Summary
B0301033
Building Permit - Commercial
Final Completion
LEES LANDING PROPERTIES LLC
NEW COMMERCIAL
SPEC OFFICE BUILDING
06/04/2003
08/06/2004
02/02/2005
02/15/2006
Locations
Contacts
HIRST & ASSOCIATES, Address:621 NE WOODS CHAPEL RD  
RK MACE ENGINEERING, INC., Address:1012 NE BRYANT CT.  
MEMCO ENTERPRISES, Address:14219 KENNEDY RD  
LEES LANDING PROPERTIES LLC, Address:2270 NW SUMMERFIELD DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/01/2003 10/29/2010
Correction

Fire Department- The driveway to the parking lot shall be posted " Fire Lane No Parking" per IFC D103.6.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - I believe the finish schedule is incorrect. It shows vinyl in the tenant space and carpet in the furnace closet.
Correction

CA - The civil plans shows the building sewer entering the structure in one location while the plumbing plans shows it entering the building in multiple locations.
Correction

CA - Information on the water services is not provided.
Correction

CA - The disconnects at the distribution panels shall be labeled with the corresponding tenant space address.
Correction

CA - A riser diagram is not provided.
Correction

CA - 2000 IBC 1104.2 - Within a site. At least one accessible rout shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IMC 304.8 - Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade or shall be suspended a minimum of 6 inches (152 mm) aboave adjoining grade.
Correction

