Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/10/2003 10/29/2010
Correction

CA - Provide location of the following equipment for review: furnace, electrical panel, water heater.
Correction

CA - Indicate the occupant load per Chapter 10 of the 2000 IBC.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

CA - 2000 IBC 1209.1 - In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

CA - 2000 IBC 1108.4 - Where kitchen, kitchenettes and wet bars are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC/ANSI A117.1.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

CA - Indicate the occupancy type per Chapter 3 of the 2000 International Building Code.
Correction

CA - 2000 IBC 1003.2.10 - Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visable to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible exit sign.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $92.00 $92.00 Paid 03/27/2003
24 BLDG Plan Check Fees $9.50 $9.50 Paid 03/27/2003
25 Electrical Permit Fee $80.00 $80.00 Paid 03/27/2003
25 Mechanical Permit Fees $24.00 $24.00 Paid 03/27/2003
25 Plumbing Permit Fees $19.00 $19.00 Paid 03/27/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Not Ready 04/02/2003
Correction
Corrective Action Required
04/02/2003
READINESS FOR INSPECTION FORMAL INSPECTION REQUIRES PERMIT PRINTS. RE-SCHEDULE WHEN PRINTS ARE ON-SITE. PRELIMINARY OBSERVATION: COPPER WATER PIPING NOT PROTECTED AT PASSAGES THRU STEEL STUDS & PLATES. WATER SERVICE RISER MUST BE LEFT ACCESSIBLE. PERMIT PRINTS NOT FOUND ON SITE > NOT READY
All Rough Inspection - Commercial Partial 04/03/2003
Correction
Resolved
04/03/2003
READINESS FOR INSPECTION
Correction
Partial Correction
04/03/2003
IN-WALL SYSTEMS 1) NORTH WALL OF WEST RESTROOM, WHERE EXISTING ELECTRICAL BOXES & CONDUIT MUST FIRST BE REMOVED. 2) WATER SERVICE RISER, AND ELECTRICAL GROUND CONNECTION TO IT, MUST NOT BE FULLY ENCLOSED. 3) ELECTRICAL EQUIPMENT, INCLUDING GUTTER, MUST REMAIN CLEAR. APPROVED > OK TO COVER EXCEPT BELOW
Above Ceiling Inspection Not Ready 04/03/2003
Correction
Corrective Action Required
04/03/2003
SYSTEMS ABOVE CEILING HVAC NOT COMPLETE; PLUMBING NOT COMPLETE; ELECTRICAL CONDUIT SUPPORTED ON OTHER SYSTEMS (e.g. DUCTWORK, CEILING SUPPORT WIRES); ELECTRICAL BOXES NOT SECURED TO STRUCTURE; CHECK ELECT BOX FILL AGAINST NEC MAXIMUMS. NOT READY FOR INSPECTION PRELIMINARY OBSERVATIONS:
All Rough Inspection - Commercial Partial 04/11/2003
Correction
Partial Correction
04/11/2003
IN-WALL SYSTEMS 1) EXISTING ELECTRICAL BOXES & CONDUIT BEHIND NORTH WALL OF WEST RESTROOM MUST BE REMOVED. 2) WATER SERVICE RISER, AND ELECTRICAL GROUND CONNECTION TO IT, MUST BE ACCESSIBLE. 3) ELECTRICAL EQUIPMENT, INCLUDING GUTTER, MUST REMAIN CLEAR. APPROVED > OK TO COVER EXCEPT BELOW
Above Ceiling Inspection Passed 04/11/2003
Correction
Resolved
04/11/2003
SYSTEMS ABOVE CEILING HVAC DUCTVCONNECTIONS TO DIFFUSERS; MC CABLE PRESENTLY UNTERMINATED (2 LOCATIONS). ALL OTHER OK TO COVER. FINAL INSPECTION WILL INCLUDE RE-CHECKING OF
All Rough Inspection - Commercial Passed 04/14/2003
Correction
Resolved
04/14/2003
IN-WALL SYSTEMS
Above Ceiling Inspection Passed 04/14/2003
Correction
Resolved
04/14/2003
SYSTEMS ABOVE CEILING
Occupancy Inspection - Codes Commercial Failed 04/14/2003
Correction
