Permit Application Status

B0300302


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0300302
Building Permit - Commercial
Certificate of Occupancy
HEUERTZ LINDA B
NEW COMMERCIAL
RELOCATE RELOCATABLE CLASSROOM
02/27/2003
04/17/2003
10/14/2003
07/23/2003
Locations
Contacts
LEE'S SUMMIT R-7 SCHOOL DISTRICT, Address:702 SE STATE ROUTE 291  
HEUERTZ LINDA B, Address:610 SE MILLER  
LEES SUMMIT SCHOOL DIST R 7, Address:600 MILLER  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/26/2003 10/29/2010
Correction

CA - Varification of code compliance on the electric, water and sewer services will be verified on inspection.
Correction

CA - ANSI A117.1 405.2 - Slope. Ramp runs shall have a running slope not steeper than 1:12.
Correction

CA - ANSI A117.1-1998 405.8 - Handrails. Ramps with a rise greater than 6 inches shall have handrails complying with Section 505. Handrails shall not reduce the required clearances of a ramp run or landing.
Correction

CA - ANSI A117.1-1998 405.9.2 - Curb or Barrier. A curb or barrier shall be provided that prevents the passage of a 4-inch diameter sphere below a height of 4 inches.
Correction

CA - The Final Development Plan shall be approved prior to issuing any building permits.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. IFC 1003.2.10.4 Exit sign illumination shall also be in accordance with the IBC.
Correction

Fire Department; An approved lock shall be installed on gates or similar barriers when required by the code official.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $17.00 $17.00 Paid 04/17/2003
24 BLDG Plan Check Fees $3.25 $3.25 Paid 04/17/2003
25 Electrical Permit Fee $30.00 $30.00 Paid 04/17/2003
25 Plumbing Permit Fees $10.00 $10.00 Paid 04/17/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Passed 04/23/2003
Correction
Resolved
04/23/2003
None 53 PIERS 30"/18" DEEP
Underground Plumbing Inspection - Commercial Passed 05/13/2003
Correction
Resolved
05/13/2003
3/4" PEX SDR-9 WATER LINE OK TO COVER WHEN READY FROM TIE-IN @ EXISTG TO RELOCATABLE NEW LOCATION
Miscellaneous Inspection Passed 06/17/2003
Correction
Resolved
06/17/2003
TIE DOWNS APPROVED PER SPECIFICATIONS SUBMITTED.
Rough Plumbing Inspection - Commercial Passed 06/25/2003
Correction
Resolved
06/25/2003
PVC DRAIN PIPING BUILDING SYSTEM CONNECTION. PLMBR NOT ON-SITE. ELECTRICIAN ON JOBSITE AGREED TO CHANGE PLMBG HANGER TO ELIMINATE BEARING AGAINST MC ELECT CABLE. RUN EXPOSED IN CRAWL AREA FROM U.G. SAN LINE TO
Electrical Service Inspection Passed 07/01/2003
Correction
Resolved
07/01/2003
TWO 200 AMP SERVICES APPROVED RELEASE SERVICE
Final Electrical Inspection - Commercial Not Ready 07/01/2003
Correction
Corrective Action Required
07/01/2003
CLOSE PERMIT NOT APPLICABLE
Final Electrical Inspection - Commercial Passed 07/17/2003
Correction
Resolved
07/17/2003
CLOSE PERMIT ***DISREGARD*** ***NOT APPLICABLE***
Occupancy Inspection - Codes Commercial Failed 07/17/2003
Correction
Corrective Action Required
07/17/2003
ROOF DRAINAGE SYSTEM INSTALL DOWNSPOUTS AND SPLASHBLOCKS OR LEADERS
Correction
Corrective Action Required
07/17/2003
STAIR & RAMP TRANSITIONS TO GRADE MEANS TO ENTER & EXIT. NOTE LSCO 7-910: MAX TREAD OR RISER VARIATION 3/8" INCOMPLETE INSTALL LANDINGS OR OTHER
Correction
Corrective Action Required
07/17/2003
OCCUPANCY STATUS IBC 110.1: UNTIL SAFETY ISSUES ARE APPROVED OCCUPANCY STATUS DO NOT OCCUPY
Occupancy Inspection - Codes Commercial Passed 07/22/2003
Correction
Resolved
07/22/2003
ROOF DRAINAGE SYSTEM
Correction
Resolved
07/22/2003
STAIR & RAMP TRANSITIONS TO GRADE
Correction
Resolved
07/22/2003
OCCUPANCY STATUS ISSUE COFO
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home