B0300899
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
ALTERATION COMMERCIAL
ALTERATIONS TO PHARMACY
05/21/2003
06/12/2003
12/09/2003
06/12/2003
Locations
Contacts
JOE COONS CONSTRUCTION CO, Address:6431 N LONDON AVE  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/17/2003 10/29/2010
Correction

CA - A code analysis is not provided with the application.
Correction

Fire Department: Fire detection, alarm and extinguishing systems shall be maintained in an op-erative condition at all times, and shall be replaced or repaired where defective.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- The doors to be fixed closed shall be marked "Not An Exit".
Correction

Fire Department- Will chemo-therapy drugs be mixed at this location? If so, provide MSDS information and quantities of each compound. A Hazardous Material Permit may be required.
Correction

Fire Department- The basement of this building is not sprinklered and the existing facility does not meet the conditions of IFC Sections 903.12.1 through 903.2.12.1.3.. The existing automatic sprinkler system shall be extended into the basement area.
Correction

Fire Department- The space shall be provided with an automatic sprinkler system.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1003.2.11 - The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
Correction

CA - 2000 IBC 1003.2.10 - Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visable to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible exit sign.
Correction

Fire Department; Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Combustible debris, waste materials and trash shall not be burned on site.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

CA - 2000 IBC 3006.4 - Machine rooms and machinery spaces. Elevator machine rooms and machinery spaces shall be enclosed with construction having a fire-resistance rating not less than the required rating of the hoistway enclosure served by the machinery. Openings shall be protected with assemblies having a fire-resistance rating not less than that required for the hoistway enclosure doors.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $350.00 $350.00 Paid 06/12/2003
24 BLDG Plan Check Fees $25.80 $25.80 Paid 06/12/2003
25 Electrical Permit Fee $80.00 $80.00 Paid 06/12/2003
25 Mechanical Permit Fees $36.00 $36.00 Paid 06/12/2003
25 Plumbing Permit Fees $19.00 $19.00 Paid 06/12/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 06/18/2003
Correction
Resolved
06/18/2003
UNDER-FLOOR D&W EXCAVATED; LAID; JOINED OK TO COVER WHEN READY
All Rough Inspection - Commercial Not Ready 06/25/2003
Correction
Corrective Action Required
06/25/2003
IN-WALL SYSTEMS - READINESS FOR INSPECTION WALL FRAMING, ELECTRICAL IN-WALL WORK APPEAR TO BE INCOMPLETE. CALL FOR IN-WALL INSPECTION WHEN PREPARATION IS COMPLETE. WORK NOT COMPLETED NOT READY FOR INSPECTION
All Rough Inspection - Commercial Partial 06/26/2003
Correction
Resolved
06/26/2003
IN-WALL SYSTEMS - READINESS FOR INSPECTION
Correction
Partial Correction
06/26/2003
IN-WALL SYSTEMS ROUGH 1) RM 102: COPPER WATER PIPE NOT COMPLETELY PROTECTED @ STUD PENETRATIONS 2) RM 104: EXISTING CONDUIT, BOXES, CABLE NOT REMOVED @ N WALL OK TO COVER WALLS EXCEPT RM 102 & RM 104 N WALL
All Rough Inspection - Commercial Passed 06/27/2003
Correction
Resolved
06/27/2003
IN-WALL SYSTEMS ROUGH CALL FOR ABOVE-CEILING INSPECTION WHEN READY, AND BEFORE CLOSING CEILING. OK TO COVER WALLS WHEN READY
Above Ceiling Inspection Failed 07/23/2003
Correction
Corrective Action Required
07/23/2003
UNUSED KNOCKOUTS AT ELECTRICAL JUNCTION BOXES NOT PLUGGED
Correction
Corrective Action Required
07/23/2003
INSTALLATION/SUPPORT OF LOW VOLTAGE CABLE DO NOT SUPPORT FROM OTHER MEP SYSTEMS OR ON CEILING SYSTEM INCOMPLETE NOT SECURED TO STRUCTURE
Correction
Corrective Action Required
07/23/2003
ELECTRICAL CONDUCTORS ENTERING SERVICE PANEL IRC E3702.1; NEC 336-18 NOT SECURED TO STRUCTURE WITHIN 12" OF ENTRY
Correction
Corrective Action Required
07/23/2003
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES AT OPPOSITE DIAGONAL CORNERS. TIE WITH TWO FULLWRAPS. NOT INSTALLED TWO TIES PER FIXTURE
Correction
Corrective Action Required
07/23/2003
SECURING/SUPPORT OF MC ELECTRICAL CABLE 4.5' MAX INTERVALS AND WITHIN 12" OF BOXES INCOMPLETE NEC 334-10
Correction
Corrective Action Required
07/23/2003
ELECTRICAL JUNCTION BOXES NOT CLOSED
Above Ceiling Inspection Passed 07/24/2003
Correction
Resolved
07/24/2003
UNUSED KNOCKOUTS AT ELECTRICAL JUNCTION BOXES
Correction
Resolved
07/24/2003
INSTALLATION/SUPPORT OF LOW VOLTAGE CABLE
Correction
Resolved
07/24/2003
ELECTRICAL CONDUCTORS ENTERING SERVICE PANEL IRC E3702.1; NEC 336-18 WILL BE CHECKED AT FINAL INSPECTION
Correction
Resolved
07/24/2003
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES
Correction
Resolved
07/24/2003
SECURING/SUPPORT OF MC ELECTRICAL CABLE
Correction
Resolved
07/24/2003
ELECTRICAL JUNCTION BOXES
Occupancy Inspection - Codes Commercial Failed 08/01/2003
Correction
Corrective Action Required
08/01/2003
Receive Fire Department approval
Correction
Corrective Action Required
08/01/2003
LABELING OF ELECTRICAL CIRCUIT BREAKERS IRC E36O6.2. EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. USE DIRECTIONS (e.g. NE, SW) RATHER THAN ROOM NUMBERS; NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. INCOMPLETE/IMPROPER SERVICE PANEL
Correction
Corrective Action Required
08/01/2003
DOOR TO ELEVATOR PUMP ROOM ACCESS 110 NOT 1-1/2 HR RATED PER DRAWING
Occupancy Inspection - Codes Commercial Failed 08/08/2003
Correction
Corrective Action Required
08/08/2003
LABELING OF ELECTRICAL CIRCUIT BREAKERS REMOVE SUPERCEEDED PAPER LABELS IN PANEL PLACE NUMERIC LABELS BESIDE BREAKERS TO MATCH TYPED SCHEDULE. INCOMPLETE SERVICE PANEL
Correction
Corrective Action Required
08/08/2003
DOOR TO ELEVATOR PUMP ROOM ACCESS 110 REVISED DRAWING ON-SITE. SUBMIT & OBTAIN APPROVAL FROM LSCA PLAN REVIEW. NOT 1-1/2 HR RATED PER DRAWING
Occupancy Inspection - Codes Commercial Passed 08/22/2003
Correction
Resolved
08/22/2003
Receive Fire Department approval P N ULLERY 8/22/03
Correction
Resolved
08/22/2003
LABELING OF ELECTRICAL CIRCUIT BREAKERS CORRECT LABELING OF CIRCUIT #29
Correction
Resolved
08/22/2003
DOOR TO ELEVATOR PUMP ROOM ACCESS 110
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home