUP AIR UNIT NOT INSTALLED
Occupancy Inspection - Codes Commercial Failed 02/13/2004
Correction
Resolved
02/13/2004
Receive Water Utilities Approval PER J WALTERS 2/13/04
Correction
Corrective Action Required
02/13/2004
Receive Fire Department approval SEE FD INSP SUMMARY
Correction
Corrective Action Required
02/13/2004
BACKFLOW DEVICE ABOVE ELECTRICAL RECEPT RELIEF PORT NOT PIPED TO PREVENT DOUSING RECEPT
Correction
Corrective Action Required
02/13/2004
CSST GAS TUBING @ WATER HEATER OF NON-RIGID MATERIAL EXPOSED TO DAMAGE INAPPROPRIATE APPLICATION
Correction
Corrective Action Required
02/13/2004
DIRT LEG ON GAS FEEDER TO WATER HEATER CAP NOT REMOVABLE
Correction
Resolved
02/13/2004
ELECTRICAL RECEPTACLES NEC 380-10; 410-56(f) NOT TIGHT TO BOX CORRECTED ON SPOT
Correction
Corrective Action Required
02/13/2004
OCCUPANCY STATUS DO NOT OCCUPY OR OPERATE UNTIL APPROVED
Correction
Corrective Action Required
02/13/2004
ROOFTOP WORK AREA DEBRIS NOT REMOVED
Correction
Corrective Action Required
02/13/2004
ROOFTOP GAS PIPING NOT STRAPPED @ SUPPORTS
Occupancy Inspection - Codes Commercial Failed 02/17/2004
Correction
Resolved
02/17/2004
Receive Water Utilities Approval
Correction
Resolved
02/17/2004
BACKFLOW DEVICE ABOVE ELECTRICAL RECEPT
Correction
Resolved
02/17/2004
CSST GAS TUBING @ WATER HEATER
Correction
Resolved
02/17/2004
DIRT LEG ON GAS FEEDER TO WATER HEATER
Correction
Resolved
02/17/2004
ELECTRICAL RECEPTACLES
Correction
Corrective Action Required
02/17/2004
OCCUPANCY STATUS DO NOT OCCUPY OR OPERATE UNTIL APPROVED
Correction
Resolved
02/17/2004
ROOFTOP WORK AREA
Correction
Resolved
02/17/2004
ROOFTOP GAS PIPING
Occupancy Inspection - Codes Commercial Passed 02/17/2004
Correction
Resolved
02/17/2004
Receive Fire Department approval
Correction
Resolved
02/17/2004
OCCUPANCY STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home