CA - 2000 IPC 410.1 - Drinking fountains shall conform to ASME A112.19.1, ASME A 112.19.2 or ASME A 112.19.9, and water coolers shall conform to ARI 1010. Where water is served in restaurants or where bottled water coolers or disposable cups next to a sink are provided in other occupancies, drinking fountains shall not be required. (As ammended in the LSCO Section 7-407.)
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,448.00 $1,448.00 Paid 08/06/2004
24 BLDG Plan Check Fees $44.10 $44.10 Paid 08/06/2004
25 Electrical Permit Fee $374.00 $374.00 Paid 08/06/2004
25 Mechanical Permit Fees $190.50 $190.50 Paid 08/06/2004
25 Plumbing Permit Fees $126.50 $126.50 Paid 08/06/2004
89 Sewer Tap Fees $540.00 $540.00 Paid 08/06/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 09/02/2004
Correction
Partial Correction
09/02/2004
PERIMETER GRADE BEAM S END WALL + S 55' OF E & W WALLS; ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Footing Inspection - Commercial Partial 09/03/2004
Correction
Resolved
09/03/2004
PERIMETER GRADE BEAM S END WALL + S 55' OF E & W WALLS; ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Correction
Partial Correction
09/03/2004
MIDDLE TENENTS D-F NORTH/SOUTH GRADE BEAM FRONT/BACK FROM MATCH LINE TO "F" TEN. CONNECTING EAST/WEST GRADE BEAM APPROVED OK TO COVER
Footing Inspection - Commercial Passed 09/08/2004
Correction
Resolved
09/08/2004
PERIMETER GRADE BEAM S END WALL + S 55' OF E & W WALLS; REMAINDER OF E & W WALLS @ N END + N CROSS-WALL GRADE BEAM; N END TO COMPLETE PERIMETER ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Correction
Resolved
09/08/2004
MIDDLE TENENTS D-F
Water Service Inspection Passed 09/15/2004
Correction
Resolved
09/15/2004
WATER SERVICE INSTALLATION OK TO COVER WHEN READY FROM BUILDING ENTRY TO CONNECTION AT STUB
Sewer Service Inspection Passed 09/15/2004
Correction
Resolved
09/15/2004
SEWER SERVICE INSTALLATION OK TO COVER WHEN READY FROM BUILDING ENTRY TO CONNECTION AT STUB
Sewer Service Inspection - Commercial Request Complete 9/15/2004 9/15/2004 09/15/2004
Underslab Plumbing Inspection - Commercial Passed 09/20/2004
Correction
Resolved
09/20/2004
UNDER-SLAB DWV & WATER PIPING OK TO COVER WHEN READY EXCAVATED; LAID; JOINED SLOPED TO DRAIN
Rough Framing Inspection - Commercial Failed 12/13/2004
Correction
Corrective Action Required
12/13/2004
No Access Provided 12/13/04 INSPECTION DENIED COULD NOT GAIN ACCESS TO STRUCTURE
Rough Framing Inspection - Commercial Request Complete 12/10/2004 12/13/2004 12/13/2004
Rough Framing Inspection - Commercial Failed 12/14/2004
Correction
Resolved
12/14/2004
No Access Provided
Correction
Corrective Action Required
12/14/2004
Roof Truss Bracing (IRC) BRACES MISSING PER DISCUSSION
Rough Framing Inspection - Commercial Not Ready 12/15/2004
Correction
Corrective Action Required
12/15/2004
READINESS FOR INSPECTION CALL FOR INSPECTION AFTER PREPARATION IS COMPLETE WORK REQUESTED FOR INSP NOT COMPLETED
Rough Framing Inspection - Commercial Request Complete 12/14/2004 12/15/2004 12/15/2004
Gas Service Inspection - Commercial Partial 12/17/2004
Correction
Partial Correction
12/17/2004
PARTIAL: 1" + 3/4" TO SUITE 101 PRESSURE TEST OK RELEASE SERVICE
Correction
Partial Correction
12/17/2004
PARTIAL: 3/4" TO SECOND SUITE FROM SOUTH NO TENANT YET. REQUEST RELEASE REINSPECTION WHEN SERVICE IS NEEDED SUITE #102? PRESSURE TEST OK
Rough Framing Inspection - Commercial Passed 12/17/2004
Correction
Resolved
12/17/2004
Roof Truss Bracing (IRC)
Correction
Resolved
12/17/2004
READINESS FOR INSPECTION
Gas Piping Inspection - Commercial Partial 12/17/2004
Correction
Partial Correction
12/17/2004
PARTIAL: SUITES 101 (FAR S) + NEXT N (103?) PIPING VISUAL OK
All Rough Inspection - Commercial Failed 12/27/2004
Correction
Corrective Action Required
12/27/2004
Through Penetrations (IRC) FIRE STOP ALL PENETRATIONS THROUGH TOP PLATES
Correction
Corrective Action Required
12/27/2004
TYPE YOUR OWN TEXT COMPLETE INSTALLATION OF JUNCTION BOX SERVING EXTERIOR GFCI NEAR A/C UNITS. EAST WALL
Correction
Resolved
12/27/2004
None OK TO INSULATE AND ROCK.
Correction
Corrective Action Required
12/27/2004
None B0401783 - INFO FROM THIS INSPECTION WAS MOVED FROM THIS PERMIT NUMBER TO THE ONE LISTED BEFORE
Gas Service Inspection - Commercial Not Ready 01/14/2005
Correction
Partial Correction
01/14/2005
PARTIAL: 3/4" TO SECOND SUITE FROM SOUTH NO TENANT YET. REQUEST RELEASE REINSPECTION WHEN SERVICE IS NEEDED SUITE #102? PRESSURE TEST OK
Correction
Corrective Action Required
01/14/2005
INSTALLATION OF GAS-FIRED EQUIPMENT/APPLIANCES SERVICES ARE RELEASED. NOT READY FOR INSPECTION. NONE INSTALLED MUST BE INSTALLED BEFORE
Gas Piping Inspection - Commercial Passed 01/18/2005
Correction
Resolved
01/18/2005
PARTIAL: SUITES 101 (FAR S) + NEXT N (103?) PIPING VISUAL OK
Correction
Resolved
01/18/2005
PIPING TO SUITES 104-109 PRELIMINARY PRESSURE TEST OK ON ALL EXCEPT SUITE# 108 VISUAL OK COVER AT RISK
Gas Service Inspection - Commercial Partial 02/03/2005
Correction
Partial Correction
02/03/2005
