Permit Application Status

B0201520


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0201520
Building Permit - Commercial
Certificate of Occupancy
HOORFAR LISA G
NEW COMMERCIAL
REMODEL OF EXISTING HOME INTO OFFICE SPACE
09/04/2002
02/20/2003
08/19/2003
04/27/2004
Locations
Contacts
BRUCE BEST, AGMP (ARCHITECTURE GRAPHICS MANAGEME, Address:226 S DOUGLAS STREET  
LYTLE CONSTRUCTION INC, Address:1051 SE BROADWAY  
HOORFAR LISA G, Address:440 NE BROCKTON DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/03/2003 10/29/2010
Correction

CA - ANSI A117.1-1998 505.2 - Location. Handrails shall be provided on both sides of stairs and ramps.
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - 2000 IBC 803.1 - Interior wall and ceiling finishes shall be classified in accordance with ASTM E 84. Such interior finish materials shall be grouped in the following classes in accordance with their flame spread and smoke-developed index.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

CA - LSCO 7-902 - The correct wind load is 90 mph. The plans indicate the wind load as 80 mph.
Correction

CA - The footing detail on sheet A-4 indicates a footing depth of 2 feet 9 inches with a varying finish grade.
Correction

CA - A note on sheet A-1 refers to sheet A-5 for header schedule. The header schedule is on sheet A-4.
Correction

CA - 2000 IBC 306.4 - Appliances Under Floors - Underfloor spaces containing appliances requirng access shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance.
Correction

CA - No plumbing details are given.
Correction

CA - The panel schedule is not complete.
Correction

CA - No mechanical details are given.
Correction

Fire Department; Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department-315.2.4 Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistive construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 1.75 inches (44.5 mm)in thickness. Storage shall not be placed on exposed joists.
Correction

CA - IMC303.3 - Fuel fired appliances shall not be located in, or obtain combustion air from, any of the following rooms or spaces: Storage Closets.
Correction

CA - All piping shall be supported in accordance with IMC Table 305.4.
Correction

Fire Department- The area below grade is less than 1,500 square feet and is not required to be sprinklered per IFC 903.2.12.1.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1208.2 - An opening not less than 20 inches by 30 inches shall be provided to any attic area having a clear height of over 30 inches. A 30-inch minimum clear headroom in the attic space shall be provided at or above the access opening.
Correction

CA - 2000 IBC 1108.2 - Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible.
Correction

CA - 2000 IBC 1003.3.3.3 - Stair riser heights shall be 7 inches maximum and 4 inches minimum. Stair tread depths shall be 11 inches minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at right angle to the tread's leading edge.
Correction

CA - 2000 IBC 1108.4 - Where kitchen, kitchenettes and wet bars are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC/ANSI A117.1.
Correction

CA - 2000 IBC 1003.3.3.11.5 - Handrail extension. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight. Where handrails are not continous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser.
Correction

CA - 2000 IBC 1003.3.1.5 - Landings at doors. Landings shall have a width not less than the width of the stairway or the width of the door, whichever is the greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

CA - 2000 IBC 1202.2 - Attic spaces. Enclosed attics and enclosed rafter spaces formed where ceiling are applied directly to the underside of roof framing member shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain and snow. Blocking and bridging shall be arranged so as not to interfere with the movement of air. A minimum of 1 inch of air space shall be provided between the insulation and the roof sheathing. The net free ventilating area shll not be less than 1/150 of the area of the space ventilated, with 50 percent of the required ventilating area provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet above the eave or cornice vents with the balance of the required ventilation provided by eave or cornice vents.
Correction

CA - 2000 IBC 1104.1 - Site arrival points. Accessible routes within the site shall be provided from public transportation stops, accessible parking and accessible passenger loading zones, and public streets or sidewalks to the accessible building entrance served.
Correction

Fire Department; Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Combustible debris, waste materials and trash shall not be burned on site.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IMC 701.2 - Combustion and dilution air required. Every room or space containing fuel-burning appliances shall be provided with combustion and dilution air as required by this code. Combustion and dilution air shall be provided in accordance with Section 702, 703, 704, 705, 706 or 707 or shall be provided by an approved engineered system. Direct vent appliances or equipment that do not draw combustion air from inside of the building are not required to be considered in the determination of the combustion and dilution air requirements. Combustion air requirements shall be determined based on the simultaneous operation of all fuel-burning appliances drawing combustion and dilution air from the room or space.
Correction

