B0300303
Building Permit - Commercial
Final Completion
LEES SUMMIT SCHOOL DIST R 7
ALTERATION COMMERCIAL
PRESS BOX ADD & PARKING LOT LIGHTS
02/27/2003
04/25/2003
10/22/2003
02/10/2004
Locations
Contacts
JE DUNN CONSTRUCTION CO., Address:929 HOLMES  
LEES SUMMIT SCHOOL DIST R 7, Address:600 MILLER  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/26/2003 10/29/2010
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $107.00 $107.00 Paid 04/25/2003
24 BLDG Plan Check Fees $10.75 $10.75 Paid 04/25/2003
25 Electrical Permit Fee $50.00 $50.00 Paid 04/25/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Electrical Inspection - Commercial Partial 04/25/2003
Correction
Partial Correction
04/25/2003
U.G. ELECTRICAL CONDUIT - PARTIAL PER DRAWINGS E1.7 & E1.8 AND SKCE WORK SKETCH (FILED). INSPECTED AND APPROVED 4/24/03 PRIOR TO ISSUANCE OF APPLIED-FOR PERMIT. SUBSTANTIALLY BACKFILLED DUE TO TIMING OF WORK VS. ISSUANCE OF PERMIT. FROM PRESS BOX WEST + FROM PRESS BOX NORTH
Underground Electrical Inspection - Commercial Partial 05/23/2003
Correction
Resolved
05/23/2003
U.G. ELECTRICAL CONDUIT - PARTIAL PER DRAWINGS E1.7 & E1.8 AND SKCE WORK SKETCH (FILED). INSPECTED AND APPROVED 4/24/03 PRIOR TO ISSUANCE OF APPLIED-FOR PERMIT. SUBSTANTIALLY BACKFILLED DUE TO TIMING OF WORK VS. ISSUANCE OF PERMIT. FROM PRESS BOX WEST + FROM PRESS BOX NORTH
Correction
Partial Correction
05/23/2003
U.G. ELECT CONDUIT - PARTIAL FROM PRESS BOX TO POLE LIGHT & SCOREBOARD EAST SOCCER FIELD ONE 1" + ONE 1 -1/2" PVC
Underground Electrical Inspection - Commercial Partial 05/27/2003
Correction
Resolved
05/27/2003
U.G. ELECT CONDUIT - PARTIAL FROM PRESS BOX TO POLE LIGHT & SCOREBOARD EAST SOCCER FIELD ONE 1" + ONE 1 -1/2" PVC
Correction
Partial Correction
05/27/2003
U.G. ELECT CONDUIT - PARTIAL FROM NORTHMOST LIGHT POLE SOUTH TO CENTER POLE. SEE SKETCH ONE 3/4" PVC UNDER CURB ALONG E BOUNDARY E PK LOT
Underground Electrical Inspection - Commercial Partial 05/30/2003
Correction
Resolved
05/30/2003
U.G. ELECT CONDUIT - PARTIAL FROM NORTHMOST LIGHT POLE SOUTH TO CENTER POLE. SEE SKETCH ONE 3/4" PVC UNDER CURB ALONG E BOUNDARY E PK LOT
Correction
Partial Correction
05/30/2003
U.G. ELECT CONDUIT - PARTIAL ALL 3/4" PVC EXCEPT SW CORNER 1" N END TO S END E PKG LOT E-W ACROSS S END E PK LOT
Underground Electrical Inspection - Commercial Passed 09/04/2003
Correction
Resolved
09/04/2003
U.G. ELECT CONDUIT - PARTIAL ALL 3/4" PVC EXCEPT SW CORNER 1" N END TO S END E PKG LOT E-W ACROSS S END E PK LOT
Occupancy Inspection - Codes Commercial Partial 09/04/2003
Correction
Partial Correction
09/04/2003
BUILDING OCCUPANCY STATUS NO LATER THAN 9/11/03 OK FOR TEMPORARY USE PENDING FULL FINAL INSP
Occupancy Inspection - Codes Commercial Partial 09/12/2003
Correction
Partial Correction
09/12/2003
BUILDING OCCUPANCY STATUS PENDING RESOLUTION OF OUTSTANDING ISSUES OK FOR TEMPORARY USE THROUGH 9/18/03
Correction
Corrective Action Required
09/12/2003
Receive Fire Department approval SEE FD LIST DTD 9/12/03
Correction
Corrective Action Required
09/12/2003
Receive Public Works Approval ELEV OF WATER METER WELL TO BE RAISED
Correction
Corrective Action Required
09/12/2003
PENETRATIONS/HOLES IN EXTERIOR WALL IRC R703.1: SEAL ANNULAR SPACE NOT SEALED PIPE, CONDUIT
Correction
Corrective Action Required
09/12/2003
SECURING OF CONDUIT NEW & EXISTING INCOMPLETE
Correction
Corrective Action Required
09/12/2003
ABANDONED CONDUIT & CABLE NOT REMOVED
Correction
Resolved
09/12/2003
Receive Planning & Development Approval PER T SCANNELL 9/12/03
Occupancy Inspection - Codes Commercial Partial 09/19/2003
Correction
Partial Correction
09/19/2003
BUILDING OCCUPANCY STATUS SEE TEMPORARY OCCUPANCY
Correction
Resolved
09/19/2003
Receive Fire Department approval PER N ULLERY 9/19/03
Correction
Resolved
09/19/2003
PENETRATIONS/HOLES IN EXTERIOR WALL
Correction
Resolved
09/19/2003
SECURING OF CONDUIT
Correction
Resolved
09/19/2003
ABANDONED CONDUIT & CABLE
Correction
Partial Correction
09/19/2003
Receive Planning & Development Approval TO BE PLANTED IN NOVEMBER PER T SCANNELL 9/12/03 ALL OK EXCEPT TREES
Occupancy Inspection - Codes Commercial Passed 12/12/2003
Correction
Resolved
12/12/2003
BUILDING OCCUPANCY STATUS
Correction
Resolved
12/12/2003
Receive Public Works Approval PER BILL LYON 12/11/03
Correction
Resolved
12/12/2003
Receive Planning & Development Approval NO ISSUES CITED AS OF 12/12/03
Correction
Resolved
12/12/2003
CLOSE PERMIT
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home