Permit Application Status

B0201101


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0201101
Building Permit - Commercial
Certificate of Occupancy
ABUNDANT LIFE BAPTIST CHURCH OF LEES SUMMIT
NEW COMMERCIAL
NEW CHURCH BUILDING
07/01/2002
10/25/2002
04/23/2003
12/04/2003
Locations
Contacts
HGK CONSTRUCTION MANAGEMENT, Address:8801 E 63RD ST #208  
ABUNDANT LIFE BAPTIST CHURCH OF LEES SUMMIT, Address:414 SW PERSELS RD, Phone:(816) 554-8181  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/09/2003 10/29/2010
Correction

Fire Department- If cooking in the facility has the potential of producing grease laden vapors or smoke, a Type 1 hood and fire suppression system shall be required.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal.
Correction

Fire Department- The swing of door 132A exceeds 50% of the width of the corridor. IFC 1003.2.3.1
Correction

CA - The domestic water service is not shown on the site plan.
Correction

CA - Details on the platform are not provided.
Correction

CA - I did not receive a spec book with the application.
Correction

CA - A soils report was not submitted with the application.
Correction

CA - Details on the stairs are not provided.
Correction

CA - Provide two (2) copies of the structural steel plans once they are available. The plans shall be signed and sealed by an engineer licensed in the State of Missouri.
Correction

CA - Details on the seating in the multipurpose room are not provided.
Correction

CA - Details on the accessible features are not provided.
Correction

CA - Details on the exterior wall construction are not provided.
Correction

CA - Details on the mezzanine floor assembly are not provided.
Correction

CA - It is unclear how the equipment on the mechanical mezzanines will be accessed.
Correction

CA - The ratings shown on the door schedule do not correspond with the plans.
Correction

CA - 2000 IBC 1008.2 - Assembly other exits. In addition to having access to a main exit, each level of an occupancy in Group A having an occupant load of greater than 300 shall be provided with additional exits that shall provide an egress capacity for at least one-half of the total occupant load served by that level and comply with Section 1004.2.2.
Correction

CA - 2000 IBC 1107.2 - Assembly area setting. Assembly areas with fixed seating shall comply with Sections 1107.2.1 through 1107.2.4.1. Dining areas shall comply with Sections 1107.2.5 through 1107.2.5.2.
Correction

CA - 2000 IBC 1108.2.1 - Unisex toilet and bathing rooms. In assembly and merchantile occupancies, an accessible unisex toilet room shall be provided where an aggregate of six or more male and female water closets are required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the unisex toilet room requirements. In recreational facilities where separate-sex bathing rooms are provided, an accessible unisex bathing room shall be provided. Fixtures located within unisex toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy.
Correction

CA - 2000 IPC 708.3.1 - Horizontal drains within buildings. All horizontal drains shall be provided with cleanouts located not more than 100 feet (30 480 mm) apart.
Correction

CA - 2000 IMC 507.2.2 - Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I or II hoods as required for the type of appliances and processes in accordance with Sections 507.2 and 507.2.1.
Correction

Fire Department- The canopy is of non-combustible construction and provides protection for patrons being picked up or dropped off. There will be no storage or parking under the canopy, therefore it is not required to be sprinklered.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1003.3.1.2 - Door swing. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a high-hazard occupancy.
Correction

CA - 2000 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as devined in Section 2406.2 shall pass the test requirements of CPSC 16 CFR 1201, listed in Chapter 35. Glazing shall comply with the CSPC 16 CFR, Part 1201 criteria for Category I or Category II as indicated in Table 2406.1.
Correction

CA - 2000 IBC 1003.2.10.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30,480 mm) from the nearest visible exit sign.
Correction

CA - 2000 IBC 1003.2.11.2 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency system shall automatically illuminate all of the follow areas: 1. Exit access corridors, passageways, and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways located in buildings required to have two or more exits. 3. Interior exit discharge elements, as permitted in Section 1006.1, in buildings required to have two or more exits. 4. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits.
Correction

1003.2.10.1 Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department; Fire apparatus access roads shall have an unobstructed width of not less than 20 feet except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised when the number of sprinkler heads are 20 (twenty) or greater.
Correction

Fire Department; Valve supervision and water flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA72 or, when approved by the code official, shall sound an audible signal at a constantly attended location.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - 2000 IMC 306.5 - Where equipment and appliances requireing access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shll be from grade or floor level to the equipment and appliances' level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal.
Correction

CA - 2000 IPC 708.3.2 - Building sewers shall be provided with cleanouts located not more than 100 feet apart measured fron the upstream entrance of the cleanout. For building sewers 8 inches and larger, manholes shall be provided and located at each change in direction and at intervals of not more than 400 feet of developed length of the drainage piping.
Correction