CA - 2000 IPC 403.2 - Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 230-70(a) - Location. The service disconnecting means shall be installed at a readily accessible location either outisde of the building or structure or inside within ten (10) feet nearest the point of entrance of the service conductors. Service disconnecting means shall not be installed in bathrooms. (As ammended and adopted.)
Correction

CA - 1999 NEC 110-26 (a) (2) - Width of working space. The width of the working space in front of the electric equipment shall be the width of the equipment or 30 in. (762 mm), whichever is greater. In all cases, the work space shall permit at least a 90 degree opening of equipment doors or hinged panels.
Correction

CA - 1999 NEC 240-24(b) - Occupancy. Each occupant shall have ready access to all overcurrent devices protecting the conductors suplying that occupancy. Where electric service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the service overcurrent devices and feeder overcurrent devices supplying more than one occupancy shall be permitted to be accessible to only authorized management personnel in the following: (1) In multiple occupancy buildings (2) For guest rooms of hotels and motels that are intended for transient occupancy.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

A note should be provided indicating a Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior to any point of use.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $503.00 $503.00 Paid 02/20/2003
24 BLDG Plan Check Fees $28.35 $28.35 Paid 02/20/2003
25 Electrical Permit Fee $105.79 $105.79 Paid 02/20/2003
25 Mechanical Permit Fees $41.00 $41.00 Paid 02/20/2003
25 Plumbing Permit Fees $28.00 $28.00 Paid 02/20/2003
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Not Ready 05/30/2003
Correction
Corrective Action Required
05/30/2003
READINESS FOR INSPECTION CALL FOR INSPECTION WHEN PREPARATION IS COMPLETE WORK NOT COMPLETED NOT READY FOR INSPECTION
Footing Inspection - Commercial Partial 06/04/2003
Correction
Resolved
06/04/2003
READINESS FOR INSPECTION
Correction
Partial Correction
06/04/2003
FOOTING INCLUDES CENTER 8` ONLY OF UNDERPINNING AT EXSTG BLDG FDN WALL. REMAINDER TO BE POURED WITH WALL POUR. SUBSTANTIALLYPER DRWG SD1 EXCEPT WIDER - 36"
Electrical Service Inspection Partial 06/06/2003
Correction
Partial Correction
06/06/2003
NONE > TEMPORARY SERVICE APPROVED 100 AMP
Foundation Inspection - Commercial Partial 06/13/2003
Correction
Partial Correction
06/13/2003
BASEMENT WALL OK TO POUR WHEN READY N; W; S WALLS PREP 4POUR SUBSTANTIALLY COMPLETE
Foundation Inspection - Commercial Passed 06/18/2003
Correction
Resolved
06/18/2003
BASEMENT WALL OK TO POUR WHEN READY N; W; S WALLS PREP 4POUR SUBSTANTIALLY COMPLETE
Footing Inspection - Commercial Passed 06/18/2003
Correction
Resolved
06/18/2003
FOOTING OK TO POUR WHEN READY REMAINDER OF UNDERPINNING @ EXSTG BLDG FDN WALL
Sewer Service Inspection Passed 07/01/2003
Correction
Resolved
07/01/2003
SANITARY SEWER CONNECTION APPROVED 4" C.I. OK TO COVER WHEN READY BLDG ENTRY NEAR NW CORNER WEST TO CONN W/ EXSTG SAN
Underground Electrical Inspection - Commercial Partial 07/07/2003
Correction
Partial Correction
07/07/2003
UNDERGROUND SERVICE CONDUIT EAST 15' TO BLDG ENTRY OK TO COVER WHEN READY
