Summary
B0201545
Building Permit - Commercial
Certificate of Occupancy
DOUGLAS STATION SHOPPING CENTER LLC
NEW SHELL BUILDING
RETAIL SHELL
09/05/2002
02/10/2003
08/09/2003
12/23/2003
Locations
Contacts
CAPITAL CONSTRUCTION SERVICES LLC, Address:1725 NE RICE RD  
DOUGLAS STATION SHOPPING CENTER LLC, Address:1725 NE RICE RD  
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/04/2003 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - I am not able to locate details on the roof drains, roof drain piping and scuppers.
Correction

CA - The hold harmless agreement included with the application is not notorized.
Correction

CA - A soils report was not included with the permit application.
Correction

CA - Details on the construction of the retaining wall were not provided with application.
Correction

CA - The truss design package was not included with the permit application.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- The backflow detail on Drawing C3 shows a fire department connection of of the private main. This is believed to be a mistake and should have been a fire hydrant detail. The FDC in this configuration would not work. Resumit drawing.
Correction

Fire Department- Confirm size of the private fire main with Public works Engineering. It is not clear what size the line will be and where line size changes.
Correction

CA - The City will not issue any type of certificate of occupancy until until all itemes required for the development have been completed and a letter of substaintal completion has been issued.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1704.1 - Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner's agent shall employ one or more special inspectors to provide inspections during construction on the types of work listed under Section 1704. The special inspecor shall be a qualified person who shall demonstrate competence, to the satisfaction of the building official, for inspection of the the particular type of construction or operation requiring special inspection.
Correction

CA - 2000 IBC 1704.1.2 - Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and the registered design professional in responsible charge prior to the completion of that phase of the work. A final report of inspections documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted periodically at a frequency agreed upon by the permit applicant and the building official prior to the start of work.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

Fire Department; Vehicle access for fire fighting shall be provided to all construction or demolition sites. Vehicle access shall be provided to within 100 feet of temporary or permanent fire department connections. Vehicle access shall be provided by either temporary or permanent roads, capable of supporting vehicle loading under all weather conditions.
Correction

Fire Department; Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Combustible debris, waste materials and trash shall not be burned on site.
Correction