CA - 2000 IPC 802.1.1 - Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO Chapter 7, Section 7-803 - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following; Exception: The Building Official may approve a decreased R-value for building exterior walls provided the space is not occupied by employees and is associated with storage/warehouse or manufactoring. a) Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or openings or approved penetrations nor does it apply to unfinished basement concrete walls. b) Floor assemblies forming portions of a building envelope shall meet or exceed a R factor rating of 19. Exception: Concrete floor in contact with the earth need not be insulated. c) Roof assemblies forming portions of a building envelope shall meet or exceed an R factor of 19.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $3,473.00 $3,473.00 Paid 10/25/2002
24 BLDG Plan Check Fees $77.85 $77.85 Paid 10/25/2002
25 Electrical Permit Fee $410.00 $410.00 Paid 10/25/2002
25 Mechanical Permit Fees $119.50 $119.50 Paid 10/25/2002
25 Plumbing Permit Fees $208.00 $208.00 Paid 10/25/2002
84 Water Meters $600.00 $600.00 Paid 10/25/2002
85 Water Taps $6,835.00 $6,835.00 Paid 10/25/2002
89 Sewer Tap Fees $1,230.00 $1,230.00 Paid 10/25/2002
Right of Way Permit $35.00 $35.00 Paid 10/25/2002
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection Not Ready 10/10/2002
Correction
Corrective Action Required
10/10/2002
Permit OBTAIN PERMIT
Miscellaneous Inspection Failed 11/05/2002
Correction
Corrective Action Required
11/05/2002
Permit Required STRUCTURE DEMO`d ON SITE. NO OCCUPANCY WILL BE AUTHORIZED UNTIL DEMO PERMIT HAS BEEN PULLED, APPROVED & CLOSED.
Water Service Inspection Not Ready 11/05/2002
Correction
Corrective Action Required
11/05/2002
Not Ready
Water Service Inspection Partial 11/08/2002
Correction
Partial Correction
11/08/2002
Not Ready 6" FIRE & 2" SERVICE APPROVED - FIRST 80` FROM FOUNDATION
Water Service Inspection Partial 11/12/2002
Correction
Resolved
11/12/2002
Not Ready 6" FIRE & 2" SERVICE APPROVED - FIRST 80` FROM FOUNDATION
Correction
Partial Correction
11/12/2002
ADDITIONAL PARTIAL WATER SERVICE LINE 8" CI FIRE LINE & 2" PVC WATER LINE FROM 80'+- S OF FDN WALL TO 160'+- S OF FDN WALL
Water Service Inspection Partial 11/14/2002
Correction
Partial Correction
11/14/2002
ADDITIONAL PARTIAL WATER SERVICE LINE FROM PREVIOUS APPROVED POINT TO WITHIN 15` OF TAP SITE. METER NOT SET. 2" LINE ONLY. 8" FIRE LINE NOT INSPECTED
All Rough Inspection - Commercial Partial 12/05/2002
Correction
Partial Correction
12/05/2002
PLATFORM 138 ROUGH-IN FRAMING & ELECTRICAL PER A4.2 & SDE1 REV 12/3
Rough Electrical Inspection - Commercial Passed 12/06/2002
Water Service Inspection Passed 01/07/2003
Correction
Resolved
01/07/2003
Not Ready
Correction
Resolved
01/07/2003
ADDITIONAL PARTIAL WATER SERVICE LINE
Correction
Resolved
01/07/2003
FINAL PARTIAL SERVICE INSTALL METER/MANHOLE INSTALLED TAP COMPLETED
All Rough Inspection - Commercial Partial 01/10/2003
Correction
Partial Correction
01/10/2003
IN-WALL SYSTEMS PARTIAL ALSO MULTIPURPOSE RM 139 W WALL. FRAMING, ELECTRICAL, & PLUMBING IN ALL DESIGNATED AREA WALLS OK TO COVER WHEN READY. WALLS @ CL F.1 & D.8 & NO EXCLUD'G MULTIPURPOSE 139
All Rough Inspection - Commercial Partial 01/31/2003
Correction
Partial Correction
01/31/2003
IN-WALL SYSTEMS PARTIAL AND N & S WALLS OF MP RM 139 OK TO COVER ALL ABOVE WHEN READY ROOMS 105, 106, 107, 108, 109, 109A, 109B, 112, 113
Erosion Control Inspection Residential Partial 01/31/2003
Correction
Partial Correction
01/31/2003
Erosion Control THROUGH FINAL INSPECTION KEEP STREET CLEAN MAINTAIN EROSION CONTROL
All Rough Inspection - Commercial Partial 02/10/2003
Correction
Partial Correction
02/10/2003
IN-WALL SYSTEMS PARTIAL IN ALL DESIGNATED AREA WALLS OK TO COVER WHEN READY: SOUTH WALLS OF 146:40 SOMETHING; 145:OVER 50; 144:CORRIDOR; 142:KITCHEN; 143:MECH EQUIPMENT. WEST WALLS OF 141:PANTRY; 142A:JAN; 143:MECH EQUIPMENT; EAST WALL OF 139:M-P RM FROM (E) TO (H). FRAMING, ELECTRICAL PLUMBING SYSTEMS
Gas Service Inspection - Commercial Passed 02/19/2003
Gas Piping Inspection - Commercial Passed 02/19/2003
All Rough Inspection - Commercial Partial 02/26/2003
Correction
Partial Correction
02/26/2003
None KITCHEN WALLS FRAM. , ELECT., PLUM. OK TO ROCK.
