Permit Application Status

B0301130


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0301130
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW COMMERCIAL
BLDG C DIAGNOSTIC CENTER
06/17/2003
11/10/2003
05/08/2004
04/12/2005
Locations
Contacts
ACI BOLAND, Address:11229 NALL SUITE 140  
SHAFER, KLINE & WARREN, Address:2940 MAIN ST.  
JE DUNN CONSTRUCTION CO, Address:929 HOLMES RD  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/14/2003 10/29/2010
Correction

Fire Department- Provide remote annunciator panels in the water supply room with the sprinkler riser.
Correction

Codes Administration - 2000 IBC 407.4 - Smoke barriers. Smoke barriers shall be provided to subdivide every story used by patients for sleeping or treatment and to devide other stories with an occupant load of 50 or more persons, into at least two smoke compartments. Such stories shall be divided into smoke compartments with an area of not more than 22,500 square feet and the travel distance from any point in a smoke compartment to a smoke barrier shall not exceed 200 feet. The smoke barrier shall be in accordance with Section 709.
Correction

Codes Administration - 2000 IBC 407.4.1 - Refuge area. At least 30 net square feet per patient shall be provided within the aggregate area of corridors, patient rooms, treatment rooms, lounge or dining areas and other low-hazard areas on each side of each smoke barrier. On floors no housing patients confined to a bed or litter, at least 6 net square feet per occupant shall be provided on each side of each smoke barrier for the total number of occupants in adjoining smoke compartments.
Correction

Codes Administration - I do not have a revised Sheet A.02 with reflects the addition to Building C.
Correction

St. Lukes - The City shall not issue any temporary or final Certificate of Occupancy for any structure in the Developerment until a Certificate of Substantial Completion for the Road Improvements has been issued by MoDOT.
Correction

St. Lukes - A Proprtionate Share of the Total Road Contribution shall be made to the City at or before the time a certificate of occupancy is issued by the City for a building constructed by, or by a building contractor on behalf of, the Developer on the Property, excluding the medical office buildings.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

All proposed hose bibb connections must have an approved (vacuum breaker) backflow preventer.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $16,475.00 $16,475.00 Paid 11/10/2003
25 Electrical Permit Fee $873.93 $873.93 Paid 11/10/2003
25 Mechanical Permit Fees $418.50 $418.50 Paid 11/10/2003
25 Plumbing Permit Fees $252.00 $252.00 Paid 11/10/2003
84 Water Meters $1,410.25 $1,410.25 Paid 11/10/2003
85 Water Taps $20,505.00 $20,505.00 Paid 11/10/2003
89 Sewer Tap Fees $1,290.00 $1,290.00 Paid 11/10/2003
24 BLDG Permit Fees ($16,475.00) ($16,475.00) $0.00 N/A
25 Electrical Permit Fee ($873.93) ($873.93) $0.00 N/A
25 Mechanical Permit Fees ($418.50) ($418.50) $0.00 N/A
25 Plumbing Permit Fees ($252.00) ($252.00) $0.00 N/A
84 Water Meters ($1,410.25) ($1,410.25) $0.00 N/A
85 Water Taps ($20,505.00) ($20,505.00) $0.00 N/A
89 Sewer Tap Fees ($1,290.00) ($1,290.00) $0.00 N/A
24 BLDG Permit Fees $18,902.00 $18,902.00 Paid 11/10/2003
25 Electrical Permit Fee $873.93 $873.93 Paid 11/10/2003
25 Mechanical Permit Fees $418.50 $418.50 Paid 11/10/2003
25 Plumbing Permit Fees $252.00 $252.00 Paid 11/10/2003
84 Water Meters $1,410.25 $1,410.25 Paid 11/10/2003
85 Water Taps $20,505.00 $20,505.00 Paid 11/10/2003
89 Sewer Tap Fees $1,290.00 $1,290.00 Paid 11/10/2003
24 BLDG Permit Fees $642.00 $642.00 Paid 07/07/2004
Road and Bridge Escrow $7,921.30 $7,921.30 Paid 02/01/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Service Inspection Failed 02/11/2004
Correction
Corrective Action Required
02/11/2004
DOMESTIC WATER SERVICE LOCATION OF METER IN PIT NOT PER DRAWING S.2.2; INSPECTOR WIILL CONSULT WITH WATER DEPT. PRESSURE TEST HOLDING STEADY @ 100 PSI. CAUTION FOR FUTURE INSTALLATIONS: 100% VISUAL INSPECTION REQUIRED ON ALL SERVICES. TAP; METER COMPLETE SVC LINE TO BLDG ENTRY
Water Service Inspection Partial 02/17/2004
Correction
Resolved
02/17/2004
FIRE LINE: SHUT-OFF TO BLDG ENTRY VISUAL OK PRESSURE TEST OK
Correction
Partial Correction
02/17/2004
DOMESTIC WATER SERVICE LOCATION OF METER IN PIT NOT PER DRAWING S.2.2 TAP; METER COMPLETE SVC LINE TO BLDG ENTRY
Rough Framing Inspection - Commercial Partial 02/20/2004
Correction