All Rough Inspection - Commercial Failed 08/08/2003
Correction
Corrective Action Required
08/08/2003
ABANDONED MEP MATERIALS NOT REMOVED @ ATTIC/BSMT ELECTRICAL, PLUMBING,...
Correction
Corrective Action Required
08/08/2003
PLUMBING VTR NOT CONNECTED
Correction
Corrective Action Required
08/08/2003
FLOOR-TO-FLOOR OPENINGS IRC R321.3; R502.13; R602.8: PLATE BORES; HOLES IN FLOOR NOT FIREBLOCKED THROUGHOUT BUILDING
Correction
Corrective Action Required
08/08/2003
DOUBLE TOP PLATE JOINTS < 34" APART; APPARENT INSECT DAMAGE; NOTCHES/CUTS CONDITION & CONTINUITY SE ROOM
Correction
Corrective Action Required
08/08/2003
HVAC WALL/FLOOR PLENUMS IRC R321.3; M1601.3.3: STUDS & JOISTS BOUNDING RETURN AIR PLENUMS CHECK ALL FOR BORES FIRE BLOCK AS REQ'D
Correction
Corrective Action Required
08/08/2003
TRIPLE CORNER STUDS SE CORNER SE ROOM NOT SUPPORTING TOP PLATE
Correction
Corrective Action Required
08/08/2003
COLUMN BASE & TOP PLATES NOT SECURED TOP BEAM/SLAB
Correction
Corrective Action Required
08/08/2003
NOTCHING OF FLOOR JOISTS NOTCHES > D/6 NOTCHES WITHIN MIDDLE 1/3 OF SPAN BEARING END NOTCHES > D/4 BASEMENT - EAST
All Rough Inspection - Commercial Passed 08/13/2003
Correction
Resolved
08/13/2003
ABANDONED MEP MATERIALS
Correction
Resolved
08/13/2003
PLUMBING VTR
Correction
Resolved
08/13/2003
FLOOR-TO-FLOOR OPENINGS
Correction
Resolved
08/13/2003
DOUBLE TOP PLATE
Correction
Resolved
08/13/2003
HVAC WALL/FLOOR PLENUMS
Correction
Resolved
08/13/2003
TRIPLE CORNER STUDS
Correction
Resolved
08/13/2003
COLUMN BASE & TOP PLATES
Correction
Resolved
08/13/2003
NOTCHING OF FLOOR JOISTS
Correction
Resolved
08/13/2003
INSULATION & GYP BOARD OK TO INSULATE OK TO INSTALL GYP BOARD
Gas Piping Inspection - Commercial Passed 09/09/2003
Gas Service Inspection - Commercial Passed 09/09/2003
Correction
Resolved
09/09/2003
PRESSURE TEST RELEASE GAS SERVICE HELD STEADY AT >= 10 PSI FOR 10 MIN
All Rough Inspection - Commercial Passed 09/09/2003
Correction
Resolved
09/09/2003
IN-WALL SYSTEMS ROUGH - BREAK RM TO STRUCTURE W/I 12" OF ENTRY TO SERVICE PANEL. OK TO COVER WHEN READY AFTER EC SECURES NMB
Electrical Service Inspection Failed 09/09/2003
Correction
Resolved
09/09/2003
NONE > TEMPORARY SERVICE APPROVED
Correction
Corrective Action Required
09/09/2003
Grounding Electrode Installation (IRC) ATTACHMENT OF CLAMP CONNECTION @ WATER PIPE NOT POLISHED BEFORE
Correction
Corrective Action Required
09/09/2003
GROUNDING ELECTRODE CONDUCTOR IRC E3510.1: G.E.C. MUST BE CARRIED ON SURFACE OF STRUCTURE ENTIRE LENGTH -- OR ENCLOSED IN CONDUIT. INCOMPLETELY PROTECTED SVC PANEL TO WATER LINE
Occupancy Inspection - Codes Commercial Failed 09/11/2003
Correction
Corrective Action Required
09/11/2003
DAMAGE TO STREET ADVISE PROJECT OWNER REPAIR MUST BE COMPLETED & APPROVED BY PUBLIC WORKS DEPT BEFORE CERTIFICATE OF OCCUPANCY IS ISSUED. 2ND ST @ ALLEY ENTRANCE BACKHOE TRACK DAMAGE
Electrical Service Inspection Passed 09/30/2003
Correction
Resolved
09/30/2003
Grounding Electrode Installation (IRC)
Correction
Resolved
09/30/2003
GROUNDING ELECTRODE CONDUCTOR
Correction
Resolved
09/30/2003
ELECTRICAL SERVICE INSTALLATION 200 AMP RELEASE SERVICE
Above Ceiling Inspection Passed 09/30/2003
Correction
Resolved
09/30/2003
BASEMENT FINISHED AREA OK TO COVER WHEN READY
Underground Electrical Inspection - Commercial Passed 10/09/2003
Correction
