Permit Application Status

B0301533


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0301533
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
NEW HANGAR
08/01/2003
05/06/2004
11/02/2004
09/22/2004
Locations
Contacts
MEYER BROTHERS BUILDING COMPANY, Address:200 NE MISSOURI RD  
DAVIDSON DESIGN GROUP, Address:11301STRANG LINE ROAD  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/28/2004 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - The north arrow on Sheet C1.1 is incorrect.
Correction

CA - 2000 IBC 412.2.1 - Exterior walls. Exterior walls located less than 30 feet from property lines, lot lines or a public way shall have a fire resistance rating not less than 2 hours.
Correction

CA - 2000 IBC 412.2.3 - Floor surface. Floors shall be graded and drained to prevent water of fuel from remaining on the floor. Floor drains shall discharge through an oil separator to the sewer or to an outside vented sump.
Correction

CA - 2000 IBC 412.2.4 - Heating Equipment. Heating equipment shall be placed in another room separated by 2-hour fire-resistant-rated construction. Entrance shall be from the outside or by means of a vestible providing a two doorway separation. Exception 1. Unit heaters suspended at least 10 feet above the upper surface of wings or engine enclosures of the highest aircraft that may be housed in the hanger and at least 8 feet above the floor in shops, offices and other sections of the hanger communicating with storage or service areas.
Correction

CA - The plumbing plans indicate that the water heater will be located on the restroom ceiling but no details are provided for the framing of the ceiling.
Correction

CA - The Jackson County Health Department acts as the health officer for the City of Lee's Summit and reviews and approves all private disposal systems.
Correction

CA - The size of the water meter is not indicated on sheet C1.1.
Correction

CA - Plan note 5 on Sheet M1 and the plans indicate that the floor drains are to be ran to daylight. This is not allowed by the International Building Code as indicated in previous comments.
Correction

CA - The layout of the space on the electrical plans does not match the rest of the plan set. The passage doors, restroom location and unit heaters are all in different locations.
Correction

Fire Department; No aircraft repair, welding, painting, bonding shall be allowed unless hanger is equipped with approved fire protection systems.
Correction

Fire Department; future expansion shall required the hanger to be equipped with fire protection systems.
Correction

Fire Department; No Smoking signs shall be posted in accordance with IFC 1103.2 & 310.3
Correction

Fire Department; The hanger shall follow nationally recognized standards for fire protection NFPA 409.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - 2000 IBC 1704.1.2 - Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and the registered design professional in responsible charge prior to the completion of that phase of the work. A final report of inspections documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted periodically at a frequency agreed upon by the permit applicant and the building official prior to the start of work.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IMC 920.1 - General. Unit heaters shall be installed in accordance with the listing and the manufacturer's installation instructions. Oil-fired unit heaters shall be tested in accordance with UL 731.
Correction