Corrective Action Required
04/14/2003
PARKING LOT COMPLETE PARKING LOT, H.C. RAMP, STRIPING, H.C. SIGNAGE, TRASH ENCLOSURE, ETC.
Correction
Corrective Action Required
04/14/2003
EXTERIOR COVERINGS REPAIR DAMAGED DRYVIT ON EAST SIDE OF BUILDING
Correction
Corrective Action Required
04/14/2003
SIGNAGE REMOVE BANNER SIGN OR OBTRAIN TEMPORARY BANNER PERMIT FROM P & D.
Correction
Corrective Action Required
04/14/2003
ROOF DRAINAGE INSTALL DOWNSPOUT AT EAST SIDE OF BUILDING (WHERE BRICK VENEER MEETS DRYVIT)
Correction
Corrective Action Required
04/14/2003
OPEN ELECTRICAL CONDUIT CAP OFF OR OTHERWISE SEAL OPEN ELECTRICAL CONDUIT IN SIDEWALK AT EAST SIDE OF BUILDING. CONDUCTORS NO LONGER NEEDED OR HOT PER CONTRACTOR.
Correction
Corrective Action Required
04/14/2003
OPEN OR UNUSED ELECTRICAL REMOVE OR PROPERLY TERMINATE ELECTRCAL UNDER GLASS DISPLAY (NEAR WEST FRONT DOOR)
Correction
Corrective Action Required
04/14/2003
OPEN ELECTRICAL INSTALL COVER AT OPEN J-BOX ABOVE CEILING AT MIRRORED PLATFORM ABOVE SOUTH WALL TRACK LIGHTING.
Correction
Corrective Action Required
04/14/2003
BACKFLOW INSTALL AVB AT HOSE BIBB AT WATER SERVICE SHUT-OFF LOCATION. SHUT-OFF SHALL REMAIN ACCESSIBLE.
Correction
Corrective Action Required
04/14/2003
CIRCUIT LABELING LABEL ALL CIRCUITS WITHIN PANELS
Correction
Corrective Action Required
04/14/2003
OPEN DWV PIPING CAP UNUSED DWV PLUMBING IN ELECTRICAL ROOM, OR INSTALL SINK AS SHOWN IN PLANS.
Correction
Corrective Action Required
04/14/2003
ACCESSIBILITY (KNEE PROTECTION) PROVIDE KNEE PROTECTION AT PLUMBING UNDER LAVATORIES
Correction
Corrective Action Required
04/14/2003
EMERGENCY LIGHTING INSTALL EMERGENCY LIGHTING
Correction
Corrective Action Required
04/14/2003
EXIT LIGHTING TWO EXIT LIGHTS AT FRONT NOT FUNCTIONING AT TIME OF INSPECTION DUE TO ELECTRICAL WORK BEING PERFORMED. ENSURE OPERATING ON BOTH PRIMARY AND BACK-UP SYSTEMS.
Occupancy Inspection - Codes Commercial Failed 07/31/2003
Correction
Corrective Action Required
07/31/2003
PARKING LOT COMPLETE PARKING LOT, H.C. RAMP, STRIPING, H.C. SIGNAGE, TRASH ENCLOSURE, ETC.
Correction
Resolved
07/31/2003
SIGNAGE
Correction
Resolved
07/31/2003
ROOF DRAINAGE
Correction
Corrective Action Required
07/31/2003
OPEN ELECTRICAL CONDUIT CAP OFF OR OTHERWISE SEAL OPEN ELECTRICAL CONDUIT IN SIDEWALK AT EAST SIDE OF BUILDING. CONDUCTORS NO LONGER NEEDED OR HOT PER CONTRACTOR.
Correction
Corrective Action Required
07/31/2003
OPEN OR UNUSED ELECTRICAL REMOVE OR PROPERLY TERMINATE ELECTRCAL UNDER GLASS DISPLAY (NEAR WEST FRONT DOOR)
Correction
Resolved
07/31/2003
OPEN ELECTRICAL
Correction
Corrective Action Required
07/31/2003
CIRCUIT LABELING LABEL ALL CIRCUITS WITHIN PANELS
Occupancy Inspection - Codes Commercial Passed 12/11/2003
Correction
Resolved
12/11/2003
PARKING LOT
Correction
Resolved
12/11/2003
EXTERIOR COVERINGS
Correction
Resolved
12/11/2003
OPEN ELECTRICAL CONDUIT
Correction
Resolved
12/11/2003
OPEN OR UNUSED ELECTRICAL
Correction
Resolved
12/11/2003
BACKFLOW
Correction
Resolved
12/11/2003
CIRCUIT LABELING
Correction
Resolved
12/11/2003
OPEN DWV PIPING
Correction
Resolved
12/11/2003
ACCESSIBILITY (KNEE PROTECTION)
Correction
Resolved
12/11/2003
EMERGENCY LIGHTING
Correction
Resolved
12/11/2003
EXIT LIGHTING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home