Fire Derpartment; When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO Chapter 7, Section 7-803 - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following; Exception: The Building Official may approve a decreased R-value for building exterior walls provided the space is not occupied by employees and is associated with storage/warehouse or manufactoring. a) Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or openings or approved penetrations nor does it apply to unfinished basement concrete walls. b) Floor assemblies forming portions of a building envelope shall meet or exceed a R factor rating of 19. Exception: Concrete floor in contact with the earth need not be insulated. c) Roof assemblies forming portions of a building envelope shall meet or exceed an R factor of 19.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $3,290.00 $3,290.00 Paid 02/10/2003
24 BLDG Plan Check Fees $74.80 $74.80 Paid 02/10/2003
25 Electrical Permit Fee $200.00 $200.00 Paid 02/10/2003
25 Mechanical Permit Fees $355.00 $355.00 Paid 02/10/2003
25 Plumbing Permit Fees $38.00 $38.00 Paid 02/10/2003
84 Water Meters $625.00 $625.00 Paid 07/24/2003
85 Water Taps $5,468.00 $5,468.00 Paid 07/24/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Passed 02/12/2003
Correction
Resolved
02/12/2003
TEMPORARY ELECTRICAL SERVICE APPROVED RELEASE SERVICE
Sewer Service Inspection Passed 03/24/2003
Correction
Resolved
03/24/2003
NONE > SEWER SERVICE APPROVED PER PERMIT PRINT C3
Footing Inspection - Commercial Partial 04/01/2003
Correction
Partial Correction
04/01/2003
PERIMETER GRADE BEAM PARTIAL ON (1) FROM (A) TO (B) ON (A) FROM (1) TO (9) ON (D/C) FRM (1) TO (6.5)
Footing Inspection - Commercial Partial 04/03/2003
Correction
Resolved
04/03/2003
PERIMETER GRADE BEAM PARTIAL ON (1) FROM (A) TO (B) ON (A) FROM (1) TO (9) ON (D/C) FRM (1) TO (6.5)
Correction
Partial Correction
04/03/2003
PERIMETER FOOTING/GRADE BEAM PARTIAL (C) FROM (6.5) TO (10.5) (10) FROM (A) TO (B) (A) FROM (8.5) TO (11.8) APPROVED OK TO POUR WHEN READY
Footing Inspection - Commercial Partial 04/10/2003
Correction
Partial Correction
04/10/2003
PERIMETER GRADE BEAM/FOOTING - PARTIAL (14) & (20) EXTERIOR WALLS N OF (10) EXCEPT @ CROSSWALLS @
Footing Inspection - Commercial Partial 04/15/2003
Correction
Resolved
04/15/2003
PERIMETER FOOTING/GRADE BEAM PARTIAL (C) FROM (6.5) TO (10.5) (10) FROM (A) TO (B) (A) FROM (8.5) TO (11.8) APPROVED OK TO POUR WHEN READY
Correction
Resolved
04/15/2003
PERIMETER GRADE BEAM/FOOTING - PARTIAL (14) & (20) EXTERIOR WALLS N OF (10) EXCEPT @ CROSSWALLS @
Correction
Partial Correction
04/15/2003
None BALANCE OF GRADE BEAM BALANCE OF PERIMETER FROST FOOTING ALL INTERIOR COLUMN PILASTERS MINOR ADJUSTMENTS MADE BY SI
Footing Inspection - Commercial Partial 05/07/2003
Correction
Resolved
05/07/2003
None BALANCE OF GRADE BEAM BALANCE OF PERIMETER FROST FOOTING ALL INTERIOR COLUMN PILASTERS MINOR ADJUSTMENTS MADE BY SI
Correction
Partial Correction
05/07/2003
ROOF OVERHANG COLUMN FOOTINGS SOME HOLES REQUIRE CLEANING PRIOR TO POUR. APPROVED SUBJECT TO INSPECTION FOR BEARING CAPACITY AND OTHER ENGINEERING FACTORS BY SPECIAL INSPECTOR. ALONG E SIDE OF BLDG FROM (1) TO (22)
Underslab Plumbing Inspection - Commercial Passed 05/07/2003
Correction
Resolved
05/07/2003
UNDER-FLOOR DWV PIPING NEAR (A) FROM (1) TO (22) PER PERMIT PRINTS
Footing Inspection - Commercial Partial 05/12/2003
Correction
Resolved
05/12/2003
PERIMETER GRADE BEAM PARTIAL
Correction
Resolved
05/12/2003
PERIMETER FOOTING/GRADE BEAM PARTIAL
Correction
Resolved
05/12/2003
PERIMETER GRADE BEAM/FOOTING - PARTIAL
Correction
Resolved
05/12/2003
None
Correction
Resolved
05/12/2003
