Permit Application Status

B0201771


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0201771
Building Permit - Commercial
Certificate of Occupancy
OADES BROTHERS LLC
NEW COMMERCIAL
AUTOMOTIVE SERVICE CENTER BUILDING
10/08/2002
01/14/2003
07/13/2003
09/23/2003
Locations
Contacts
A.L. HUBER, Address:10770 EL MONTE  
JANTSCH SLAGGIE ARCHITECTS, Address:218 DELAWARE  
OADES BROTHERS LLC, Address:3408 W 122ND ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/06/2003 10/29/2010
Correction

Fire Department; The FDC shall be a 4" STORZ connection.
Correction

Fire Department; The structure shall be supplied with horn/strobe occupant notification located throughout the structure. The horn/strobes shall activate upon water flow from the sprinkler system equal to a single sprinkler head activation. IFC 903.4.2
Correction

Fire Department; A horn/strobe alarm device shall be located on the exterior of the building directly above the FDC. This device shall activate upon water flow from the fire sprinkler system equal to a single head activation.
Correction

Fire Department; A Haz-Mat application needs to be completed to determine if a Haz-Mat permit is required. Obtain application through the L.S. Fire Department.
Correction

Fire Department; Information and cut sheets needed on the oil storage tanks located in the building.
Correction

CA - 2000 IBC 714.3.8 - Fire-resistance-rated glazing. Fire-resistance-rated glazing tested as part of a fire-resistance-rated wall assembly in accordance with ASTM E 119 shall be permitted where the required fire-resistance rating of the wall exceeds 1 hour in applications set forth in Sections 714.3.6 and 714.3.6.1 and shall have a fire-resistance rating equal to the fire-resistance rating required for the wall. The window area size limitations set forth in Section 714.3.6.2 shall not apply to such fire-resistance -rated assemblies tested in accordance with ASTM E 119.
Correction

CA - The Codes Administration Department and Fire Department have determined that this is a repair garage which falls under the occupancy type S-1.
Correction

CA - 2000 IBC 406.6.2 - Mixed occupancy. A repair garage shall not be located within, or attached to, a building occupied for other purpose, unless separated from the other occupancies as prescribed in Section 302.3.3. Such separation shall be continuous and unpierced, except for doors leading to salesrooms, or offices, operated in connection with such garages, and provided such openings are equipped with self-closing fire doors conforming to the requirements of Chapter 7.
Correction

CA - 2000 IBC 1108.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, the accessible counters shall also be dispersed.
Correction

CA - Details on the roof drainage piping are not provided.
Correction

CA - The materials to be used in the plumbing system are not indicated.
Correction

CA - 2000 IMC 403.3 - Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and the occupant load or other perameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less then the number determined from the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

CA - Compliance with Article 511 - Commercial Garages, Repair and Storage is not indicated on the plans.
Correction

Fire Department; per revised ordinance #5192 of the IFC Section 903.2.10.1 Repair Garages greater than 3000 sq. ft. shall be provided with an automatic fire sprinkler system.
Correction

Fire Department; The automatic fire sprinkler system shall conform to NFPA 13 standards for high hazards commodities per IFC 2303.6.
Correction

Fire Department; a fire hydrant needs to be placed within 50 feet of the FDC for the fire sprinkler system.
Correction

CA - The City will not issue any type of certificate of occupancy until until all itemes required for the development have been completed and a letter of substaintal completion has been issued.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

The location of the Fire Department Connection (FDC) must be shown on the site plan.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. IFC 1003.2.10.4 Exit sign illumination shall also be in accordance with the IBC.
Correction

Fire Department; Egress from a room or space shall not pass through adjoining or interven-ing rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not a high-hazard occupancy; and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit access shall not pass though a room which can be locked to prevent egress. IFC 1004.2.3
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department: Fire detection, alarm and extinguishing systems shall be maintained in an op-erative condition at all times, and shall be replaced or repaired where defective.
Correction

Fire Department; All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised when the number of sprinkler heads are 20 (twenty) or greater.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IMC 304.8 - Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade or shall be suspended a minimum of 6 inches (152 mm) aboave adjoining grade.
Correction

