Permit Application Status

B0202088


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0202088
Building Permit - Commercial
Certificate of Occupancy
REORGANIZED SCHOOL DIST NO 7
NEW COMMERCIAL
FOOTBALL/SOCCER STADIUM
11/27/2002
04/22/2003
10/19/2003
01/20/2005
Locations
Contacts
DLR GROUP, Address:7421 W. 129 STREET, SUITE 100  
DLR GROUP, Address:7421 W. 129 STREET, SUITE 100  
REORGANIZED SCHOOL DIST NO 7, Address:301 NE Tudor Rd, Phone:(816) 986-1000  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/26/2003 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - I am unable to locate a code plan for this structure.
Correction

CA - Details were not provided on the bleachers at the time of permit application.
Correction

CA - Information on the engineered truss system was not provided at the time of permit application.
Correction

CA - Information on the differnt wall types for this building was not provided with the plans.
Correction

CA - 2000 IBC 1107.2 - Assembly area seating. Assembly areas with fixed seating shall comply with Sections 1107.2.1 through 1107.2.4.1. Dining areas shall comply with Sections 1107.2.5 through 1107.2.5.2.
Correction

CA - 2000 IBC 1108.2.1 - Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an accessible unisex toilet room shall be provided where an aggregate of six or more male and female water closets are required. In buildings of mixed occupancy, only those water closets requried for the assembly or mercantile occupancy shall be used to determine the unisex toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible unisex bathing room shall be provided. Fixtures located within unisex toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy.
Correction

CA - The electrical and plumbing plans are not complete.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- 1003.2.10.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department- Provide a complete set of stamped plans for review and approval.
Correction

Fire department- Provide a set of stamped plans.
Correction

CA - Jackson County Health Department - Hand sinks are required in the concession areas.
Correction

Fire Department- Fire lanes shall also be marked in accordance with IFC Section D103.6.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1005.3.2 - Vertical exit enclosures. Interior exit stairways shall be enclosed. Vertical exit enclosures four stories or more shall be 2-hour fire-resistance rated. Vertical exit enclosures less than fiyr stories shall be 1-hour fire-resistance rated. The number of stories shall be computed as all floor levels, including besements but excluding mezzanines. An exit enclosure shall not be used for any purpose other than means of egress. Vertical exit enclosures shall be constructed as fire barriers in accordance with Section 706. The enclosure requirements for interior exit ramps shall be the same for interior exit stairways.
Correction

CA - 2000 IBC 1003.3.3.11.5 - Handrail extension. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight. Where handrails are not continous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.2.12 - Guards. Guards shall be located along open-sided walking surfaces, mezzanines, industrial equipment platforms, stairways, ramps and landings which are located more than 30 inches above the floor or grade below. Guards shall be adequate in strength and attachment in accordance with Section 1607.7. Guards shall also be located along glazed sides of stairways, ramps and landings that are located more than 30 inches above the floor or grade below where the glazing provided does not meet the strength and attachment requirements in Section 1607.7. In addition, guards are required at retaining walls over 30 inches above grade when walking surfaces are within 10 feet of the high side of the retaining wall. (As amended in the Lee's Summit Code of Ordinances, Chapter 7, Section 7-216.)
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

CA - 2000 IBC 1003.3.4.9 - Guards. Guards shall be provided where required by Section 1003.2.12 and shall be constructed in accordance with Section 1003.2.12.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

No by-pass piping can be placed around or before the backflow prevention assemblies. Backflow prevention assemblies may be placed in parallel. Should you have any questions relating to backflow prevention with the respect to type of device, placement and detail of vault contact Jeff Walters, Backflow Prevention Coordinator, Water Utilities Department at 816-969-7636.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,802.00 $1,802.00 Paid 04/22/2003
24 BLDG Plan Check Fees $50.00 $50.00 Paid 04/22/2003
25 Electrical Permit Fee $164.00 $164.00 Paid 04/22/2003
25 Mechanical Permit Fees $148.50 $148.50 Paid 04/22/2003
25 Plumbing Permit Fees $280.50 $280.50 Paid 04/22/2003
89 Sewer Tap Fees $1,830.00 $1,830.00 Paid 04/22/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 07/24/2003
Correction
Resolved
07/24/2003
None DWV APPROVED.
Miscellaneous Inspection Not Ready 02/27/2004
Electrical Service Inspection Passed 04/23/2004
Correction
Resolved
04/23/2004
None
Rough Electrical Inspection - Commercial Passed 04/23/2004
Correction
Resolved
04/23/2004
None MAIN GEAR FOR STADIUM APPROVED. TRANSFORMER APPROVED. 2ND LEVEL PRESS BOX
Electrical Service Inspection Passed 06/14/2004
Correction
Resolved
06/14/2004
None RELEASE SERVICE FOR BASEBALL AREA.
Gas Piping Inspection - Commercial Passed 06/29/2004
Correction
Resolved
06/29/2004
None
Gas Service Inspection - Commercial Passed 06/29/2004
Correction
Resolved
06/29/2004
Gas Test Pressure (IRC) 60 POUNDS HELD 30 MIN.
Above Ceiling Inspection Failed 06/29/2004
Correction
Corrective Action Required
06/29/2004
ROOD TRUSS INSTALLATION PROVIDE DOCUMENTATION FOR APPROVAL OF INSTALLATION. TRUSS DESIGN CALLS FOR 2 3*6 TOP PLATES FOR BEARING OF TRUSS. 1 2*6INSTALLED. DOES NOT ALLOW FOR PROPER NAILING OF FASTNERS AT TOP PLATE.
Correction
Corrective Action Required
06/29/2004
TRUSS NOTCHING BOTTOM CHORD NOTCHED FOR ELECTRICAL CONDUIT IN PRESS BOX AREA AT WEST WALL. PROVIDE DOCUMENTATION FOR APPROVAL. DO NOT COVER.
Above Ceiling Inspection Partial 07/06/2004
Correction
Resolved
07/06/2004
ROOD TRUSS INSTALLATION APPROVED PER REPORT FROM TRUSS SUPPLIER. OKAY TO COVER LOWER AREA.
Correction
Partial Correction
07/06/2004
TRUSS NOTCHING REPORT FROM TRUSS SUPPLIER APPROVED. NEED TO INSPECT FIX PRIOR TO COVERING ATTIC AREA.
Above Ceiling Inspection Passed 07/09/2004
Correction
Resolved
07/09/2004
TRUSS NOTCHING
Above Ceiling Inspection Passed 08/12/2004
Correction
Resolved
08/12/2004
FIRST FLOOR MIDDLE TILE CEILING ON 1ST FLOOR MIDDLE SECTION OKAY TO DROP.
Occupancy Inspection - Codes Commercial Failed 10/07/2004
Correction
Corrective Action Required
10/07/2004
Receive Planning & Development Approval Under cover with High School Permit
Correction
Corrective Action Required
10/07/2004
Receive Fire Department approval Under Cover with High School Permit
Correction
Corrective Action Required
10/07/2004
Receive Public Works Approval Under cover with High School Permit
Correction
Resolved
10/07/2004
Text Occupancy inspection performed with high school building
Occupancy Inspection - Codes Commercial Passed 01/19/2005
Correction
Resolved
01/19/2005
Receive Planning & Development Approval
Correction
Resolved
01/19/2005
Receive Fire Department approval
Correction
Resolved
01/19/2005
Receive Public Works Approval
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home