ROOF OVERHANG COLUMN FOOTINGS
Correction
Partial Correction
05/12/2003
COLUMN B/16 PREP APPROVED OK TO POUR WHEN READY
Underslab Electrical Inspection - Commercial Failed 05/12/2003
Correction
Corrective Action Required
05/12/2003
TWO HORIZONTAL SWEEPS OTHER APPROVED PER DRWG SHEETS ME1 & ME3 POINTED OUT TO E.C. DISTORTED > REPLACE
Underslab Electrical Inspection - Commercial Passed 05/13/2003
Correction
Resolved
05/13/2003
TWO HORIZONTAL SWEEPS DISTORTED > REPLACED
Underground Plumbing Inspection - Commercial Passed 05/13/2003
Correction
Resolved
05/13/2003
6" FIRE MAIN + 2" DOMESTIC WATER FIRE MAIN PRESSURE TEST WITNESSED AT 110 PSI STEADY FOR APPROX 50 MINUTES. CROSSING BLDG N OF (17) OK TO COVER WHEN READY
Underground Electrical Inspection - Commercial Partial 05/15/2003
Correction
Partial Correction
05/15/2003
SECONDARY ELECTRICAL SERVICE CONDUIT READY FOR CONCRETE ENCASEMENT. OK TO COVER WHEN READY. FROM BUILDING ENTRY TO NEAR XFORMER LOCATION
Retaining Wall Inspection Partial 05/19/2003
Correction
Partial Correction
05/19/2003
PROGRESS TO DATE APPROVED SUBSTANTIALLY PER PERMIT DRWG. ENSURE SOILS TEST RESULTS, PER NOTE ON PERMIT DRWG, ARE SUBMITTED TO INSPECTOR. 8 COURSES LAID @ W END + W 30' OF N ELEVATION
Retaining Wall Inspection Partial 05/30/2003
Correction
Resolved
05/30/2003
PROGRESS TO DATE APPROVED SUBSTANTIALLY PER PERMIT DRWG. ENSURE SOILS TEST RESULTS, PER NOTE ON PERMIT DRWG, ARE SUBMITTED TO INSPECTOR. 8 COURSES LAID @ W END + W 30' OF N ELEVATION
Correction
Partial Correction
05/30/2003
PROGRESS TO DATE APPROVED 3 COURSES HIGH @ ~105` E OF WEST WALL SUPT STATES CRUSHED STONE B/F HAS BEEN SUBSTITUTED FOR SPECIFIED CLAY DUE TO CHARACTERISTICS OF NATIVE CLAY MATERIAL. 9 COURSES LAID @ W END + W 30' OF N ELEVATION
Underslab Electrical Inspection - Commercial Not Ready 06/02/2003
Correction
Resolved
06/02/2003
TWO HORIZONTAL SWEEPS
Correction
Corrective Action Required
06/02/2003
READINESS FOR INSPECTION NO PERSONNEL ON-SITE PERMIT PRINTS NOT AVAILABLE (LOCKED)
Underground Electrical Inspection - Commercial Partial 06/03/2003
Correction
Resolved
06/03/2003
SECONDARY ELECTRICAL SERVICE CONDUIT READY FOR CONCRETE ENCASEMENT. OK TO COVER WHEN READY. FROM BUILDING ENTRY TO NEAR XFORMER LOCATION
Correction
Partial Correction
06/03/2003
U.G. CONDUIT TO PARKING LOT LIGHTS THEN N & S TO THREE OTHER POLE LOCATIONS AT TRAFFIC ISLANDS OK TO COVER WHEN READY 2" PVC FROM BLDG TO LIGHT POLE @ APEX ISLAND
Retaining Wall Inspection Partial 06/03/2003
Correction
Resolved
06/03/2003
PROGRESS TO DATE APPROVED 3 COURSES HIGH @ ~105` E OF WEST WALL SUPT STATES CRUSHED STONE B/F HAS BEEN SUBSTITUTED FOR SPECIFIED CLAY DUE TO CHARACTERISTICS OF NATIVE CLAY MATERIAL. 9 COURSES LAID @ W END + W 30' OF N ELEVATION
Correction
Partial Correction
06/03/2003
PROGRESS TO DATE APPROVED 5 COURSES HIGH @ ~105` E OF WEST WALL SUBSTANTIALLY PER DRWG . SUPT STATES CRUSHED STONE B/F HAS BEEN SUBSTITUTED FOR SPECIFIED CLAY DUE TO CHARACTERISTICS OF NATIVE CLAY MATERIAL. 12 COURSES LAID @ W END + W 30'+ OF N ELEVATION
Underground Electrical Inspection - Commercial Partial 06/05/2003
Correction
Resolved
06/05/2003
SECONDARY ELECTRICAL SERVICE CONDUIT FOUR 4" PVC READY FOR CONCRETE ENCASEMENT. OK TO COVER WHEN READY. FROM S ELECT METER CENTER TO NEAR XFORMER LOCATION
Correction
Resolved
06/05/2003
U.G. CONDUIT TO PARKING LOT LIGHTS THEN N & S TO THREE OTHER POLE LOCATIONS AT TRAFFIC ISLANDS OK TO COVER WHEN READY 2" PVC FROM BLDG TO LIGHT POLE @ APEX ISLAND
Correction
Partial Correction
06/05/2003
SECONDARY ELECTRICAL SERVICE CONDUIT FOUR 4" PVC READY FOR CONCRETE ENCASEMENT. OK TO COVER WHEN READY. FROM N ELECT METER CENTER TO XFORMER PAD LOCATION