CA - 2000 IPC 308.5 - Pipe shall be supported in accordance with Table 308.5.
Correction

CA - 2000 IPC 312.1 - Required tests. The permit holder shall make the applicable test prescribed in Sections 312.2 through 312.9 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the code official when the plumbing work is ready for tests. The equipment, material, power and labor necessary for the inspection and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. All plumbing system piping shall be tested with either water or air. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be submitted to final tests. The code official shall require the removal of any cleanouts if necessary to ascertain if the pressure has reached all parts of the system. Note: Testing of the plumbing system is not required to be witnessed by the Codes Administration Staff with the exception of gas piping.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO Chapter 7, Section 7-803 - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following; Exception: The Building Official may approve a decreased R-value for building exterior walls provided the space is not occupied by employees and is associated with storage/warehouse or manufactoring. a) Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or openings or approved penetrations nor does it apply to unfinished basement concrete walls. b) Floor assemblies forming portions of a building envelope shall meet or exceed a R factor rating of 19. Exception: Concrete floor in contact with the earth need not be insulated. c) Roof assemblies forming portions of a building envelope shall meet or exceed an R factor of 19.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - 2000 IBC 1704.1 - Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner's agent shall employ one or more special inspectors to provide inspections during construction on the types of work listed under Section 1704. The special inspecor shall be a qualified person who shall demonstrate competence, to the satisfaction of the building official, for inspection of the the particular type of construction or operation requiring special inspection.
Correction

CA - 2000 IBC 1704.1.2 - Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and the registered design professional in responsible charge prior to the completion of that phase of the work. A final report of inspections documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted periodically at a frequency agreed upon by the permit applicant and the building official prior to the start of work.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

A double check detector check valve assembly is required on the fire service line.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

A note should be provided indicating a Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior to any point of use.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,952.00 $1,952.00 Paid 01/14/2003
24 BLDG Plan Check Fees $52.50 $52.50 Paid 01/14/2003
25 Electrical Permit Fee $270.51 $270.51 Paid 01/14/2003
25 Mechanical Permit Fees $171.00 $171.00 Paid 01/14/2003
25 Plumbing Permit Fees $89.00 $89.00 Paid 01/14/2003
84 Water Meters $200.00 $200.00 Paid 01/14/2003
85 Water Taps $5,468.00 $5,468.00 Paid 01/14/2003
89 Sewer Tap Fees $300.00 $300.00 Paid 01/14/2003
Right of Way Permit $35.00 $35.00 Paid 01/14/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 02/03/2003
Correction
Partial Correction
02/03/2003
None SOUTH ASPECT 25 FT TO EAST WEST ASPECT NORTH ASPECT EAST ASPECT 50 FT SOUTH 3 NO 5 T/B APPROVED
Footing Inspection - Commercial Passed 02/04/2003
Correction
Resolved
02/04/2003
None
Water Service Inspection Partial 02/11/2003
Correction
Partial Correction
02/11/2003
INITIAL PARTIAL SERVICE INSTALL OK TO COVER WHEN READY FROM BUILDING ENTRY TO 60' SOUTH PER DRWG C2
Water Service Inspection Passed 02/12/2003
Correction
Resolved
02/12/2003
FINAL PARTIAL SERVICE INSTALL METER/WELL INSTALLED TAP COMPLETED
Correction
Resolved
02/12/2003
INITIAL PARTIAL SERVICE INSTALL OK TO COVER WHEN READY FROM BUILDING ENTRY TO 60' SOUTH PER DRWG C2
Sewer Service Inspection Partial 02/13/2003
Correction
Partial Correction
02/13/2003
PARTIAL SAN SEWER SVC FROM TIE-IN AT MAIN NE TO POINT ONLINE W/ SOUTH B/L
Erosion Control Inspection Residential Passed 02/13/2003
Correction
Resolved
02/13/2003
Erosion Control THROUGH FINAL INSPECTION KEEP STREET CLEAN MAINTAIN EROSION CONTROL
Sewer Service Inspection Passed 02/18/2003
Correction
Resolved
02/18/2003
NONE > SANITARY SEWER SERVICE LINE COMPLETE C.O. TO BE INSTALLED WHEN OIL SEPARATOR IS CONNECTED TO OIL SEPARATOR AND S BLDG ENTRY
Correction
Resolved
02/18/2003
PARTIAL SAN SEWER SVC FROM TIE-IN AT MAIN NE TO POINT ONLINE W/ SOUTH B/L
Sewer Service Inspection Passed 03/10/2003
Correction
Resolved
03/10/2003
RELOCATION RE-CONNECTS APPROVED IN ACCORDANCE W/ EARLIER PW DIRECTION TO CONTRACTOR. TWO LOCATIONS S OF S BLDG WALL
Sewer Service Inspection Passed 03/11/2003
Correction
Resolved
03/11/2003
SANITARY SEWER PRESSURE TEST HELD STEADY @ 6 PSI APPROVED
Electrical Service Inspection Partial 03/11/2003
Correction
Partial Correction
03/11/2003
TEMPORARY ELECTRICAL SERVICE APPROVED RELEASE TEMPORARY SERVICE
Underslab Plumbing Inspection - Commercial Passed 04/09/2003
Underslab Electrical Inspection - Commercial Passed 04/10/2003
Correction
Resolved
04/10/2003
PVC CONDUIT OK TO COVER WHEN READY S 1/3 OF BLDG OFFICE/STORAGE AREA
Underground Electrical Inspection - Commercial Failed 04/22/2003
Correction
Corrective Action Required
04/22/2003
COVERED PRIOR TO INSPECTION SUBMIT LETTER ON E.C. LETTERHEAD SIGNED BY COMPANY OFFICER CERTIFYING: SPECIFIC MATERIALS, METHODS & LOCATION OF INSTALLATION (REFER TO PERMIT DRAWINGS AND DESCRIBE ANY VARIATIONS THEREFROM). CERTIFY COMPLIANCE WITH 1999 N.E.C. BURIED SERVICE CONDUIT REQUIRES DOCUMENTATION
All Rough Inspection - Commercial Partial 05/06/2003
Correction
Partial Correction
05/06/2003
IN-WALL SYSTEMS PLUMBING CONTR COMPLETE PLACING SHIELD PLATES @ RR WALLS OFFICE AREA OK TO COVER AFTER
Underground Electrical Inspection - Commercial Passed 05/09/2003
Correction
Resolved
05/09/2003
COVERED PRIOR TO INSPECTION TWO 4" PVC CONDUITS; ONE FOR SERVICE & ONE SPARE APPROVED PER SCHULTZ ELEC LETTER DTD 4/22/03
Rated Assembly Inspection Partial 05/09/2003
Correction
Partial Correction
05/09/2003
FIRE-RATED PARTITION BOTH FACES OK TO COVER BETWEEN SERVICE & OFFICE 1ST LAYER 5/8" TYPE X GWB
Rated Assembly Inspection Failed 05/13/2003
Correction
Corrective Action Required
05/13/2003
FIRE BARRIER WALL BETWEEN SERVICE & OFFICE WALL DESIGN #334 2ND LAYER DRYWALL NON-CONFORMING TO UL
Rated Assembly Inspection Partial 05/14/2003
Correction
Partial Correction
05/14/2003
FIRE BARRIER WALL BETWEEN SERVICE & OFFICE OKMTO TAPE & MUD. NOTE UL WALL DESIGN #334 REQUIRES GYP BOARD COMPOUND COATING ON JOINTS AND ON SCREW/NAIL HEADS. 2ND LAYER DRYWALL APPROVED
Electrical Service Inspection Passed 05/15/2003
Correction
Resolved
05/15/2003
TEMPORARY ELECTRICAL SERVICE
Correction
Resolved
05/15/2003
NONE > APPROVED GEC CONNECTION TO WATER SERVICE LINE TO BE COMPLETED TODAY PRIOR TO SERVICE ACTIVATION. SERVICE PANEL INTERIORS TO BE INSPECTED WHEN COMPLETED. SERVICE TO BE UTILIZED FOR TEMP POWER & LIGHTING FOR PRESENT. RELEASE SERVICE 400 AMPS PER DRWG E2
Above Ceiling Inspection Partial 05/23/2003
Correction
Partial Correction
05/23/2003
ABOVE-CEILING SYSTEMS TWO ELECT J.B.'s OPEN SALES AREA (SE RM) OK TO COVER EXCEPT WHERE
Gas Piping Inspection - Commercial Passed 05/30/2003
Gas Service Inspection - Commercial Passed 05/30/2003
Correction
Resolved
05/30/2003
NONE > PRESSURE TEST HELD STEADY RATED OPERATING PRESSURES NOT TO EXCEED 4 PSIG AT >= 10 PSI FOR > 30 MIN RELEASE GAS SERVICE
Underground Electrical Inspection - Commercial Passed 05/30/2003
Correction
Resolved
05/30/2003
COVERED PRIOR TO INSPECTION
Rated Assembly Inspection Passed 05/30/2003
Correction
Resolved
05/30/2003
FIRE BARRIER WALL BETWEEN SERVICE & OFFICE
All Rough Inspection - Commercial Passed 05/30/2003
Correction
Resolved
05/30/2003
IN-WALL SYSTEMS
Above Ceiling Inspection Passed 06/16/2003
Correction
Resolved
06/16/2003
ABOVE-CEILING SYSTEMS
Occupancy Inspection - Codes Commercial Failed 06/16/2003
Correction
Corrective Action Required
06/16/2003
FIRE-BLOCKING OF DEMISING WALL ROOF DECK FLUTES + PENETRATIONS @ MEZZANINE
Correction
Corrective Action Required
06/16/2003
Receive Water Utilities Approval B/F TEST RESULTS FOR DOMESTIC & IRRIGATION SVC
Correction
Corrective Action Required
06/16/2003
Receive Public Works Approval BILL LYON 969-7324 EROSION CONTROL @ W P/L
Correction
Corrective Action Required
06/16/2003
Receive Planning & Development Approval 969-7796 OR 969-7317 CONTACT TOM SCANNELL WHEN LANDSCAPING DONE
Correction
Corrective Action Required
06/16/2003
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Failed 06/18/2003
Correction
Corrective Action Required
06/18/2003
Receive Planning & Development Approval WHEN LANDSCAPING & DUMPSTER ENCLOSURE ARE COMPLETED. IF QUESTIONS, CONTACT TOM SCANNELL 969-7796 OR 969-7317 SEE LIST PROVIDED REQUEST TCO EXTENSION
Correction
Partial Correction
06/18/2003
Receive Public Works Approval AT DOUGLAS STREET PER BILL LYON 6/18/03 COMPLETE IMPROVEMENTS
Correction
Resolved
06/18/2003
Receive Water Utilities Approval PER J WALTERS 6/18/03
Correction
Resolved
06/18/2003
FIRE-BLOCKING OF DEMISING WALL
Correction
Partial Correction
06/18/2003
OCCUPANCY STATUS SEE TEMPORARY OCCUPANCY
Correction
Resolved
06/18/2003
Receive Fire Department approval PER J EDEN 6/18/03
Occupancy Inspection - Codes Commercial Partial 06/26/2003
Correction
Partial Correction
06/26/2003
Receive Planning & Development Approval ACCEPTED BY CODES ADMINISTRATION ON BEHALF OF PLANNING & DEVELOPMENT NOT IN ATTENDANCE. IF QUESTIONS REGARDING CORRECTION OF EXTERIOR WALL LIGHTS CONTACT TOM SCANNELL @ 969-7796 OR 969-7317 LANDSCAPING & DUMPSTER ENCLOSURE
Correction
Partial Correction
06/26/2003
OCCUPANCY STATUS SEE TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Passed 09/22/2003
Correction
Resolved
09/22/2003
Receive Planning & Development Approval
Correction
Resolved
09/22/2003
Receive Public Works Approval PER K INGHAM 9/12/03 LTR
Correction
Resolved
09/22/2003
OCCUPANCY STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home