Partial Correction
02/20/2004
CIP CONCRETE COLUMNS - FIRST LEVEL E.2/5.2; OK TO POUR WHEN READY ENSURE CLEARANCE @ FORMS
Rough Framing Inspection - Commercial Partial 03/22/2004
Correction
Partial Correction
03/22/2004
CIP CONCRETE COLUMNS - FIRST LEVEL E.2/5.2; F/5; F/6; F/8; F/8.7; E.6/7.05; OK TO POUR WHEN READY ENSURE CLEARANCE @ FORMS
Rough Framing Inspection - Commercial Partial 03/23/2004
Correction
Partial Correction
03/23/2004
CIP CONCRETE COLUMNS - FIRST LEVEL E.2/5.2; F/5; F/6; F/8; F/8.7; E.6/7.05; A/5.5; A.5/5; B/6; E/6; E/8; E.6/7.05; OK TO POUR WHEN READY ENSURE CLEARANCE @ FORMS
Rough Framing Inspection - Commercial Partial 03/24/2004
Correction
Partial Correction
03/24/2004
CIP CONCRETE COLUMNS - FIRST LEVEL E.2/5.2; F/5; F/6; F/8; F/8.7; E.6/7.05; A/5.5; A.5/5; B/6; E/6; E/8; E.6/7.05; A.5/5; A.8/3; A.8/4; CC/55; DD/55; OK TO POUR WHEN READY ENSURE CLEARANCE @ FORMS
Rough Framing Inspection - Commercial Partial 03/25/2004
Correction
Partial Correction
03/25/2004
CIP CONCRETE COLUMNS - FIRST LEVEL E.2/5.2; F/5; F/6; F/8; F/8.7; E.6/7.05; A/5.5; A.5/5; B/6; E/6; E/8; E.6/7.05; A.5/5; A.8/3; A.8/4; CC/55; DD/55; F.5/8.4; OK TO POUR WHEN READY ENSURE CLEARANCE @ FORMS
Rough Framing Inspection - Commercial Partial 03/29/2004
Correction
Partial Correction
03/29/2004
CIP CONCRETE COLUMNS - FIRST LEVEL E.2/5.2; F/5; F/6; F/8; F/8.7; E.6/7.05; A/5.5; A.5/5; B/6; E/6; E/8; E.6/7.05; A.5/5; A.8/3; A.8/4; CC/55; DD/55; F.5/8.4; AA/44; BB/44; CC/33; DD/33; EE/44; FF/44; GG/44; HH/44; JJ/44; AA/44; BB/44; CC/33; DD/33; EE/44; FF/44; GG/44; HH/44; JJ/44 OK TO POUR WHEN READY ENSURE CLEARANCE @ FORMS
Rough Framing Inspection - Commercial Partial 04/05/2004
Correction
Partial Correction
04/05/2004
CIP CONCRETE COLUMNS - FIRST LEVEL A.5/5; B/6; E/6; E/8; E.6/7.05; A.5/5; A.8/3; A.8/4; CC/55; DD/55; F.5/8.4; AA/44; BB/44; CC/33; DD/33; EE/44; FF/44; GG/44; HH/44; JJ/44; AA/44; BB/44; CC/33; DD/33; EE/44; FF/44; GG/44; HH/44; JJ/44; G/5; G/6; G/7; F.6/4; D.5/1; F/2; G/3; G/2; E.2/5.2; F/5; F/6; F/8; F/8.7; E.6/7.05; A/5.5;
Rough Framing Inspection - Commercial Partial 04/06/2004
Correction
Resolved
04/06/2004
CIP CONCRETE COLUMNS - FIRST LEVEL A.5/5; B/6; E/6; E/8; E.6/7.05; A.5/5; A.8/3; A.8/4; CC/55; DD/55; F.5/8.4; AA/44; BB/44; CC/33; DD/33; EE/44; FF/44; GG/44; HH/44; JJ/44; AA/44; BB/44; CC/33; DD/33; EE/44; FF/44; GG/44; HH/44; JJ/44; G/5; G/6; G/7; F.6/4; D.5/1; F/2; G/3; G/2; E.2/5.2; F/5; F/6; F/8; F/8.7; E.6/7.05; A/5.5;
Correction
Partial Correction
04/06/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/07/2004
Correction
Partial Correction
04/07/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/08/2004
Correction
Partial Correction
04/08/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; [G.2/9 OK IF/WHEN APP`D BY SEA]; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/09/2004
Correction
Partial Correction
04/09/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; [G.2/9 OK IF/WHEN APP`D BY SEA]; G/1; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/12/2004
Correction
Partial Correction
04/12/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9 SAID NOW TO BE APP`D BY SEA; G/1; H/5; H/6; H/7; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/15/2004
Correction
Partial Correction
04/15/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9; G/1; H/5; H/6; H/7; F/1; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/19/2004
Correction
Partial Correction
04/19/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9; G/1; H/5; H/6; H/7; F/1; H/1; H/2; H/3; {I/2; I/3 NOT ON PERMIT DRAWINGS} ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/21/2004
Correction
Partial Correction
04/21/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9; G/1; H/5; H/6; H/7; F/1; H/1; H/2; H/3; I/2; I/3; J/1; K/2; K/3; K/4; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/22/2004
Correction
Partial Correction
04/22/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9; G/1; H/5; H/6; H/7; F/1; H/1; H/2; H/3; I/2; I/3; J/1; K/2; K/3; K/4; K/5; K/6; K/7; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/23/2004
Correction
Partial Correction
04/23/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9; G/1; H/5; H/6; H/7; F/1; H/1; H/2; H/3; I/2; I/3; J/1; K/2; K/3; K/4; K/5; K/6; K/7; B/1; D.5/2; F/3; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/26/2004
Correction
Partial Correction
