Summary
B0201751
Building Permit - Commercial
Certificate of Occupancy
RAZMJZ DEVELOPMENT LLC
NEW COMMERCIAL
RESID. TO COMMERCIAL
10/04/2002
11/04/2002
05/03/2003
05/29/2003
Locations
Contacts
ARCHITECTURE, GRAPHICS, MANAGEMENT & PLANNING, Address:226 SE DOUGLAS, SUITE 204  
MARIAN ZATIC, Address:604 SW JEFFERSON ST  
RAZMJZ DEVELOPMENT LLC, Address:604 SW JEFFERSON  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/02/2003 10/29/2010
Correction

CA - ICC/ANSI A117.1-1998 603.3 - Mirrors shall be mounted with the bottom edge of the reflecting surface 40 inches maximum above the floor or ground.
Correction

CA - The plans indicate that the occupancy type is an E but the plans show two toddler rooms.
Correction

CA - 2000 IBC 903.2.5 - Group I An automatic sprinkler system shall be provided throughout buildings with a Group I occupancy.
Correction

CA - A site plan was not provided with the building permit application.
Correction

CA - A door schedule was not included with the plans.
Correction

CA - The loads were not included with the plans.
Correction

CA - A front counter detail is provided but it is not located on the floor plans.
Correction

CA - A bathtub/shower, drinking fountain and service sink are not shown on the plans as required by Table 403.1 of the 2000 International Plumbing Code.
Correction

Fire Department- IFC Sec. 903.2.5 Group I. An automatic sprinkler system shall be provided throughout buildings with a Group I fire area.
Correction

Fire Departmen- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The holder of this permit agrees and understands that only persons authorized per LSCO 7-130 are permitted to perform electrical, plumbing or mechanical work authorized by this permit.
Correction

CA - 2000 IBC 1003.3.3.3 - Stair riser heights shall be 7 inches maximum and 4 inches minimum. Stair tread depths shall be 11 inches minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at right angle to the tread's leading edge.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

CA - 2000 IBC 1003.3.3.11 - Handrails. Stairways shall have handrails on each side. Handrails shall be adequate in strength and attachment in accordance with Section 1607.7.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.3.1.5 - Landings at doors. Landings shall have a width not less than the width of the stairway or the width of the door, whichever is the greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches.
Correction

CA - 2000 IBC 1003.2.12.1 - Guard height. Guards shall form a protective barrier not less than 42 inches high, measured vertically above the leading edge of the tread, adjacent walking surface or adjacent seatboard.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

CA - 2000 IBC 1003.2.7 - Elevation change. Where changes in elevation of less than 12 inches (305 mm) exist in the means of egress, sloped surfaces shall be used. Where the slope is greater than one unit vertical in 20 units horizontal (5 percent slope), ramps complying with Section 1003.3.4 shall be used. Where the difference in elevation is 6 inches (152 mm) or less, the ramp shall be equipped with either handrails or floor finish materials that contrast with adjacent floor finish materials. (Exceptions available)
Correction

CA - 2000 IBC 1003.2.10.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30,480 mm) from the nearest visible exit sign.
Correction

CA - 2000 IBC 1003.2.11.2 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency system shall automatically illuminate all of the follow areas: 1. Exit access corridors, passageways, and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways located in buildings required to have two or more exits. 3. Interior exit discharge elements, as permitted in Section 1006.1, in buildings required to have two or more exits. 4. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - 2000 IMC 403.3 - Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and the occupant load or other perameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less then the number determined from the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