CA - 2000 IPC 504.3 - A means of disconnecting an electric hot water supply system from its energy supply shall be provided in accordance with the 1999 National Electric Code. A seperate valve shall be provided to shut off the energy fuel supply to all other types of hot water supply systems.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,076.00 $1,076.00 Paid 05/06/2004
24 BLDG Plan Check Fees $37.90 $37.90 Paid 05/06/2004
25 Electrical Permit Fee $50.00 $50.00 Paid 05/06/2004
25 Mechanical Permit Fees $63.50 $63.50 Paid 05/06/2004
25 Plumbing Permit Fees $30.00 $30.00 Paid 05/06/2004
84 Water Meters $125.00 $125.00 Paid 05/06/2004
85 Water Taps $2,734.00 $2,734.00 Paid 05/06/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 05/21/2004
Correction
Resolved
05/21/2004
PERIMETER GRADE BEAM + INTEGRAL COLUMN FOOTINGS OK TO POUR WHEN READY RE-BAR COVERAGE >= 3" TO BOTTOMS/BANKS
Underslab Plumbing Inspection - Commercial Partial 06/02/2004
Correction
Partial Correction
06/02/2004
UNDER-SLAB FLOOR DRAIN SYSTEM OK TO COVER WHEN READY NO PIPING @ RESTROOM YET
Footing Inspection - Commercial Passed 06/02/2004
Correction
Resolved
06/02/2004
COLUMN FOOTING PREPARATION E WALL CENTER TWO F70 FOOTINGS + WIDENED GRADE BEAM @
Underslab Plumbing Inspection - Commercial Passed 06/08/2004
Correction
Resolved
06/08/2004
UNDER-SLAB FLOOR DRAIN SYSTEM
Correction
Resolved
06/08/2004
UNDER-SLAB DWV PIPING @ RESTROOM
Water Service Inspection Partial 06/08/2004
Correction
Partial Correction
06/08/2004
INITIAL PARTIAL WATER SERVICE INSTALL FROM BUILDING ENTRY TO NEAR METER LOCATION
Water Service Inspection - Commercial Request Complete 6/8/2004 6/8/2004 06/08/2004
Water Service Inspection Passed 06/09/2004
Correction
Resolved
06/09/2004
INITIAL PARTIAL WATER SERVICE INSTALL
Correction
Resolved
06/09/2004
FINAL PARTIAL WATER SERVICE INSTALL OK TO COVER WHEN READY METER/WELL INSTALLED TAP COMPLETED
Water Service Inspection - Commercial Request Complete 6/9/2004 6/9/2004 06/09/2004
Electrical Service Inspection Passed 07/30/2004
Correction
Resolved
07/30/2004
ELECTRICAL SERVICE INSTALLATION 200 AMP RELEASE SERVICE
All Rough Inspection - Commercial Passed 08/03/2004
Correction
Resolved
08/03/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH PER IPC 305.8; THEN OK TO COVER WHEN READY RESTROOM WALLS SHIELD PLATE PVC PIPE
Gas Piping Inspection - Commercial Passed 08/12/2004
Correction
Resolved
08/12/2004
GAS PIPING ROUGH HELD STEADY AT >= 10 PSI FOR 10 MIN. NOTE: GAS SERVICE RELEASE NOT REQUESTED NOR PROVIDED. GAS PIPING NOT FOUND ON PERMIT DRAWINGS. VISUAL OK TEST PRESSURE LEVEL
Occupancy Inspection - Codes Commercial Failed 09/09/2004
Correction
Corrective Action Required
09/09/2004
Receive Fire Department approval
Correction
Corrective Action Required
09/09/2004
Receive Planning & Development Approval
Correction
Corrective Action Required
09/09/2004
Receive Public Works Approval
Correction
Corrective Action Required
09/09/2004
Receive Water Utilities Approval
Correction
Corrective Action Required
09/09/2004
SIDING BASE DRIP EDGE REPLACE WHERE DAMAGED EXAMPLE: S WALL
Correction
Corrective Action Required
09/09/2004
WATER METER WELL CLEAN OUT DOWN TO AGGREGATE BASE DISPLACED/DAMAGED LID NOT IN PLACE
Correction
Corrective Action Required
09/09/2004
STATUS OF GAS SERVICE NEVER APPROVED/RELEASED
Correction
Corrective Action Required
09/09/2004
WATER CLOSET SEAT IPC 420.3 NOT COMMERCIAL TYPE WITH OPEN FRONT
Correction
Corrective Action Required
09/09/2004
HANDICAPPED ACCESSIBLE RESTROOM SIGNS NOT IN PLACE RESTROOM DOORS
Correction
Corrective Action Required
09/09/2004
PENETRATIONS/HOLES IN EXTERIOR WALL IRC R703.1: SEAL ANNULAR SPACE NOT SEALED EX: CONDUIT @ WEST WALL
Occupancy Inspection - Codes Commercial Failed 09/10/2004
Correction
Resolved
09/10/2004
Receive Planning & Development Approval PER HECTOR SOTO 9/9/04
Occupancy Inspection - Codes Commercial Passed 09/21/2004
Correction
Resolved
09/21/2004
Receive Fire Department approval
Correction
Resolved
09/21/2004
Receive Public Works Approval NO ISSUES PRESENTED
Correction
Resolved
09/21/2004
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
09/21/2004
SIDING BASE DRIP EDGE
Correction
Resolved
09/21/2004
WATER METER WELL
Correction
Resolved
09/21/2004
STATUS OF GAS SERVICE INTENDED TO BE PROPANE-FUELED
Correction
Resolved
09/21/2004
WATER CLOSET SEAT
Correction
Resolved
09/21/2004
HANDICAPPED ACCESSIBLE RESTROOM SIGNS
Correction
Resolved
09/21/2004
PENETRATIONS/HOLES IN EXTERIOR WALL
Documents & Images

No documents are currently available for viewing.

Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home