Summary
B0300941
Building Permit - Commercial
Final Completion
PHAM MAI & TRAN JOSEPH
ALTERATION COMMERCIAL
NEW HOOD AND MAKE UP AIR
05/28/2003
05/28/2003
11/24/2003
06/25/2003
Locations
Contacts
JOSEPH TRAN, Address:510 SW 3RD ST  
PHAM MAI & TRAN JOSEPH, Address:510 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/24/2003 10/29/2010
Correction

CA - IMC 506.3.3 - Joints, seams and penetrations of grease ducts. Joints, seams and penetrations of grease ducts shall be made with a continuous liquid-tight weld or braze made on the external surface of the duct system.
Correction

CA - IMC 506.3.7 - Clearances. Grease duct systems serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm). Exception: Listed and labeled factory-built commercial kitchen grease ducts installed in accordance with Section 304.1.
Correction

CA - IMC 506.3.4 - Grease duct supports. Grease duct bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of the International Building Code. Bolts, screws, rivets and other mechanical fasteners shall not penetrate duct walls.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IMC 507.17 - A performance test shall be conducted upon completion and before final approval of the installation of a ventilation system serving commercial food heat-processing appliances. The test shall verify the rate of airflow and proper operation as specified in this chapter. The permit holder shall furnish the necessary test equipment and devices required to perform the test.
Correction

CA - 2000 IMC 501.3 - Outdoor discharge. The air removed by every mechanical exhaust system will be discharged outdoors at a point where it will not cause a nuisance and from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic or crawl space.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $11.00 $11.00 Paid 05/28/2003
24 BLDG Plan Check Fees $2.75 $2.75 Paid 05/28/2003
25 Electrical Permit Fee $15.00 $15.00 Paid 05/28/2003
25 Mechanical Permit Fees $32.50 $32.50 Paid 05/28/2003
25 Plumbing Permit Fees $25.00 $25.00 Paid 05/28/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Hood/Duct Inspection Failed 06/09/2003
Correction
Corrective Action Required
06/09/2003
DUCT CLEARANCE OBTAIN 18 INCH CLEARANCE TO COMBUSTIBLES OR PROVIDE PROTECTION WHERE DUCTS ARE WITHIN 18 INCHES OF EXHAUST DUCTS. BOTH EXHAUST DUCTS
Correction
Corrective Action Required
06/09/2003
SEAL OPENING IN CEILING SEAL ROUND HOLE IN CEILING AT SMALL HOOD ABOVE SMALL HOOD
Occupancy Inspection - Codes Commercial Failed 06/09/2003
Correction
Corrective Action Required
06/09/2003
CIRCUIT LABELS LABEL CIRCUIT 27 IN LARGE PANEL AND ALL CIRCUITS IN SMALLER PANEL. SEE ALSO HOOD & DUCT INSPECTION FOR OTHER ITEMS.
Correction
Corrective Action Required
06/09/2003
Receive Fire Department approval RECEIVE FIRE DEPT. APPROVAL. (UNDER SEPARATE COVER).
Final Mechanical Inspection Passed 06/24/2003
Hood/Duct Inspection Passed 06/24/2003
Correction
Resolved
06/24/2003
DUCT CLEARANCE
Correction
Resolved
06/24/2003
SEAL OPENING IN CEILING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home