Underground Electrical Inspection - Commercial Passed 08/01/2003
Correction
Resolved
08/01/2003
SECONDARY ELECTRICAL SERVICE CONDUIT FOUR 4" PVC READY FOR CONCRETE ENCASEMENT. FROM N ELECT METER CENTER TO XFORMER PAD LOCATION
Retaining Wall Inspection Passed 08/01/2003
Correction
Resolved
08/01/2003
PROGRESS TO DATE APPROVED 5 COURSES HIGH @ ~105` E OF WEST WALL SUBSTANTIALLY PER DRWG . SUPT STATES CRUSHED STONE B/F HAS BEEN SUBSTITUTED FOR SPECIFIED CLAY DUE TO CHARACTERISTICS OF NATIVE CLAY MATERIAL. 12 COURSES LAID @ W END + W 30'+ OF N ELEVATION
Footing Inspection - Commercial Passed 08/01/2003
Correction
Resolved
08/01/2003
COLUMN B/16 PREP APPROVED
Underslab Electrical Inspection - Commercial Passed 08/01/2003
Correction
Resolved
08/01/2003
READINESS FOR INSPECTION
Rough Framing Inspection - Commercial Failed 08/05/2003
Correction
Corrective Action Required
08/05/2003
ROOF TRUSS PLACEMENT 1) CHECK TYPE 2 HANGERS FOR PROPER ATTACHMENT OF BOTH STRAPS TO RESIST TENSILE LOADS. 2) SCAB REINFORCEMENT OF ANY BROKEN TOP CHORDS MUST BE FULL LENGTH PAST ADJACENT PANEL POINTS. CHECK TYPE 2 HANGERS & CHECK DAMAGED TOP CHORDS
Electrical Service Inspection Partial 08/06/2003
Correction
Partial Correction
08/06/2003
HOUSE SERVICE ONLY RELEASE ONE METER ONLY
Water Service Inspection Passed 08/11/2003
Correction
Resolved
08/11/2003
NONE > WATER SERVICE APPROVED TAP; METER COMPLETE
Above Ceiling Inspection Failed 08/13/2003
Correction
Corrective Action Required
08/13/2003
ABOVE-CEILING SYSTEMS @ CANOPY SOFFITS IF LISTED, LISTING MAY BE COMPROMISED BY RING MODIFICATION. NOTE STICKER NOTATION "MOUNTING FRAME IS TO BE FLUSH WITH FINISHED CEILING". "DAMP LOCATION" LABEL NOT FOUND ON LIGHT FIXTURES
Miscellaneous Inspection Passed 08/13/2003
Correction
Resolved
08/13/2003
TEMPORARY ELECTRICAL SERVICE
Above Ceiling Inspection Failed 08/14/2003
Correction
Corrective Action Required
08/14/2003
ABOVE-CEILING SYSTEMS @ CANOPY SOFFITS AS PURCHASED BUT NOT AS MODIFIED. NOTE STICKER NOTATION "MOUNTING FRAME IS TO BE FLUSH WITH FINISHED CEILING". LIGHT FIXTURE 422R LISTED FOR DAMP LOCATION
Rough Framing Inspection - Commercial Partial 08/14/2003
Correction
Partial Correction
08/14/2003
ROOF TRUSS PLACEMENT
Above Ceiling Inspection Passed 08/27/2003
Correction
Resolved
08/27/2003
ABOVE-CEILING SYSTEMS @ CANOPY SOFFITS NOW INSTALLED AT ALL LIGHT FIXTURES 422R MFGR's EXTENDED PLASTER RINGS
Rated Assembly Inspection Partial 08/27/2003
Correction
Partial Correction
08/27/2003
WALLS OF MECH ROOM OK TO COVER WHEN READY. OBTAIN APPROVAL OF OUTSIDE FACE GWB PRIOR TO TAPING IT. FRAMING & INSIDE FACE 5/8" TYPE GWB
Rated Assembly Inspection Passed 09/03/2003
Correction
Resolved
09/03/2003
WALLS OF MECH ROOM FIRE-BLOCKING OF UPPER WALLS SUBJECT TO APPROVAL BY FINAL. FRAMING & INSIDE FACE 5/8" TYPE GWB
Correction
Resolved
09/03/2003
WALLS OF MECH ROOM OK TO COVER WHEN READY OUTSIDE FACE 5/8" TYPE GWB
Gas Piping Inspection - Commercial Failed 09/10/2003
Correction
Corrective Action Required
09/10/2003
ROOFTOP INSPECTION SEE SUPPORT DETAILS ON PERMIT PRINTS. REQUIRED FOR APPROVAL CALL REQUEST WHEN READY
Gas Service Inspection - Commercial Failed 09/10/2003
Correction
Partial Correction
09/10/2003
SERVICES TO SPACES 1; 2; 5-20 AT >= 10 PSI FOR 10 MIN. RELEASE GAS SERVICES PRESSURE TEST HELD STEADY
Correction
Corrective Action Required
09/10/2003
SERVICES TO SPACES 3; 4 10 PSI or 6" Hg REQUIRED. PRESSURIZE SYSTEM TO HOLD STEADY AT OR ABOVE MINIMUM. TEST PRESSURE LEVEL BELOW REQUIRED MINIMUM
Gas Service Inspection - Commercial Passed 09/25/2003
Correction
Resolved
09/25/2003
SERVICES TO SPACES 1; 2; 5-20
Correction
Resolved
09/25/2003