Resolved
10/09/2003
UNDERGROUND SERVICE CONDUIT
Occupancy Inspection - Codes Commercial Failed 10/09/2003
Correction
Resolved
10/09/2003
DAMAGE TO STREET
Correction
Resolved
10/09/2003
Receive Public Works Approval PER M WEISENBORN 10/09/03
Correction
Corrective Action Required
10/09/2003
Receive Fire Department approval SEE FD REPORT PROVIDED
Correction
Corrective Action Required
10/09/2003
Receive Water Utilities Approval SUBMIT REPORT OF BACKFLOW PREVENTION TEST
Correction
Corrective Action Required
10/09/2003
Receive Planning & Development Approval REQUEST INSPECTION WHEN LANDSCAPING IS COMPLETED
Correction
Corrective Action Required
10/09/2003
ELECTRICAL RECEPTACLES/SWITCHES IRC E3901.10; E3902.6 <> NEC 380-10; 410-56(f) NOT TIGHT TO BOX CHECK ALL
Correction
Corrective Action Required
10/09/2003
REQUIRED HANDRAIL AT STAIR IRC R315 / LSCO 7-914: ANY STAIR W/ 3+ RISERS. AT LEAST ONE SIDE. MIN/MAX HEIGHT 34" TO 38" VERTICAL FROM TREAD NOSING. NOT PROVIDED CONTINUOUS UPPER SEGMENT TO ATTIC
Correction
Corrective Action Required
10/09/2003
WINDOW GLAZING @ STAIRWELL < 18" ABOVE WALK SURFACE NOT TEMPERED GLASS
Correction
Corrective Action Required
10/09/2003
SECURING/SUPPORT OF NM ELECTRICAL CABLE NEC 336-18; IRC E3702.1: 4.5' MAX INTERVALS AND WITHIN 12" OF BOXES WITH BUSHINGS INCOMPLETE FURNACE ROOM
Correction
Corrective Action Required
10/09/2003
OCCUPANCY STATUS IBC 110.1: UNTIL APPROVED DO NOT OCCUPY OR PLACE PERSONAL PROPERTY
Occupancy Inspection - Codes Commercial Failed 10/14/2003
Correction
Resolved
10/14/2003
Receive Fire Department approval PER N ULLERY 10/14/03
Correction
Resolved
10/14/2003
Receive Water Utilities Approval PER J WALTERS 10/14/03
Correction
Corrective Action Required
10/14/2003
Receive Planning & Development Approval LINDA TYRELL 969-7318 REQUEST INSPECTION WHEN LANDSCAPING IS COMPLETED
Correction
Resolved
10/14/2003
ELECTRICAL RECEPTACLES/SWITCHES
Correction
Resolved
10/14/2003
REQUIRED HANDRAIL AT STAIR
Correction
Resolved
10/14/2003
WINDOW GLAZING @ STAIRWELL
Correction
Resolved
10/14/2003
SECURING/SUPPORT OF NM ELECTRICAL CABLE
Correction
Resolved
10/14/2003
OCCUPANCY STATUS SEE TEMPORARY OCCUPANCY
Correction
Corrective Action Required
10/14/2003
PERMANENT EROSION CONTROL, VEGATATION, & DRAINAGE GRADING LSCO #5029: FINE GRADE, SOD/SEED; 6" MIN CLEARANCE TO WOOD SIDING/TRIM; SPLASH BLOCKS TO 3`-0 FROM WALL; POSITIVE DRAINAGE ENTIRE LOT; UTILITY STRUCTURE COVERS SET TO FINISH GRADE; AC CONDENSER PAD LEVEL & 3" +- ABOVE GRADE. INCOMPLETE LOT
Occupancy Inspection - Codes Commercial Failed 11/04/2003
Correction
Resolved
11/04/2003
Receive Public Works Approval
Correction
Resolved
11/04/2003
Receive Fire Department approval
Correction
Resolved
11/04/2003
Receive Water Utilities Approval
Correction
Corrective Action Required
11/04/2003
PERMANENT EROSION CONTROL, VEGATATION, & DRAINAGE GRADING to a satisfactory condition prior to full C of O issuance. Ensure adjoining property to the north is restored
Occupancy Inspection - Codes Commercial Passed 04/23/2004
Correction
Resolved
04/23/2004
Receive Planning & Development Approval NO ISSUES COMMUNICATED
Correction
Resolved
04/23/2004
OCCUPANCY STATUS
Correction
Resolved
04/23/2004
PERMANENT EROSION CONTROL, VEGATATION, & DRAINAGE GRADING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home