Permit Application Status

B0202103


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0202103
Building Permit - Commercial
Certificate of Occupancy
RMT INVESTMENTS INC
CHANGE OF TENANT
CARLITOS RESTAURANT TENANT FINISH
12/02/2002
12/23/2002
06/21/2003
02/14/2003
Locations
Contacts
ANCONA CONSTRUCTION INC., Address:3367 S COCHISE AV  
RMT INVESTMENTS INC, Address:8951 S 126TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/31/2003 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- Clarify method of cooking food. If appliances that cook food producing grease laden vapors are being used. A ventilation hood and supression system are required.
Correction

A grease/solids interceptor must be shown with an indication of size, type and detail of the interceptor, picking up the waste from the triple bowl sink.
Correction

A note should be provided indicating a Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior to any point of use isolating tenant from the rest of the shell building.
Correction

Backflow prevention assemblys (RPZ's) will be placed inside the building on the domestic water service line prior to the Ice Machine and the Carbonated Beverage dispenser.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - For the Health Department inspection contact Bob Thomas with the Jackson County Public Works Department at 816-881-4530. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Indicate the construction type per Chaper 6 of the 2000 International Building Code.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1003.2.2.5 - Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

CA - 2000 IBC 1209.1 - In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

CA - 2000 IBC 803.4 - Interior finish requirements based on group. Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.4 for the group and location designated.
Correction

CA - 2000 IBC 1108.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, the accessible counters shall also be dispersed.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IMC 403.3 - Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and the occupant load or other perameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less then the number determined from the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

CA - 2000 IPC 802.1.1 - Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Correction

CA - 2000 IPC 802.2.1 - The air gap between the indirect waste pipe and the flood level rim of the waste receptor shall be a minimum of twice the effective opening of the indirect waste pipe.
Correction

CA - 2000 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $32.00 $32.00 Paid 12/23/2002
24 BLDG Plan Check Fees $4.50 $4.50 Paid 12/23/2002
25 Electrical Permit Fee $45.00 $45.00 Paid 12/23/2002
25 Mechanical Permit Fees $15.00 $15.00 Paid 12/23/2002
25 Plumbing Permit Fees $27.00 $27.00 Paid 12/23/2002
89 Sewer Tap Fees $60.00 $60.00 Paid 12/23/2002
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 01/07/2003
Correction
Corrective Action Required
01/07/2003
Not As Plans SUBMIT CHANGES IN ELECTRICAL SYSTEM FOR APPROVAL
Correction
Corrective Action Required
01/07/2003
Not Inspected NORTH / SOUTH TENANT SEPARATION WALLS SHEET ROCKED - NO INSPECTION.
Correction
Resolved
01/07/2003
None OKAY TO SHEETROCK INTERIOR (KITCHEN) WALLS
Underslab Plumbing Inspection - Commercial Passed 01/09/2003
Correction
Resolved
01/09/2003
NONE: MODIFICATIONS TO UNDER-FLOOR DWV PIPING OK TO COVER TOILETS #1 & 2 SUBSTANTIALLY PERDRWG P-1
All Rough Inspection - Commercial Passed 02/07/2003
Correction
Resolved
02/07/2003
Not As Plans
Correction
Resolved
02/07/2003
Not Inspected
Correction
Resolved
02/07/2003
None
Occupancy Inspection - Codes Commercial Failed 02/11/2003
Correction
Corrective Action Required
02/11/2003
AIR GAP BETWEEN INDIRECT WASTE LINES AND WASTE RECEPTORS NOT PROVIDED PER NOTE 13 ON DRWG P1
Correction
Partial Correction
02/11/2003
Receive Fire Department approval
Correction
Corrective Action Required
02/11/2003
Receive Water Utilities Approval BACKFLOW PREVENTION PER NOTE 14 DRWG P1
Correction
Corrective Action Required
02/11/2003
ELECTRICAL CIRCUIT BREAKERS IRC E36O6.2. EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS IMPROPERLY LABELED SERVICE PANEL
Correction
Corrective Action Required
02/11/2003
OCCUPANCY STATUS DO NOT OCCUPY UNTIL APPROVED
Occupancy Inspection - Codes Commercial Passed 02/13/2003
Correction
Resolved
02/13/2003
AIR GAP BETWEEN INDIRECT WASTE LINES AND WASTE RECEPTORS
Correction
Resolved
02/13/2003
Receive Fire Department approval
Correction
Resolved
02/13/2003
Receive Water Utilities Approval
Correction
Resolved
02/13/2003
ELECTRICAL CIRCUIT BREAKERS
Correction
Resolved
02/13/2003
OCCUPANCY STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home