SERVICES TO SPACES 3; 4 AT >= 10 PSI FOR 10 MIN RELEASE GAS SERVICE PRESSURE TEST HELD STEADY
Gas Piping Inspection - Commercial Failed 09/25/2003
Correction
Partial Correction
09/25/2003
ROOFTOP INSPECTION
Correction
Corrective Action Required
09/25/2003
PIPING NEAR CONNECTIONS TO RTU's WITH ROOF CHECK & ADJUST LENGTHS OF DROP LEGS FOR CONTACT
Gas Piping Inspection - Commercial Failed 09/29/2003
Correction
Resolved
09/29/2003
ROOFTOP INSPECTION
Correction
Corrective Action Required
09/29/2003
PIPING NEAR CONNECTIONS TO RTU's ALSO @ PARAPET DROP LEGS FOR SPACES 5, 6, 7 CHECK & ADJUST LENGTHS OF DROP LEGS FOR BLOCK CONTACT WITH ROOF. SUPPORT OF PIPE & 90's SPACES 5 & 6 FROM NORTH
Rough Electrical Inspection - Commercial Partial 10/03/2003
Correction
Corrective Action Required
10/03/2003
SEE TEXT ELECTRICAL IN SHELL DEMISING WALL 3,7,10,14,AND 20 APPROVED OK TO COVER DEMISING WALLS
Gas Piping Inspection - Commercial Passed 10/03/2003
Correction
Resolved
10/03/2003
PIPING NEAR CONNECTIONS TO RTU's ALSO @ PARAPET DROP LEGS FOR SPACES 5, 6, 7 CHECK & ADJUST LENGTHS OF DROP LEGS FOR BLOCK CONTACT WITH ROOF. SUPPORT OF PIPE & 90's SPACES 5 & 6 FROM NORTH
Occupancy Inspection - Codes Commercial Failed 10/28/2003
Correction
Corrective Action Required
10/28/2003
SPRINKLER ROOM WALLS PENETRATIONS NOT SEALED
Correction
Corrective Action Required
10/28/2003
JOIST LOWER CHORD BRIDGING RUN THRU RTU DROPS CORRECT CONFLICT
Correction
Corrective Action Required
10/28/2003
LABELING OF ELECTRICAL SERVICE PANEL INCOMPLETE NUMBER BREAKER POSITIONS
Correction
Corrective Action Required
10/28/2003
Receive Fire Department approval
Correction
Corrective Action Required
10/28/2003
Receive Planning & Development Approval
Correction
Corrective Action Required
10/28/2003
Receive Public Works Approval
Correction
Corrective Action Required
10/28/2003
Receive Water Utilities Approval
Electrical Service Inspection Passed 10/28/2003
Correction
Resolved
10/28/2003
HOUSE SERVICE ONLY
Rough Electrical Inspection - Commercial Passed 10/28/2003
Correction
Resolved
10/28/2003
SEE TEXT
Rough Framing Inspection - Commercial Passed 10/28/2003
Correction
Resolved
10/28/2003
ROOF TRUSS PLACEMENT
Occupancy Inspection - Codes Commercial Failed 12/01/2003
Correction
Resolved
12/01/2003
JOIST LOWER CHORD BRIDGING
Correction
Resolved
12/01/2003
LABELING OF ELECTRICAL SERVICE PANEL
Correction
Resolved
12/01/2003
Receive Fire Department approval PER J EDEN 12/01/03
Correction
Corrective Action Required
12/01/2003
REQUIRED HANDRAILS AT STAIRS IBC 1003.3.3.11 NOT PROVIDED 2 LOCATIONS @ CONCOURSE
Occupancy Inspection - Codes Commercial Failed 12/02/2003
Occupancy Inspection - Codes Commercial Failed 12/18/2003
Correction
Corrective Action Required
12/18/2003
SPRINKLER ROOM WALLS PENETRATIONS NOT SEALED
Correction
Corrective Action Required
12/18/2003
Receive Fire Department approval PER J EDEN 12/01/03
Correction
Corrective Action Required
12/18/2003
Receive Planning & Development Approval
Correction
Corrective Action Required
12/18/2003
Receive Water Utilities Approval BACKFLOW REPORT ON FIRE LINE BY-PASS
Correction
Corrective Action Required
12/18/2003
REQUIRED HANDRAILS AT STAIRS RETURN HANDRAIL TO WALL
Occupancy Inspection - Codes Commercial Passed 12/22/2003
Correction
Resolved
12/22/2003
SPRINKLER ROOM WALLS
Correction
Resolved
12/22/2003
Receive Fire Department approval
Correction
Resolved
12/22/2003
Receive Planning & Development Approval
Correction
Resolved
12/22/2003
Receive Public Works Approval
Correction
Resolved
12/22/2003
Receive Water Utilities Approval
Correction
Resolved
12/22/2003
REQUIRED HANDRAILS AT STAIRS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents