Summary
B0302029
Building Permit - Commercial
Certificate of Occupancy
ALLEGHENY PROPERTIES LLC
CHANGE OF TENANT
TENANT FINISH
10/14/2003
10/29/2003
04/26/2004
12/04/2003
Locations
Contacts
MALLORY ACCOUNTING CORPORATION, Address:305 SW MARKET ST STE 5  
ALLEGHENY PROPERTIES LLC, Address:7401 E 67TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/11/2004 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - If the restrooms shown are to be used by the other tenants of the buildings, the must have access to the restrooms any time that the spaces are occupied.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $35.00 $35.00 Paid 10/29/2003
24 BLDG Plan Check Fees $4.75 $4.75 Paid 10/29/2003
25 Electrical Permit Fee $32.38 $32.38 Paid 10/29/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Passed 11/11/2003
Correction
Resolved
11/11/2003
None FRAMING AND ELECT. WALLS ONLY APPROVED OK TO ROCK
Occupancy Inspection - Codes Commercial Failed 11/26/2003
Correction
Resolved
11/26/2003
CIRCUIT BREAKERS FOR CERTAIN CIRCUITS PER FIRE DEPARTMENT DIRECTION NOT IN THIS SERVICE PANEL PROVIDE PERMANENT SIGN
Correction
Corrective Action Required
11/26/2003
ELECTRICAL JUNCTION BOXES NOT CLOSED
Correction
Corrective Action Required
11/26/2003
UNUSED KNOCKOUTS AT ELECTRICAL JUNCTION BOXES NOT PLUGGED
Correction
Corrective Action Required
11/26/2003
ELECTRICAL EQUIPMENT ABOVE CEILING NOT OK NOT SECURED TO STRUCTURE BOXES ATTACHED TO GRID
Correction
Corrective Action Required
11/26/2003
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES AT OPPOSITE DIAGONAL CORNERS. TIE WITH TWO FULLWRAPS. NOT INSTALLED TWO TIES PER FIXTURE
Correction
Corrective Action Required
11/26/2003
INSTALLATION OF MC CABLE NEC 300-11 & 334-10 NOT SECURELY FASTENED WITHIN 12" OF BOXES
Correction
Corrective Action Required
11/26/2003
ELECTRICAL RECEPTACLES/SWITCHES NEC 380-10; 410-56(f) NOT TIGHT TO BOX CHECK ALL
Correction
Corrective Action Required
11/26/2003
ELECTRICAL RECEPTACLES NOT GFCI PROTECTED RESTROOMS
Correction
Corrective Action Required
11/26/2003
Receive Fire Department approval
Correction
Corrective Action Required
11/26/2003
Receive Water Utilities Approval
Correction
Partial Correction
11/26/2003
OCCUPANCY STATUS SEE TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Passed 12/03/2003
Correction
Resolved
12/03/2003
ELECTRICAL JUNCTION BOXES
Correction
Resolved
12/03/2003
UNUSED KNOCKOUTS AT ELECTRICAL JUNCTION BOXES
Correction
Resolved
12/03/2003
ELECTRICAL EQUIPMENT ABOVE CEILING
Correction
Resolved
12/03/2003
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES
Correction
Resolved
12/03/2003
INSTALLATION OF MC CABLE
Correction
Resolved
12/03/2003
ELECTRICAL RECEPTACLES/SWITCHES
Correction
Resolved
12/03/2003
ELECTRICAL RECEPTACLES
Correction
Resolved
12/03/2003
Receive Fire Department approval JB CHECKED DEVICES + CIRCUIT LABELING
Correction
Resolved
12/03/2003
Receive Water Utilities Approval NO ISSUES CITED
Correction
Resolved
12/03/2003
OCCUPANCY STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home