04/26/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9; G/1; H/5; H/6; H/7; F/1; H/1; H/2; H/3; I/2; I/3; J/1; K/2; K/3; K/4; K/5; K/6; K/7; B/1; D.5/2; F/3; H/4; J.8/1; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 04/27/2004
Correction
Partial Correction
04/27/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9; G/1; H/5; H/6; H/7; F/1; H/1; H/2; H/3; I/2; I/3; J/1; K/2; K/3; K/4; K/5; K/6; K/7; B/1; D.5/2; F/3; H/4; J.8/1; J/2; J/3; J/4; J/5; J/6; J/7; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Suspended Slab Inspection Partial 04/28/2004
Correction
Partial Correction
04/28/2004
2ND FLOOR PAN SLAB DECK N RADIUS S TO (G.4) x (44) W TO (4.5); CONTIGENT ON SEA APPROVAL OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 05/04/2004
Correction
Resolved
05/04/2004
CIP CONC COLUMNS - 1ST LEVEL CONT'D F/4; F.8/9; G.3/8.2; G.3/10; A.4/1.5; A.7/2; D/3; G/3; G.3/9; A.4/1.5; C.6/5.1; G.2/9; G/1; H/5; H/6; H/7; F/1; H/1; H/2; H/3; I/2; I/3; J/1; K/2; K/3; K/4; K/5; K/6; K/7; B/1; D.5/2; F/3; H/4; J.8/1; J/2; J/3; J/4; J/5; J/6; J/7;
Correction
Partial Correction
05/04/2004
C.I.P. CONC COLUMNS - 2ND LEVEL E.6/7.05; E.6/8.2; F/1; G/7; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 05/05/2004
Correction
Partial Correction
05/05/2004
C.I.P. CONC COLUMNS - 2ND LEVEL E.6/7.05; E.6/8.2; F/1; G/7; F/8.6; F.5/8.4; F.8/9; G.2/9; G.3/8.2; ENSURE RE-BAR COVERAGE OK TO POUR WHEN READY
Suspended Slab Inspection Partial 05/07/2004
Correction
Partial Correction
05/07/2004
2ND FLOOR PAN SLAB DECK N RADIUS S TO (G.4) x (44) W TO (4.5); N OF (G.4) TO EXT x W OF (4.5) TO EXT; CONTIGENT ON SEA APPROVAL OK TO POUR WHEN READY
Suspended Slab Inspection Partial 05/20/2004
Correction
Partial Correction
05/20/2004
2ND FLOOR PAN SLAB DECK N RADIUS S TO (G.4) x (44) W TO (4.5); N OF (G.4) TO EXT x W OF (4.5) TO EXT; REMAINDER OF SLAB AREA [ALL S OF (G.4)] CONTIGENT ON SEA APPROVAL OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 05/21/2004
Correction
Partial Correction
05/21/2004
C.I.P. CONC STUB COLUMNS - 2ND LEVEL E/6; F/6; G/6; D/5; F/5; G/5; D/4; F/4; F.6/4; G/3; WORKMANSHIP OK BUT NOT FOUND ON PERMIT DRWGS
Suspended Slab Inspection Partial 05/21/2004
Correction
Partial Correction
05/21/2004
2ND FLOOR PAN SLAB DECK N RADIUS S TO (G.4) x (44) W TO (4.5); N OF (G.4) TO EXT x W OF (4.5) TO EXT; REMAINDER OF SLAB AREA [ALL S OF (G.4)] CONTIGENT ON SEA APPROVAL
Rough Framing Inspection - Commercial Partial 05/24/2004
Correction
Partial Correction
05/24/2004
C.I.P. CONC COLUMNS - 2ND LEVEL E.6/7.05; E.6/8.2; F/1; G/7; F/8.6; F.5/8.4; F.8/9; G.2/9; G.3/8.2; H/7;
Correction
Partial Correction
05/24/2004
C.I.P. CONC STUB COLUMNS - 2ND LEVEL E/6; F/6; G/6; D/5; F/5; G/5; D/4; F/4; F.6/4; G/3; PER SHT S5.0 DETS (6)&(7) OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 05/25/2004
Correction
Partial Correction
05/25/2004
C.I.P. CONC STUB COLUMNS - 2ND LEVEL E/6; F/6; G/6; D/5; F/5; G/5; D/4; F/4; F.6/4; G/3; E.2/5.2; G/1; H/1; H/3; H/4; H/5; H/6; J/1; J/3; J/4; J/5; J/6; J.8/1; K/1; K/2; K/3; K/4; K/5; K/6; K/7; PER SHT S5.0 DETS (6)&(7) OK TO POUR WHEN READY
Rough Framing Inspection - Commercial Partial 05/26/2004
Correction
Partial Correction
05/26/2004
C.I.P. CONC STUB COLUMNS - 2ND LEVEL G/5; D/4; F/4; F.6/4; G/3; E.2/5.2; G/1; H/1; H/3; H/4; H/5; H/6; J/1; J/3; J/4; J/5; J/6; J.8/1; K/1; K/2; K/3; K/4; K/5; K/6; K/7; B/1; D.5/1; C.6/5.1; A.4/1.5; A.7/2; D.5/2; F/2; G/2; H/2; ?/2; A.9/3; D/3; F/3; A.8/4; A.5/5; A/5.5; B/6; E/8; ?/?; OK TO POUR WHEN READY E/6; F/6; G/6; D/5; F/5;
Rough Framing Inspection - Commercial Partial 05/28/2004
Correction
Resolved
05/28/2004
C.I.P. CONC STUB COLUMNS - 2ND LEVEL G/5; D/4; F/4; F.6/4; G/3; E.2/5.2; G/1; H/1; H/3; H/4; H/5; H/6; J/1; J/3; J/4; J/5; J/6; J.8/1; K/1; K/2; K/3; K/4; K/5; K/6; K/7; B/1; D.5/1; C.6/5.1; A.4/1.5; A.7/2; D.5/2; F/2; G/2; H/2; J/2; A.9/3; D/3; F/3; A.8/4; A.5/5; A/5.5; B/6; E/8; J/7; OK TO POUR WHEN READY E/6; F/6; G/6; D/5; F/5;
Rough Plumbing Inspection - Commercial Partial 06/04/2004
Correction
Partial Correction
06/04/2004
DWV PIPING - FIRST LEVEL SUBJECT TO APPROVAL WHEN COMPLETED & PRESSURE-TESTED WORK PROGRESS TO DATE NO ISSUES NOTED
Correction
Partial Correction
06/04/2004
ROOF DRAIN PIPING - FIRST LEVEL SUBJECT TO APPROVAL WHEN COMPLETED & PRESSURE-TESTED WORK PROGRESS TO DATE NO ISSUES NOTED
Suspended Slab Inspection Passed 06/10/2004
Correction
Resolved
06/10/2004
PENTHOUSE PAN-SLAB ROOF DECK CONTINGENTON SEA APPROVAL OK TO POUR WHEN READY
Correction
Resolved
06/10/2004
2ND FLOOR PAN SLAB DECK
Rough Plumbing Inspection - Commercial Partial 06/15/2004