CA - 2000 IMC 507.2.2 - Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I or II hoods as required for the type of appliances and processes in accordance with Sections 507.2 and 507.2.1.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly will be placed inside the building on the domestic water service line prior to any point of use.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
25 Electrical Permit Fee $30.00 $30.00 Paid 11/04/2002
25 Mechanical Permit Fees $24.00 $24.00 Paid 11/04/2002
25 Plumbing Permit Fees $41.00 $41.00 Paid 11/04/2002
25 Electrical Permit Fee $15.00 $15.00 Paid 03/28/2003
25 Electrical Permit Fee $5.00 $5.00 Paid 04/25/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Codes Commercial Failed 11/22/2002
Correction
Corrective Action Required
11/22/2002
SEE BELOW SUBMIT BACKLFOW TEST REPORT. OCCUPANCY INSPECTION ONLY PERFORMED FOR MAIN LEVEL. BASEMENT LEVEL STILL UNDER CONSTRUCTION AS WELL AS PARKING LOT.
Correction
Corrective Action Required
11/22/2002
SEE BELOW 1. COMPLETE RAMP AT FRONT DOOR (JEFFERSON). HANDRAILS REQUIRED AT RAMP IS RISE IS OVER 6 INCHES. 2. INSTALL HANDRAIL AT EXTERIOR STEPS (SE CORNER) AND AT STEPS LEADING INTO OFFICE. 3. SUBMIT LETTER OF CREDIT FOR LICENSE TAX PAYMENT
Occupancy Inspection - Codes Commercial Failed 12/06/2002
Correction
Corrective Action Required
12/06/2002
SEE BELOW SUBMIT BACKLFOW TEST REPORT. OCCUPANCY INSPECTION ONLY PERFORMED FOR MAIN LEVEL. BASEMENT LEVEL STILL UNDER CONSTRUCTION AS WELL AS PARKING LOT.
Correction
Corrective Action Required
12/06/2002
SEE BELOW 1. COMPLETE RAMP AT FRONT DOOR (JEFFERSON). HANDRAILS REQUIRED AT RAMP IS RISE IS OVER 6 INCHES. RAMP STILL UNDER CONSTRUCTION.
Electrical Service Inspection Failed 04/24/2003
Correction
Corrective Action Required
04/24/2003
DEDICATED ELECTRICAL SPACE NEC 110-26(f); IRC E3305.3 PIPING SYSTEMS ABOVE SERVICE PANEL
Electrical Service Inspection Passed 04/25/2003
Correction
Resolved
04/25/2003
DEDICATED ELECTRICAL SPACE
Correction
Resolved
04/25/2003
NONE > APPROVED RELEASE SERVICE 200 AMP
Occupancy Inspection - Codes Commercial Failed 05/20/2003
Correction
Partial Correction
05/20/2003
SEE BELOW
Correction
Partial Correction
05/20/2003
SEE BELOW
Correction
Corrective Action Required
05/20/2003
Receive Water Utilities Approval BACKLFLOW TEST REPORT SUBMIT TO WATER UTILITIES
Correction
Corrective Action Required
05/20/2003
Receive Planning & Development Approval PARKING LOT AND OTHER SITE ELEMENTS
Correction
Corrective Action Required
05/20/2003
Receive Fire Department approval
Correction
Resolved
05/20/2003
HANDRAIL AT DECK STAIR DUE TO PRIMARY USE BY CHILDREN < 34" ABOVE STAIR TREAD ALLOWED AS EXCEPTION
Correction
Resolved
05/20/2003
LANDING AT DECK STAIR OK IF/WHEN SURROUNDING GRADE IS BROUGHT TO ELEVATION OF CONCRETE LANDING. NOT 36" IN DIRECTION OF TRAVEL
Correction
Corrective Action Required
05/20/2003
LABELING OF ELECTRICAL CIRCUIT BREAKERS IRC E36O6.2. EACH BREAKER MUST BE LABELED AS TO ROOM(S) OR EQUIPMENT SERVED. NO DITTO MARKS OR CONTINUATION SYMBOLS INCOMPLETE SERVICE PANEL
Occupancy Inspection - Codes Commercial Failed 05/27/2003
Correction
Resolved
05/27/2003
SEE BELOW
Correction
Resolved
05/27/2003
SEE BELOW
Correction
Resolved
05/27/2003
Receive Planning & Development Approval SITE INSPECTION BY CA
Correction
Resolved
05/27/2003
Receive Fire Department approval
Correction
Resolved
05/27/2003
LABELING OF ELECTRICAL CIRCUIT BREAKERS
Correction
Corrective Action Required
05/27/2003
HANDICAPPED PARKING SIGN NOT INSTALLED PER SITE DRWG 1/1
Occupancy Inspection - Codes Commercial Passed 05/28/2003
Correction
Resolved
05/28/2003
Receive Water Utilities Approval PER J WALTERS 5/28/03
Correction
Resolved
05/28/2003
HANDICAPPED PARKING SIGN
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home