Summary
B0300649
Building Permit - Commercial
Final Completion
JOHN KNOX VILLAGE
ALTERATION COMMERCIAL
COMMERCIAL ALTERATION
04/18/2003
06/11/2003
12/08/2003
11/06/2003
Locations
Contacts
THE WEITZ COMPANY, Address:9900 W 109TH ST  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/15/2003 10/29/2010
Correction

Fire Department- The design and installation of commercial kitchen exhaust hoods shall be in accordance with the International Mechanical Code. Clearance between the duct work and building shallbe per NFPA 96.
Correction

Fire Department- Activation of the hood fire suppression system shall activate the building alarm system. IFC 907.14
Correction

Fire Department- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. IFC 1003.2.2.5
Correction

Fire Department- Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. IFC 907.12
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.IFC 1003.2.10.1
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

CA - 2000 IBC 1004.3.2.1 - Corridor construction. Corridors shall be fire-resistance rated in accordance with Table 1004.3.2.1. The corridor walls required to be fire-resistance-rated shall comply with Section 708 for fire partitions.
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IMC 507.2 - Where required. A Type I or Type II hood shall be installed at or above all commercial food heat-processing appliances. A Type II hood shall be installed above commercial dishwashing machines.
Correction

CA - 2000 IPC 904.1 - All open vent pipes that extend through a roof shall be terminiated at least 6 inches above the roof, except that where a roof is to be used for any purpose other than weather protection, the vent extensions shall be run at least 7 feet above the roof.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1003.3.1.9 - Panic and fire exit hardware. Each door in a means of egress from an occupancy of Group A or E having an occupant load of 100 or more and any occupancy of Group H-1, H-2, H-3 or H-5 shall not be provided with a latch or lock unless it is panic hardware of fire exit hardware.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $167.00 $167.00 Paid 06/11/2003
24 BLDG Plan Check Fees $15.50 $15.50 Paid 06/11/2003
25 Electrical Permit Fee $115.00 $115.00 Paid 06/11/2003
25 Mechanical Permit Fees $119.00 $119.00 Paid 06/11/2003
25 Plumbing Permit Fees $111.50 $111.50 Paid 06/11/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Not Ready 07/25/2003
Correction
Corrective Action Required
07/25/2003
READINESS FOR INSPECTION LSCO 7-142: NOT READY FOR INSPECTION PERMIT PRINTS NOT FOUND ON SITE
All Rough Inspection - Commercial Partial 07/29/2003
Correction
Partial Correction
07/29/2003
IN-WALL SYSTEMS ROUGH - PARTIAL FIRE CAULK ELECT CONDUIT FLOOR BORE @ HAIR WASH SE BEAUTY SHOP 106 OK TO COVER AFTER
Correction
Resolved
07/29/2003
READINESS FOR INSPECTION
All Rough Inspection - Commercial Partial 08/08/2003
Correction
Partial Correction
08/08/2003
IN-WALL SYSTEMS ROUGH - PARTIAL 107: FIRE-BLOCK HOLE IN N WALL AND SHAFT ABOVE -- PER DISCUSSION; CALL FOR REINSPECTION ROOMS 121-125; 127 OK TO COVER WHEN READY
Correction
Partial Correction
08/08/2003
IN-WALL SYSTEMS ROUGH - PARTIAL BEAUTY SHOP 106
All Rough Inspection - Commercial Partial 08/11/2003
Correction
Partial Correction
08/11/2003
IN-WALL SYSTEMS ROUGH - PARTIAL ROOMS 107; 121-125; 127 OK TO COVER WHEN READY
Correction
Resolved
08/11/2003
IN-WALL SYSTEMS ROUGH - PARTIAL BEAUTY SHOP 106
Rated Assembly Inspection Partial 08/11/2003
Correction
Partial Correction
08/11/2003
S WALL OF ENTRY 127 1ST LAYER 5/8" TYPE X GWB OK TO COVER WHEN READY
Above Ceiling Inspection Passed 08/28/2003
Correction
Resolved
08/28/2003
ABOVE-CEILING SYSTEMS - PARTIAL RMS 106;107; 121-125; 127 OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 08/29/2003
Correction
Partial Correction
08/29/2003
IN-WALL SYSTEMS ROUGH - PARTIAL HALLWAY 109; RMS 101; 102 OK TO COVER WHEN READY
Correction
Resolved
08/29/2003
IN-WALL SYSTEMS ROUGH - PARTIAL ROOMS 107; 121-125; 127
Occupancy Inspection - Codes Commercial Failed 09/02/2003
Correction
Corrective Action Required
09/02/2003
TOILET ACCESSORIES NOT INSTALLED
Correction
Corrective Action Required
09/02/2003
TOILET PARTITIONS NOT INSTALLED
Correction
Corrective Action Required
09/02/2003
FIRE SEPARATION DOOR OPENING 127 NOT INSTALLED
Correction
Corrective Action Required
09/02/2003
FINISH HARDWARE @ DOOR 125 PERMANENT NOT INSTALLED
Correction
Corrective Action Required
09/02/2003
GLAZING @ DOOR 107 NOT INSTALLED SUBJECT TO APPROVAL
Correction
Corrective Action Required
09/02/2003
PARTIAL OCCUPANCY - BEAUTY SHOP AREA FIRE DEPT REQUIRES ALARM NOTIFICATION PROVISION BE ACTIVATED SEPARATE CONSTRUCTION FROM OCCUPANCY AT 1) HALLWAY 121 S END 2) WINDOW OPENING @ RM 125 S WALL RMS 106;107; 121-125; 127 TEMPORARY OCC NOT OK
Occupancy Inspection - Codes Commercial Partial 09/04/2003
Correction
Resolved
09/04/2003
GLAZING @ DOOR 107
Correction
Partial Correction
09/04/2003
PARTIAL OCCUPANCY - BEAUTY SHOP AREA PENDING RESOLUTION OF OUTSTANDING ISSUES AND COMPLETION/APPROVAL OF DINING AREA + KITCHEN. IMMEDIATELY SEPARATE CONSTRUCTION FROM OCCUPANCY AT S END HALLWAY 121. RMS 106;107; 121-125; 127 OK THROUGH 10/30/03
All Rough Inspection - Commercial Partial 09/04/2003
Correction
Partial Correction
09/04/2003
IN-WALL SYSTEMS ROUGH - PARTIAL OK TO COVER WHEN READY REMAINDER OF DINING AREA BUT EXCLUDING KITCHEN
Correction
Resolved
09/04/2003
IN-WALL SYSTEMS ROUGH - PARTIAL HALLWAY 109; RMS 101; 102
Above Ceiling Inspection Partial 09/04/2003
Correction
Resolved
09/04/2003
ABOVE-CEILING SYSTEMS - PARTIAL RMS 106;107; 121-125; 127
Correction
Partial Correction
09/04/2003
ABOVE-CEILING SYSTEMS ROUGH - PARTIAL OK TO COVER WHEN READY DINING AREA GWB HARD LID AREAS
All Rough Inspection - Commercial Partial 09/19/2003
Correction
Corrective Action Required
09/19/2003
WATER PIPING TO EXISTING DRINKING FOUNTAIN PRIOR TO INSTALLING WALK-IN COOLER/FREEZER DAMAGED @ HORIZONTAL LEG REPLACE & HAVE INSPECTED
Correction
Resolved
09/19/2003
IN-WALL SYSTEMS ROUGH - FINAL OK TO COVER WHEN READY
Correction
Resolved
09/19/2003
IN-WALL SYSTEMS ROUGH - PARTIAL
Above Ceiling Inspection Partial 10/07/2003
Correction
Resolved
10/07/2003
ABOVE-CEILING SYSTEMS ROUGH - PARTIAL DINING AREA GWB HARD LID AREAS
Correction
Partial Correction
10/07/2003
ABOVE-CEILING SYSTEMS ROUGH E END OF 101 OPEN ELECT J.B. & UNTERMINATED FIXTURE WHIPS; N 12` OF 102 DAMAGED PRE-CAST CONCRETE FLOOR UNITS WITH PRE-STRESS TENDONS SEVERED. REQUIRE ENGINEER`S REPORT. RMS 101-105; 118-120 OK TO COVER EXCEPT:
Gas Service Inspection - Commercial Not Ready 10/09/2003
Correction
Corrective Action Required
10/09/2003
TEST PRESSURE LEVEL PRESSURIZE SYSTEM TO HOLD STEADY AT OR ABOVE MINIMUM BELOW REQUIRED MINIMUM 10 PSI or 6" Hg REQUIRED
Gas Piping Inspection - Commercial Failed 10/09/2003
Correction
Corrective Action Required
10/09/2003
PIPING SUPPORT @ ROOF 1) CHECK SPACING PER IFCG TABLE 415.1 2) SUPPORT @ CHANGES OF DIRECTION 3) NO STRAPS TO WOOD BLOCKS 4) LAYERED BLOCKS NOT FASTENED TOGETHER INCOMPLETE PER IFCG 415 & DRWG P-1
Gas Piping Inspection - Commercial Passed 10/13/2003
Correction
Resolved
10/13/2003
PIPING SUPPORT @ ROOF
Gas Service Inspection - Commercial Passed 10/13/2003
Correction
Resolved
10/13/2003
TEST PRESSURE LEVEL RELEASE GAS SERVICE HELD STEADY AT >= 10 PSI FOR > 30 MIN
All Rough Inspection - Commercial Passed 10/13/2003
Correction
Resolved
10/13/2003
WATER PIPING TO EXISTING DRINKING FOUNTAIN
Above Ceiling Inspection Passed 10/28/2003
Correction
Resolved
10/28/2003
ABOVE-CEILING SYSTEMS ROUGH ALL OK TO COVER WHEN READY
Rated Assembly Inspection Passed 10/28/2003
Correction
Resolved
10/28/2003
S WALL OF ENTRY 127
Occupancy Inspection - Codes Commercial Failed 10/28/2003
Correction
Resolved
10/28/2003
PARTIAL OCCUPANCY - BEAUTY SHOP AREA
Correction
Resolved
10/28/2003
FINISH HARDWARE @ DOOR 125
Correction
Resolved
10/28/2003
FIRE SEPARATION DOOR OPENING 127
Correction
Resolved
10/28/2003
TOILET PARTITIONS
Correction
Resolved
10/28/2003
TOILET ACCESSORIES
Correction
Corrective Action Required
10/28/2003
KITCHEN/DINING AREA INSPECTION SCHEDULED 10/29/03
Occupancy Inspection - Codes Commercial Partial 10/29/2003
Correction
Partial Correction
10/29/2003
KITCHEN/DINING AREA KITCHEN / DINNING ROOM AREA - OCCUPANCY APPROVED. HOLD FOR FIRE DEPT. APPROVAL INSPECTION SCHEDULED 10/29/03
Occupancy Inspection - Codes Commercial Passed 11/05/2003
Correction
Resolved
11/05/2003
KITCHEN/DINING AREA
Correction
Resolved
11/05/2003
Receive Fire Department approval PER N ULLERY 10/3/03
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.