Correction
Partial Correction
06/15/2004
DWV PIPING - FIRST LEVEL G/6; A.7/1.9; VISUAL & PRESSURE TEST BRANCHES WITH VTR @
Correction
Partial Correction
06/15/2004
ROOF DRAIN PIPING - FIRST LEVEL C/3.8; F/3; F/5; VISUAL & PRESSURE TEST BRANCHES WITH STACK @
Rough Plumbing Inspection - Commercial Partial 06/16/2004
Correction
Partial Correction
06/16/2004
DWV PIPING - FIRST LEVEL G/6; A.7/1.9; REMAINDER OF W&V WEST OF (7); VISUAL & PRESSURE TEST BRANCHES WITH VTR @
Correction
Partial Correction
06/16/2004
ROOF DRAIN PIPING - FIRST LEVEL DRAIN BRANCHES WITH STACK @ C/3.8; F/3; F/5; VISUAL & PRESSURE TEST OVERFLOWLINE ALONG (F.7);
Rated Assembly Inspection Partial 07/02/2004
Correction
Partial Correction
07/02/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 EXCEPT AROUND DR# C192B + TOP-OUT @ W WALL; RM C194 EXCEPT AROUND DR# C193 + 4` TOP-OUT @ ALL WALLS; ENSURE TOP FIRE-BLOCK OK TO COVER WHEN READY
Rated Assembly Inspection Partial 07/06/2004
Correction
Partial Correction
07/06/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 EXCEPT AROUND DR# C192B; RM C194; ENSURE TOP FIRE-BLOCK OK TO COVER WHEN READY
Rated Assembly Inspection Partial 07/07/2004
Correction
Partial Correction
07/07/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 EXCEPT AROUND DR# C192B; RM C194; RM C191 W & S WALLS; CORR E OF RM C191 E WALL TOP 9`; ENSURE TOP FIRE-BLOCK OK TO COVER WHEN READY
Rated Assembly Inspection Partial 07/15/2004
Correction
Partial Correction
07/15/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 EXCEPT AROUND DR# C192B; RM C194; RM C191 W & S WALLS; CORR E OF RM C191 E WALL TOP 9`; FRAMING + 1ST LAYER GWB OF HORIZONTAL CHASE @ TOP OF WEST WALL RM C194; OK TO COVER WHEN READY
Correction
Partial Correction
07/15/2004
FIREPROOFING OF CLERESTORY COLUMNS ONE LAYER
Rated Assembly Inspection Partial 07/16/2004
Correction
Partial Correction
07/16/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 EXCEPT AROUND DR# C192B; RM C194; RM C191 W & S WALLS; CORR E OF RM C191 E WALL TOP 9`; 2ND LAYER GWB OF HORIZONTAL CHASE @ TOP OF WEST WALL RM C194; FRAMING OF HORIZONTAL CHASE @ TOP OF WEST WALL RM C192; OK TO COVER WHEN READY
Rated Assembly Inspection Partial 07/19/2004
Correction
Partial Correction
07/19/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 INCLUDING AROUND DR# C192B; RM C194 N WALL @DOOR; RM C191 W & S WALLS; CORR E OF RM C191 E WALL TOP 9`; 2ND LAYER GWB OF HORIZONTAL CHASE @ TOP OF WEST WALL RM C194; 1ST LAYER GWB ON HORIZONTAL CHASE @ TOP OF WEST WALL RM C192; OK TO COVER WHEN READY
Correction
Partial Correction
07/19/2004
WALLS @ TUNNEL ENTRY C189 LINER BOARD @ PLAN S & W WALLS; OK TO COVER WHEN READY
Correction
Partial Correction
07/19/2004
FIREPROOFING OF CLERESTORY COLUMNS 2ND LAYER GWB
Rated Assembly Inspection Partial 07/20/2004
Correction
Partial Correction
07/20/2004
WALLS @ TUNNEL ENTRY C189 LINER BOARD @ INSIDE FACE PLAN S & W WALLS; TYPE X GWB O/S FACE S WALL W 10`; OK TO COVER WHEN READY
Correction
Resolved
07/20/2004
FIREPROOFING OF CLERESTORY COLUMNS 2ND LAYER GWB 3RD LAYER GWB
Electrical Service Inspection Passed 07/22/2004
Correction
Resolved
07/22/2004
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE
Rough Plumbing Inspection - Commercial Passed 08/09/2004
Correction
Resolved
08/09/2004
DWV PIPING - FIRST LEVEL G/6; A.7/1.9; REMAINDER OF W&V WEST OF (7); NE CORNER TO COMPLETE 1ST LEVEL VISUAL & PRESSURE TEST BRANCHES WITH VTR @
Correction
Resolved
08/09/2004
ROOF DRAIN PIPING - FIRST LEVEL VISUAL & PRESSURE TEST
All Rough Inspection - Commercial Partial 08/12/2004
Correction
Partial Correction
08/12/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH RM C103 S WALL; OK TO COVER WHEN READY
Rated Assembly Inspection Partial 08/12/2004
Correction
Partial Correction
08/12/2004
WALLS @ CORRIDOR C103 S WALL N FACE (1) TO (3) 1ST LAYER; UL DESIGN U411 OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 08/16/2004
Correction
Partial Correction
08/16/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH RM C103 S WALL; RMS 161; 162; 163; 164; 165; 166; 167; 168; 170; 171; 172; 173; 174; 175; 176; 179; 180; 181; 182; 183; 184; 185; [COPPER PIPING NOT ISOLATED FROM STEEL FRAMING a) C160 S WALL b) RM C159 NE CORNER] OK TO COVER WHEN READY
Rated Assembly Inspection Partial 08/18/2004
Correction
Resolved
08/18/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 INCLUDING AROUND DR# C192B; RM C194 N WALL @DOOR; RM C191 W & S WALLS; CORR E OF RM C191 E WALL TOP 9`; 2ND LAYER GWB OF HORIZONTAL CHASE @ TOP OF WEST WALL RM C194; 1ST LAYER GWB ON HORIZONTAL CHASE @ TOP OF WEST WALL RM C192; VARIOUS AREAS LISTED BELOW
Correction
Partial Correction
08/18/2004
WALLS @ TUNNEL ENTRY C189 LINER BOARD @ INSIDE FACE PLAN S & W WALLS; TYPE X GWB O/S FACE S WALL W 10`; LINER BOARD @ INSIDE FACE PLAN N/E WALL; OK TO COVER WHEN READY
Correction
Partial Correction
08/18/2004
WALLS @ CORRIDOR C103 S WALL N FACE (1) TO (5) 1ST LAYER; S WALL N FACE (1) TO (3.2) 2ND LAYER; UL DESIGN U411 OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 08/19/2004
Correction
Partial Correction
08/19/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH RM C103 S WALL; RMS 161; 162; 163; 164; 165; 166; 167; 168; 170; 171; 172; 173; 174; 175; 176; 179; 180; 181; 182; 183; 184; 185; 160; 159; OK TO COVER WHEN READY
Rated Assembly Inspection Partial 08/19/2004
Correction
Partial Correction
08/19/2004
WALLS @ CORRIDOR C103 S WALL N FACE (1) TO (5.5) 1ST LAYER; S WALL N FACE (1) TO (3.2) 2ND LAYER; UL DESIGN U411 OK TO COVER WHEN READY
Rated Assembly Inspection Partial 08/20/2004
Correction
Partial Correction
08/20/2004
WALLS @ CORRIDOR C103 S WALL N FACE (1) TO (5.5) 1ST LAYER; S WALL N FACE (1) TO (3.2) 2ND LAYER; S WALL S FACE (1) TO (3) 2ND LAYER; S WALL S FACE (3) TO (5.5) 1ST LAYER; UL DESIGN U411 OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 08/20/2004
Correction
Partial Correction
08/20/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH RM C103 S WALL; RMS 161; 162; 163; 164; 165; 166; 167; 168; 170; 171; 172; 173; 174; 175; 176; 179; 180; 181; 182; 183; 184; 185; 160; 159; 104; 105; 106; 183; 183A; 184; 185; 186; 187; OK TO COVER WHEN READY
Rated Assembly Inspection Partial 08/25/2004
Correction
Partial Correction
08/25/2004
WALLS @ CORRIDOR C103 S WALL N FACE (1) TO (5.5) 1ST LAYER; S WALL N FACE (1) TO (3.2) 2ND LAYER; S WALL S FACE (1) TO (3) 2ND LAYER; S WALL S FACE (3) TO (5.5) 1ST LAYER; S WALL (3) TO (5.5) S & N FACE 2ND LAYER; S WALL N FACE (1) TO (4) TOP 6' FIRE CAULK & TAPE; UL DESIGN U411 OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 08/25/2004
Correction
Partial Correction
08/25/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH RM C103 S WALL; RMS 161; 162; 163; 164; 165; 166; 167; 168; 170; 171; 172; 173; 174; 175; 176; 179; 180; 181; 182; 183; 184; 185; 160; 159; 104; 105; 106; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 08/27/2004
Correction
Partial Correction
08/27/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 160; 159; 104; 105; 106; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 107; 108; 109; 110; 111; 112; 113; 130; 131; 132; 133; 134; 135; 136; 137; 138; OK TO COVER WHEN READY RMS 103 ; 161; 162; 163;.
All Rough Inspection - Commercial Partial 09/09/2004
Correction
Partial Correction
09/09/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 160; 159; 104; 105; 106; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 107; 108; 109; 110; 111; 112; 113; 130; 131; 132; 133; 134; 135; 136; 137; 138; 169; 177; OK TO COVER WHEN READY RMS 103 ; 161; 162; 163;.
Rated Assembly Inspection Partial 09/14/2004
Correction
Partial Correction
09/14/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 INCLUDING AROUND DR# C192B; RM C194 N WALL @DOOR; RM C191 W & S WALLS; CORR E OF RM C191 E WALL TOP 9`; 2ND LAYER GWB OF HORIZONTAL CHASE @ TOP OF WEST WALL RM C194; 1ST LAYER GWB ON HORIZONTAL CHASE @ TOP OF WEST WALL RM C192; 192 E WALL E FACE VARIOUS AREAS LISTED BELOW
Correction
Partial Correction
09/14/2004
WALLS @ TUNNEL ENTRY C189 LINER BOARD @ INSIDE FACE PLAN S & W WALLS; TYPE X GWB O/S FACE S WALL W 10`; LINER BOARD @ INSIDE FACE PLAN N/E WALL; N&S WALLS O/S FACE 1ST LAYER COMPLETE; INSIDE FACE @ E END 1ST LAYER + 2ND LAYER TOP 9'; OK TO COVER WHEN READY
Correction
Partial Correction
09/14/2004
WALLS @ CORRIDOR C103 S WALL N FACE (1) TO (5.5) 1ST LAYER; S WALL N FACE (1) TO (3.2) 2ND LAYER; S WALL S FACE (1) TO (3) 2ND LAYER; S WALL S FACE (3) TO (5.5) 1ST LAYER; S WALL (3) TO (5.5) S & N FACE 2ND LAYER; S WALL N FACE (1) TO (4) TOP 6' FIRE CAULK & TAPE; UL DESIGN U411
All Rough Inspection - Commercial Partial 09/17/2004
Correction
Partial Correction
09/17/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 160; 159; 104; 105; 106; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 107; 108; 109; 110; 111; 112; 113; 130; 131; 132; 133; 134; 135; 136; 137; 138; 169; 177; 141; 144; 147; 148; 149; 150; 151; OK TO COVER WHEN READY RMS 103 ; 161; 162; 163;.
Rated Assembly Inspection Partial 09/21/2004
Correction
Partial Correction
09/21/2004
GWB INSTALLATION @ FIRE-RATED WALLS RM C192 INSIDE & OUTSIDE FACES; RM C194 INSIDE & OUTSIDE FACES; RM C191 W & S WALLS; CORR E OF RM C191 E WALL TOP 9`; VARIOUS AREAS LISTED BELOW
Correction
Resolved
09/21/2004
WALLS @ TUNNEL ENTRY C189 OK TO COVER WHEN READY INSIDE & OUTSIDE FACES
All Rough Inspection - Commercial Partial 09/21/2004
Correction
Partial Correction
09/21/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 159 - 163; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 130 - 138; 169; 177; 141; 144; 147; 148; 149; 150; 151; 178; OK TO COVER WHEN READY RMS 103 - 113;...
Rated Assembly Inspection Partial 09/22/2004
Correction
Resolved
09/22/2004
WALLS @ ELECT RM C152 OK TO COVER WHEN READY 1 LAYER 5/8" TYPE X GWB FOUR WALLS BOTH FACES
Rated Assembly Inspection Partial 09/28/2004
Correction
Partial Correction
09/28/2004
U465 WALL ALONG (H) SOUTH FACE; FROM (1.5) TO (8) OK TO COVER WHEN READY
Correction
Partial Correction
09/28/2004
WEST WALL OF CORRIDOR C114 OK TO COVER WHEN RE4ADY 1ST LAYER
All Rough Inspection - Commercial Partial 09/28/2004
Correction
Partial Correction
09/28/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 159 - 163; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 130 - 138; 169; 177; 141; 144; 147; 148; 149; 150; 151; 178; 114 S WALL; OK TO COVER WHEN READY RMS 103 - 113;...
All Rough Inspection - Commercial Partial 09/29/2004
Correction
Partial Correction
09/29/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 159 - 163; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 130 - 138; 169; 177; 141; 144; 147; 148; 149; 150; 151; 178; 114 S WALL; 153; 154; OK TO COVER WHEN READY RMS 103 - 113;...
All Rough Inspection - Commercial Partial 10/04/2004
Correction
Partial Correction
10/04/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 159 - 163; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 130 - 138; 169; 177; 141; 144; 147; 148; 149; 150; 151; 178; 114 S WALL; 153; 154; 115 - 123; 195; OK TO COVER WHEN READY RMS 103 - 113;...
Rated Assembly Inspection Partial 10/04/2004
Correction
Resolved
10/04/2004
ROOM 154 MEETS UL465 SPEC SOUTH WALL 1 LAYER 5/8" TYPE X GWB
Rated Assembly Inspection Partial 10/05/2004
Correction
Partial Correction
10/05/2004
CORRIDOR 114 - SOUTH WALL UL411 1ST LAYER BOTH FACES; PATCH HOLES IN GWB OK TO COVER WHEN READY
Above Ceiling Inspection Partial 10/11/2004
Correction
Partial Correction
10/11/2004
SOFFIT@ PUBLIC CORRIDOR 103 OK TO COVER WHEN READY PER DETAIL 19/A6.2.3 FRAMING & M/E/P SYSTEMS
Rated Assembly Inspection Partial 10/11/2004
Correction
Partial Correction
10/11/2004
CORRIDOR 114 - SOUTH WALL UL411 2ND LAYER BOTH FACES OF S WALL; BULKHEADS @ W END: E BULKHEAD 1ST LAYER; EAST LEG (7.5) TO (10) OK TO COVER WHEN READY
Rated Assembly Inspection Partial 10/12/2004
Correction
Partial Correction
10/12/2004
CORRIDOR 114 - SOUTH WALL UL411 2ND LAYER BOTH FACES OF S WALL; BULKHEADS @ W END: E BULKHEAD 1ST LAYER; W BULKHEAD 1ST LAYER; EAST LEG (7.5) TO (10) OK TO COVER WHEN READY
Correction
Partial Correction
10/12/2004
FIRE-STOPPING @ TOPS OF CANOPY COLUMNS 4" MINERAL FIBER SEALED @ TOP W/ >= 1/8" JM FIRETEMP SE OK TO COVER WHEN READY PER A6.1.2 DETAIL 21 ON DRWGS FOR BLDG B
Rated Assembly Inspection Partial 10/13/2004
Correction
Partial Correction
10/13/2004
CORRIDOR 114 - SOUTH WALL UL411 2ND LAYER BOTH FACES OF S WALL; BULKHEADS @ W END: E BULKHEAD 2ND LAYER; W BULKHEAD 2ND LAYER EXCEPT W FACE; EAST LEG (7.5) TO (10) OK TO COVER WHEN READY
Above Ceiling Inspection Partial 10/19/2004
Correction
Resolved
10/19/2004
SOFFIT@ PUBLIC CORRIDOR 103
Correction
Partial Correction
10/19/2004
ENTRANCE CANOPY OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 10/28/2004
Correction
Partial Correction
10/28/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 159 - 163; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 130 - 138; 169; 177; 141; 144; 147; 148; 149; 150; 151; 178; 114 S WALL; 153; 154; 115 - 123; 195; 197; 126; 127; 129 S WALL; OK TO COVER WHEN READY RMS 103 - 113;...
Rated Assembly Inspection Partial 10/29/2004
Correction
Partial Correction
10/29/2004
ROOM C121 1ST LAYER @ S & W WALLS; ONE LAYER N WALL; 5/8" TYPE X GWB OK TO COVER WHEN READY
Correction
Partial Correction
10/29/2004
ROOM C123 1ST LAYER GWB @ S WALL; 5/8" TYPE X GWB OK TO COVER WHEN READY
Correction
Partial Correction
10/29/2004
ROOM C126 ONE LAYER GWB @ S WALL; 5/8" TYPE X GWB OK TO COVER WHEN READY
Correction
Partial Correction
10/29/2004
ROOM C127 ONE LAYER GWB @ S WALL; 5/8" TYPE X GWB OK TO COVER WHEN READY
Correction
Partial Correction
10/29/2004
ROOM C128 ONE LAYER GWB @ S WALL; 5/8" TYPE X GWB OK TO COVER WHEN READY
Correction
Partial Correction
10/29/2004
ROOM C197 1ST LAYER GWB @ E WALL; 5/8" TYPE X GWB OK TO COVER WHEN READY
Correction
Partial Correction
10/29/2004
ROOM C120 ONE LAYER GWB @ S WALL; 5/8" TYPE X GWB OK TO COVER WHEN READY
Rated Assembly Inspection Partial 11/02/2004
Correction
Partial Correction
11/02/2004
ROOM C197 E WALL 1ST LAYER GWB; E WALL 2ND LAYER; S WALL ONE LAYER; 5/8" TYPE X GWB OK TO COVER WHEN READY
Rated Assembly Inspection Partial 11/04/2004
Correction
Partial Correction
11/04/2004
ROOM C121 1ST LAYER @ S & W WALLS; ONE LAYER N WALL; 2ND LAYER S WALL; 2ND? LAYER E? WALL; 5/8" TYPE X GWB OK TO COVER WHEN READY
Correction
Partial Correction
11/04/2004
ROOM C123 S WALL 1ST LAYER GWB; S WALL 2ND LAYER GWB; 5/8" TYPE X GWB OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 11/10/2004
Correction
Partial Correction
11/10/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164 - 168; 170 - 176; 179 - 185; 159 - 163; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 130 - 138; 169; 177; 141; 144; 147; 148; 149; 150; 151; 178; 114 S WALL; 153; 154; 115 - 123; 195; 197; 126; 127; 129 S WALL; MRI RM 154; OK TO COVER WHEN READY RMS 103 - 113;...
Above Ceiling Inspection Partial 11/11/2004
Correction
Resolved
11/11/2004
ENTRANCE CANOPY
Correction
Partial Correction
11/11/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164; 169; 170; 171; 174; 177; 178; 181; REMOVE TEMP ELECT CABLE OK TO COVER WHEN READY
Above Ceiling Inspection Partial 11/16/2004
Correction
Partial Correction
11/16/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164; 169; 170; 171; 174; 177; 178; 181; 159; 163; 165; 166; 167; 168; 182; 183; 183A; 184; 186; 187; REMOVE TEMP ELECT CABLE OK TO COVER WHEN READY
Above Ceiling Inspection Partial 11/18/2004
Correction
Partial Correction
11/18/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164; 169; 170; 171; 174; 177; 178; 181; 159; 163; 165; 166; 167; 168; 182; 183; 183A; 184; 186; 187; 141; 142; 143; 144; 145; 146; 147; OK TO COVER WHEN READY 164; 169; 170; 171; 174;
Above Ceiling Inspection Partial 11/19/2004
Correction
Partial Correction
11/19/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164; 169; 170; 171; 174; 177; 178; 181; 159; 163; 165; 166; 167; 168; 182; 183; 183A; 184; 186; 187; 141; 142; 143; 144; 145; 146; 147; 148; 149; 156 DO NOT COVER ELECT WORK IN PROGRESS: 150; 158 TWO LOCATIONS OK TO COVER WHEN READY 164; 169; 170; 171; 174;
Above Ceiling Inspection Partial 11/23/2004
Correction
Partial Correction
11/23/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164; 169; 170; 171; 174; 177; 178; 181; 159; 163; 165; 166; 167; 168; 182; 183; 183A; 184; 186; 187; 141; 142; 143; 144; 145; 146; 147; 148; 149; 156; 150; 158; 161; 162; 172; 173; 175; 176; 179; 180; OK TO COVER WHEN READY 164; 169; 170; 171; 174;
All Rough Inspection - Commercial Partial 12/02/2004
Correction
Partial Correction
12/02/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164-168; 170-176; 179-185; 159-163; 183; 183A; 184; 185; 186; 187; 142; 143; 145; 146; 149; 150; 153; 130-138; 169; 177; 141; 144; 147; 148; 149; 150; 151; 178; 114 S WALL; 153; 154; 115-123; 195; 197; 126; 127; 129 S WALL; MRI 154 INCL W WALL; OK TO COVER WHEN READY RMS 103 - 113;...
Above Ceiling Inspection Partial 12/06/2004
Correction
Partial Correction
12/06/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164; 169; 170; 171; 174; 177; 178; 181; 159; 163; 165; 166; 167; 168; 182; 183; 183A; 184; 186; 187; 141; 142; 143; 144; 145; 146; 147; 148; 149; 156; 150; 158; 161; 162; 172; 173; 175; 176; 179; 180; 151; 153; OK TO COVER WHEN READY 164; 169; 170; 171; 174;
Above Ceiling Inspection Partial 12/08/2004
Correction
Corrective Action Required
12/08/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164;169; 170; 171; 174; 177; 178; 181; 159; 163; 165; 166; 167; 168; 182; 183; 183A; 184; 186; 187; 141; 142; 143; 144; 145; 146; 147; 148; 149; 156; 150; 158; 161; 162; 172; 173; 175; 176; 179; 180; 151; 153; NOT APPROVED: 108; 109; 110; 111; 112; 113 OK TO COVER WHEN READY 164; 169; 170; 171; 174;
Above Ceiling Inspection Partial 12/09/2004
Correction
Corrective Action Required
12/09/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164;169;170;171;174;177;178;181;159;163;165;166;167;168;182;183;183A; 184;186;187;141;142;143;144;145;146;147;148;149;156;150;158;161;162; 172;173;175;176;179;180;151;153;108;109;110;111;112;113;115-119; 195; NOT APPROVED: 104; 105 OK TO COVER WHEN READY 164;169;170;171;174;
Above Ceiling Inspection Partial 12/13/2004
Correction
Resolved
12/13/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,.. 164;169;170;171;174;177;178;181;159;163;165;166;167;168;182;183;183A; 184;186;187;141;142;143;144;145;146;147;148;149;156;150;158;161;162; 172;173;175;176;179;180;151;153;108;109;110;111;112;113;115-119; 195; 104; 105; 106; CONT'D 164;169;170;171;174;
Correction
Partial Correction
12/13/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 121; 122; 123; 126; 129; 133; 134; 139; NOT APPROVED: 102; 107; 120; 197; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/13/2004
Correction
Partial Correction
12/13/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 121; 122; 123; 126; 129; 133; 134; 139; 102; 107; 120; 127; 197; NOT APPROVED: 103 EAST END - TO BE DISCUSSED OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/14/2004
Correction
Partial Correction
12/14/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 121; 122; 123; 126; 129; 133; 134; 139; 102; 107; 120; 127; 197; 125; 132; 155; 188; NOT APPROVED: 103 EAST END - TO BE DISCUSSED OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 12/16/2004
Correction
Partial Correction
12/16/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH ..164-168; 170-176; 179-185; 159-163; 183; 183A; 184; 185; 186;187; 141-151; 153; 130-138; 169; 177; 178; 114 S WALL; 153; 154; 115-123; 195; 197; 126; 127; 129 S WALL; MRI 154 INCL W WALL; 136; OK TO COVER WHEN READY RMS 103 - 113;...
