Permit Application Status

B0300896


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0300896
Building Permit - Commercial
Certificate of Occupancy
OCTOBER SKY DEVELOPERS LLC
NEW TENANT FINISH
ALTAMERE WINDOW TINT TENANT FINISH
05/21/2003
06/03/2003
11/30/2003
09/12/2003
Locations
Contacts
HEARTLAND STUCCO, Address:5112 SW PIPING PLOVER DR  
GUY GRONBERG ARCHITECTS, PC, Address:PO BOX 2024  
OCTOBER SKY DEVELOPERS LLC, Address:PO BOX 2372  
CFC SQUARED LLC, Address:1314 SW MARKET ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/17/2003 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - The plan review for this project was perfomed on the information indicating that the tenant will be limited to applying window tinting to cars. The tenant in this location will not use this space for the exchange of parts, mechanical repair or operations requiring welding, sparks or compressed gases.
Correction

CA - As the work in the areas of plumbing, mechanical and electrical is minor in nature, plans for such work were not required for permiting. Compliance with the codes as amended and adopted by the City of Lee's Summit will be verified in the field. Violations noted by the field staff will be repaired and reinspected prior to covering.
Correction

Fire Department: Information needed on type of work to be conducted within the structure.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

CA - 2000 IBC 1209.1 - In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Fire Department; Egress from a room or space shall not pass through adjoining or interven-ing rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not a high-hazard occupancy; and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit access shall not pass though a room which can be locked to prevent egress. IFC 1004.2.3
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IPC 403.2 - Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $32.00 $32.00 Paid 06/03/2003
24 BLDG Plan Check Fees $4.50 $4.50 Paid 06/03/2003
25 Electrical Permit Fee $30.00 $30.00 Paid 06/03/2003
25 Mechanical Permit Fees $15.00 $15.00 Paid 06/03/2003
25 Plumbing Permit Fees $11.00 $11.00 Paid 06/03/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 06/09/2003
Correction
Corrective Action Required
06/09/2003
SEE TEXT SECURE FLOOR JOIST IN STORAGE TO GIRT LATERALLY BLOCK FREE(NONLAPPED) ENDS OF FLOOR JOISTS IN WALL APPROVED OK TO COVER WALL
Above Ceiling Inspection Partial 06/23/2003
Correction
Partial Correction
06/23/2003
EXCESS ELEC. WIRE SECURE OR TERMINATE EXCESS ELECTRIAL WHIP IN SW SECTION OF OFFICE. EVERYTHING ELSE OKAY TO DROP.
Occupancy Inspection - Codes Commercial Failed 06/24/2003
Correction
Corrective Action Required
06/24/2003
GRAB BARS INSTALL GRAB BARS IN WEST BATHROOM.
Occupancy Inspection - Codes Commercial Passed 09/11/2003
Correction
Resolved
09/11/2003
GRAB BARS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home