Summary
B0300908
Building Permit - Commercial
Certificate of Occupancy
JADAN DEVELOPMENT COMPANY LLC
CHANGE OF TENANT
LUMBERMANS UNDERWRITING ALLIANCE TENANT FINISH
05/22/2003
06/11/2003
12/08/2003
08/04/2003
Locations
Contacts
DRUMMOND AND SONS, Address:1215 N MCCOY  
JADAN DEVELOPMENT COMPANY LLC, Address:430 NE DICKINSON LN  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/18/2003 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.4.1 - Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.4.1.
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - 2000 IBC 1004.3.1.1 - Public areas Group B and M. In public areas of Group B and M occupancies, the minimum clear aisle width shall be 36 inches where seats, tables, furnishings, displays and similar fixtures or equipment are placed on only one side of the aisle and 44 inches where such fixtures or equipment are placed on both sides of the aisle.
Correction

CA - The materials to be used for the HVAC installation are not indicated on the plans.
Correction

CA - Exhaust fans are not shown in the restrooms.
Correction

CA - The water piping and hot water source are not shown on the plans.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

CA - 2000 IBC 1209.1 - In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

CA - 2000 IBC 1108.4 - Where kitchen, kitchenettes and wet bars are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC/ANSI A117.1.
Correction

CA - 2000 IBC 711.3 - Fire-resistance-rated walls. Penetrations into or through fire walls, fire barriers, smoke barrier walls, and fire partitions shall comply with this section.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

CA - 2000 IMC 403.3 - Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and the occupant load or other perameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less then the number determined from the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 240-24(b) - Occupancy. Each occupant shall have ready access to all overcurrent devices protecting the conductors suplying that occupancy. Where electric service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the service overcurrent devices and feeder overcurrent devices supplying more than one occupancy shall be permitted to be accessible to only authorized management personnel in the following: (1) In multiple occupancy buildings (2) For guest rooms of hotels and motels that are intended for transient occupancy.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IPC 308.5 - Pipe shall be supported in accordance with Table 308.5.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $122.00 $122.00 Paid 06/11/2003
24 BLDG Plan Check Fees $12.00 $12.00 Paid 06/11/2003
25 Electrical Permit Fee $20.00 $20.00 Paid 06/11/2003
25 Mechanical Permit Fees $24.00 $24.00 Paid 06/11/2003
25 Plumbing Permit Fees $27.00 $27.00 Paid 06/11/2003
89 Sewer Tap Fees $150.00 $150.00 Paid 06/11/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 06/17/2003
Correction
Resolved
06/17/2003
UNDER-FLOOR DWV & WATER PIPING PER PERMIT DRWGS. OK TO COVER WHEN READY EXCAVATED; LAID; JOINED SLOPED TO DRAIN
All Rough Inspection - Commercial Partial 06/24/2003
Correction
Partial Correction
06/24/2003
IN-WALL SYSTEMS ROUGH - PARTIAL OTHER IN-WALL TRADES YET TO BE APPROVED H&C WATER + DWV PIPING APPROVED
All Rough Inspection - Commercial Partial 06/26/2003
Correction
Partial Correction
06/26/2003
IN-WALL SYSTEMS ROUGH COPPER WATER PIPE IS NOT PROTECTED FROM SHARP EDGES OF STUDS OK TO COVER EXCEPT PLUMBING WALL WHERE
Correction
Resolved
06/26/2003
IN-WALL SYSTEMS ROUGH - PARTIAL H&C WATER + DWV PIPING
All Rough Inspection - Commercial Passed 06/27/2003
Correction
Resolved
06/27/2003
IN-WALL SYSTEMS ROUGH OK TO COVER WHEN READY
Above Ceiling Inspection Failed 07/17/2003
Correction
Corrective Action Required
07/17/2003
CEILING TILE INSTALLATION LEAVE OUT THREE TILE (ONE @ SW CORNER) UNTIL FINAL INSPECTION. OK TO PROCEED WHEN CORRECTIONS ARE COMPLETED
Correction
Corrective Action Required
07/17/2003
FIRE-BLOCKING OF OCCUPANCY SEPARATION ABOVE SW CORNER INCOMPLETE PENETRATIONS OF DECK
Correction
Corrective Action Required
07/17/2003
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES AT OPPOSITE DIAGONAL CORNERS. TIE WITH TWO FULLWRAPS. NOT INSTALLED TWO TIES PER FIXTURE
Above Ceiling Inspection Passed 07/28/2003
Correction
Resolved
07/28/2003
CEILING TILE INSTALLATION
Correction
Resolved
07/28/2003
FIRE-BLOCKING OF OCCUPANCY SEPARATION
Correction
Resolved
07/28/2003
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES
Occupancy Inspection - Codes Commercial Failed 07/28/2003
Correction
Corrective Action Required
07/28/2003
OCCUPANCY STATUS IBC 110.1: UNTIL APPROVED DO NOT OCCUPY OR PLACE PERSONAL PROPERTY
Correction
Corrective Action Required
07/28/2003
LABELING OF ELECTRICAL CIRCUIT BREAKERS IRC E36O6.2. EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. INCOMPLETE/IMPROPER SERVICE PANEL
Correction
Corrective Action Required
07/28/2003
EMERGENCY LIGHTS & EXIT SIGNS NOT OPERATIONAL
Correction
Corrective Action Required
07/28/2003
CIRCUIT BREAKER INSTALLATION INCOMPLETE
Correction
Corrective Action Required
07/28/2003
RESTROOM LIGHT FIXTURES NOT INSTALLED
Correction
Corrective Action Required
07/28/2003
ELECTRICAL RECEPTACLES IRC E3901.10; E3902.6 <> NEC 380-10; 410-56(f) NOT TIGHT TO BOX CHECK ALL
Occupancy Inspection - Codes Commercial Passed 07/30/2003
Correction
Resolved
07/30/2003
OCCUPANCY STATUS OK TO OCCUPY ISSUE COFO
Correction
Resolved
07/30/2003
LABELING OF ELECTRICAL CIRCUIT BREAKERS
Correction
Resolved
07/30/2003
EMERGENCY LIGHTS & EXIT SIGNS
Correction
Resolved
07/30/2003
CIRCUIT BREAKER INSTALLATION
Correction
Resolved
07/30/2003
RESTROOM LIGHT FIXTURES TEMPORARY FIXTURES IN PLACE
Correction
Resolved
07/30/2003
ELECTRICAL RECEPTACLES
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home