PARTIAL: 1" + 3/4" TO SUITE 101 FOR SUITE 101 ONLY PRESSURE TEST OK RELEASE SERVICE
Gas Service Inspection - Commercial Partial 02/09/2005
Correction
Resolved
02/09/2005
PARTIAL: 1" + 3/4" TO SUITE 101
Correction
Resolved
02/09/2005
PARTIAL: 3/4" TO SECOND SUITE FROM SOUTH
Correction
Resolved
02/09/2005
INSTALLATION OF GAS-FIRED EQUIPMENT/APPLIANCES
Correction
Partial Correction
02/09/2005
PARTIAL: SUITES 013; 106; 107 RELEASE 3 GAS SSERVICES. THESE SERVICES APPROVED UNDER BUILDING SHELL PERMIT PRIOR TO APPLICATION/ISSUANCE OF T/F PERMITS FOR THE SPACES. TEST PRESSURE LEVEL HELD STEADY >10 PSI FOR 10 MIN
Electrical Service Inspection Failed 02/22/2005
Correction
Corrective Action Required
02/22/2005
METER/DISCONNECT ADDRESS IDENTIFICATION MUST BE IN PLACE ON COVER PRIOR TO SERVICE RELEASE
Correction
Corrective Action Required
02/22/2005
LABELING OF MAIN SERVICE DISCONNECT SWITCH MUST BE IN PLACE PRIOR TO SERVICE RELEASE
Correction
Corrective Action Required
02/22/2005
GROUNDING ELECTRODE CONDUCTOR TERMINATION NEC 110-14: CHECK / TIGHTEN CLAMP & LUG AT WATER LINE NOT TIGHT
Final Inspection - Commercial Failed 02/24/2005
Correction
Resolved
02/24/2005
Receive Fire Department approval NO ISSUES ON BLDG SHELL
Correction
Corrective Action Required
02/24/2005
Receive Planning & Development Approval
Correction
Resolved
02/24/2005
Receive Public Works Approval PER SHAWN GRAFF 2/24/04
Correction
Resolved
02/24/2005
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Corrective Action Required
02/24/2005
ROOF OVERHANG SOFFIT LIGHTS NOT INSTALLED
Correction
Partial Correction
02/24/2005
ROOF COVERING INSTALLATION IN PROGRESS
Correction
Resolved
02/24/2005
PVC & COPPER PLUMBING PIPING < 1-1/2" FROM FACE OF STUDS/PLATES WILL BE REQUIRED WHEN TENANT FINISH WORK PROCEEDS PER SUITE SPACES STILL VACANT SOME NOT PROTECTED
Correction
Corrective Action Required
02/24/2005
SAFETY PROVISIONS @ FRONT OF BUILDING A/E CONTACT PLAN REVIEW TO DETERMINE REQUIREMENTS
Correction
Corrective Action Required
02/24/2005
CONSTRUCTION ACTIVITY, MATERIAL CLEAR FROM FRONT OF SPACES TO BE OCCUPIED
All Rough Inspection - Commercial Passed 02/24/2005
Correction
Resolved
02/24/2005
Through Penetrations (IRC)
Correction
Resolved
02/24/2005
TYPE YOUR OWN TEXT
Correction
Resolved
02/24/2005
None
Correction
Resolved
02/24/2005
None
Footing Inspection - Commercial Passed 02/24/2005
Correction
Resolved
02/24/2005
PERIMETER GRADE BEAM
Correction
Resolved
02/24/2005
MIDDLE TENENTS D-F
Electrical Service Inspection Passed 02/24/2005
Correction
Resolved
02/24/2005
METER/DISCONNECT ADDRESS IDENTIFICATION SEE TENANT FINISH PERMITS FOR INDIVIDUAL RELEASES
Correction
Resolved
02/24/2005
LABELING OF MAIN SERVICE DISCONNECT SWITCH
Correction
Resolved
02/24/2005
GROUNDING ELECTRODE CONDUCTOR TERMINATION
Correction
Resolved
02/24/2005
SERVICES FOR TEMPORARY HEAT IN SUITES 103, 106, 107 RELEASE ONLY 3 SERVICES
Electrical Service Inspection Partial 03/16/2005
Correction
Partial Correction
03/16/2005
HOUSE METER SERVICE 100 AMPS RELEASE SERVICE
Final Inspection - Commercial Failed 06/06/2005
Correction
Resolved
06/06/2005
ROOF OVERHANG SOFFIT LIGHTS
Correction
Resolved
06/06/2005
ROOF COVERING INSTALLATION
Correction
Resolved
06/06/2005
PVC & COPPER PLUMBING PIPING < 1-1/2" FROM FACE OF STUDS/PLATES WILL BE REQUIRED WHEN TENANT FINISH WORK PROCEEDS PER SUITE SPACES STILL VACANT SOME NOT PROTECTED
Correction
Resolved
06/06/2005
CONSTRUCTION ACTIVITY, MATERIAL
Final Inspection - Commercial Failed 09/26/2005
Final Inspection - Commercial Failed 09/27/2005
Correction
Resolved
09/27/2005
Receive Fire Department approval
Correction
Corrective Action Required
09/27/2005
Receive Planning & Development Approval COORDINATE W/ M GORECKI TO RESOLVE ISSUES
Correction
Resolved
09/27/2005
Receive Public Works Approval
Correction
Resolved
09/27/2005
Receive Water Utilities Approval
Correction
Resolved
09/27/2005
PVC & COPPER PLUMBING PIPING < 1-1/2" FROM FACE OF STUDS/PLATES
Correction
Resolved
09/27/2005
SAFETY PROVISIONS @ FRONT OF BUILDING
Electrical Service Inspection Passed 11/18/2005
Correction
Resolved
11/18/2005
METER/DISCONNECT ADDRESS IDENTIFICATION
Correction
Resolved
11/18/2005
LABELING OF MAIN SERVICE DISCONNECT SWITCH
Correction
Resolved
11/18/2005
GROUNDING ELECTRODE CONDUCTOR TERMINATION
Correction
Resolved
11/18/2005
SERVICES FOR TEMPORARY HEAT IN SUITES 103, 106, 107
Correction
Resolved
11/18/2005
HOUSE METER SERVICE
Final Inspection - Commercial Failed 11/18/2005
Gas Service Inspection - Commercial Passed 11/18/2005
Correction
Resolved
11/18/2005
PARTIAL: 1" + 3/4" TO SUITE 101
Correction
Resolved
11/18/2005
PARTIAL: 3/4" TO SECOND SUITE FROM SOUTH
Correction
Resolved
11/18/2005
INSTALLATION OF GAS-FIRED EQUIPMENT/APPLIANCES
Correction
Resolved
11/18/2005
PARTIAL: SUITES 013; 106; 107
Final Inspection - Commercial Passed 02/14/2006
Correction
Resolved
02/14/2006
Receive Planning & Development Approval RESOLVE ANY REMAINING ISSUES WITH BLDG "D"
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home