Above Ceiling Inspection Partial 12/16/2004
Correction
Partial Correction
12/16/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 121; 122; 123; 126; 129; 133; 134; 139; 102; 107; 120; 127; 197; 125; 132; 155; 188; 103; 114; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/22/2004
Correction
Partial Correction
12/22/2004
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 121; 122; 123; 126; 129; 133; 134; 139; 102; 107; 120; 127; 197; 125; 132; 155; 188; 103; 114; 101; 154; 160; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/06/2005
Correction
Partial Correction
01/06/2005
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 101-103; 107; 114; 120-123; 125-127; 129; 132-134; 139; 154; 155; 160; 188; 196; 197; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/10/2005
Correction
Partial Correction
01/10/2005
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 101-103; 107; 114; 120-123; 125-127; 129; 132-134; 135-138; 139; 154; 155; 160; 188; 196; 197; OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/20/2005
Correction
Partial Correction
01/20/2005
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 101-103; 107; 114; 120-123; 125-127; 129; 132-134; 135-138; 139; 154; 155; 160; 188; 196; 197; VEST @ (K)/(5) OK TO COVER WHEN READY
Above Ceiling Inspection Partial 01/28/2005
Correction
Partial Correction
01/28/2005
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,... 101-103; 107; 114; 120-123; 125-127; 129; 132-139; 154; 155; 160; 188; 196; 197; VEST @ (K)/(5); CORR198 INCL N-S LEG @ EAST END OK TO COVER WHEN READY
All Rough Inspection - Commercial Passed 02/03/2005
Correction
Resolved
02/03/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Above Ceiling Inspection Passed 02/03/2005
Correction
Resolved
02/03/2005
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,..
Correction
Resolved
02/03/2005
ABOVE-CEILING SYSTEMS @ ROOMS, CORRIDORS,...
Rated Assembly Inspection Passed 02/03/2005
Correction
Resolved
02/03/2005
GWB INSTALLATION @ FIRE-RATED WALLS
Correction
Resolved
02/03/2005
FIREPROOFING OF CLERESTORY COLUMNS
Correction
Resolved
02/03/2005
WALLS @ TUNNEL ENTRY C189
Correction
Resolved
02/03/2005
WALLS @ CORRIDOR C103
Correction
Resolved
02/03/2005
WALLS @ ELECT RM C152
Correction
Resolved
02/03/2005
U465 WALL ALONG (H)
Correction
Resolved
02/03/2005
WEST WALL OF CORRIDOR C114
Correction
Resolved
02/03/2005
ROOM 154
Correction
Resolved
02/03/2005
CORRIDOR 114 - SOUTH WALL UL411
Correction
Resolved
02/03/2005
FIRE-STOPPING @ TOPS OF CANOPY COLUMNS
Correction
Resolved
02/03/2005
ROOM C121
Correction
Resolved
02/03/2005
ROOM C123
Correction
Resolved
02/03/2005
ROOM C126
Correction
Resolved
02/03/2005
ROOM C127
Correction
Resolved
02/03/2005
ROOM C128
Correction
Resolved
02/03/2005
ROOM C197
Correction
Resolved
02/03/2005
ROOM C120
Water Service Inspection Passed 02/03/2005
Correction
Resolved
02/03/2005
DOMESTIC WATER SERVICE
Correction
Resolved
02/03/2005
FIRE LINE: SHUT-OFF TO BLDG ENTRY
Occupancy Inspection - Codes Commercial Failed 02/03/2005
Correction
Corrective Action Required
02/03/2005
HANDICAPPED ACCESSIBLE RESTROOM SIGN NOT IN PLACE ADA/ANSI
Correction
Corrective Action Required
02/03/2005
Receive Water Utilities Approval
Correction
Corrective Action Required
02/03/2005
Receive Public Works Approval
Correction
Corrective Action Required
02/03/2005
Receive Planning & Development Approval
Correction
Corrective Action Required
02/03/2005
Receive Fire Department approval
Rough Framing Inspection - Commercial Passed 02/03/2005
Correction
Resolved
02/03/2005
CIP CONCRETE COLUMNS - FIRST LEVEL
Correction
Resolved
02/03/2005
CIP CONC COLUMNS - 1ST LEVEL CONT'D
Correction
Resolved
02/03/2005
C.I.P. CONC COLUMNS - 2ND LEVEL
Correction
Resolved
02/03/2005
C.I.P. CONC STUB COLUMNS - 2ND LEVEL
Occupancy Inspection - Codes Commercial Passed 04/08/2005
Correction
Resolved
04/08/2005
HANDICAPPED ACCESSIBLE RESTROOM SIGN
Correction
Resolved
04/08/2005
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
04/08/2005
Receive Public Works Approval NO ISSUES PRESENTED
Correction
Resolved
04/08/2005
Receive Planning & Development Approval PER MIKE GORECKI 4/5/05
Correction
Resolved
04/08/2005
Receive Fire Department approval NO REMAINING ISSUES PER NEIL ULLERY
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.