Rough Framing Inspection - Commercial Failed 03/07/2003
Correction
Corrective Action Required
03/07/2003
BELOW RM 146 , 145 WALLS OK TO COVER RM 114 SOFFIT OK TO COVER COL. E-1,F-1, G, H, I-9 OK TO COVER
Electrical Service Inspection Passed 03/07/2003
Rough Framing Inspection - Commercial Partial 04/11/2003
Correction
Partial Correction
04/11/2003
BELOW ROOM 194 (AUDIO ROOM AND ROOF ACCESS) APPROVED--OK TO COVER
Above Ceiling Inspection Not Ready 04/29/2003
Correction
Corrective Action Required
04/29/2003
NOT READY
Above Ceiling Inspection Partial 05/01/2003
Correction
Resolved
05/01/2003
NOT READY
Correction
Partial Correction
05/01/2003
None NORTH SECTION CLASSROOMS FROM F-LINE NORTH EXCEPT CLOSET 132A APPROVED. MASTER BATHROOMS APPROVED. NOTE: DETATCH LOW VOLTAGE WIRES FROM SPRINKLER SYSTEM AND SUPPORTS. SECURE ELSWHERE
Above Ceiling Inspection Partial 05/07/2003
Correction
Partial Correction
05/07/2003
None HALLWAY EAST OF GYM APPROVED EXCLUDING EAST ENTRY CORIDOR
Above Ceiling Inspection Partial 05/21/2003
Correction
Partial Correction
05/21/2003
None EXTERIOR OVERHANG APPROVED. INTERIOR CLOSET APPROVED.
Above Ceiling Inspection Partial 05/23/2003
Correction
Corrective Action Required
05/23/2003
NOT READY
Above Ceiling Inspection Passed 05/30/2003
Correction
Resolved
05/30/2003
NOT READY
Correction
Resolved
05/30/2003
None NORTH SECTION CLASSROOMS FROM F-LINE NORTH EXCEPT CLOSET 132A APPROVED. MASTER BATHROOMS APPROVED. NOTE: DETATCH LOW VOLTAGE WIRES FROM SPRINKLER SYSTEM AND SUPPORTS. SECURE ELSWHERE
Correction
Resolved
05/30/2003
None HALLWAY EAST OF GYM APPROVED EXCLUDING EAST ENTRY CORIDOR
Correction
Resolved
05/30/2003
None EXTERIOR OVERHANG APPROVED. INTERIOR CLOSET APPROVED.
Occupancy Inspection - Codes Commercial Failed 06/03/2003
Correction
Corrective Action Required
06/03/2003
Receive Planning & Development Approval Receive Planning & Development Dept. approval. (Landscaping, H.C. parking signage, trash enclosure, etc.) P & D did not submit information prior to or during inspection.
Correction
Corrective Action Required
06/03/2003
Receive Public Works Approval Submit overtime fees Restore yard at 1211 SW Mission Place (tap excavation) Backfill curbs at R-O-W Complete street asphalt at entrances Raise hydrant at SW corner of building
Correction
Corrective Action Required
06/03/2003
See Below Complete parking lot lighting electrical Provide site address Install landing at south exit door (corridor from Sanctuary) Blank off panel opening (Storage room L140) Install and secure ladders to mezzanine areas above stage area
Correction
Corrective Action Required
06/03/2003
See below Vent bath fan at restroom south of stage Close junction boxes above ceiling in sound center (sanctuary) Install exterior handrails Install exit and emergency lighting in rooms 145 & 146 Exit/emergency lights not functioning on back up (138,132,109)
Correction
Corrective Action Required
06/03/2003
See below Post occupant load in sanctuary Missing outlet/swith plates:east wall of south mezzanine, mens restroom, water heater closet off of lobby break area, day care counter Outlet at office sink not wired (no power) Remove temp. wiring in north mezzanine
Correction
Resolved
06/03/2003
None
Correction
Corrective Action Required
06/03/2003
Receive Fire Department approval List provided under separate cover (Jim Eden)
Occupancy Inspection - Codes Commercial Failed 08/20/2003
Correction
Corrective Action Required
08/20/2003
Receive Planning & Development Approval Landscape
Correction
Corrective Action Required
08/20/2003
Receive Public Works Approval Submit overtime fees Restore yard at 1211 SW Mission Place (tap excavation) Backfill curbs at R-O-W Complete street asphalt at entrances Raise hydrant at SW corner of building
Correction
Corrective Action Required
08/20/2003
See Below SECURE LADDER TO NORTH MEZZANINE.
Correction
Corrective Action Required
08/20/2003
See below Exit/emergency lights not functioning on back up (138,132,109) NO ONE HERE TO TEST. 8-20-03
Correction
Corrective Action Required
08/20/2003
See below POST OCCUPANT LOAD IN SANCTUARY.
Correction
Resolved
08/20/2003
None
Correction
Corrective Action Required
08/20/2003
Receive Fire Department approval List provided under separate cover (Jim Eden)
Occupancy Inspection - Codes Commercial Failed 08/21/2003
Correction
Resolved
08/21/2003
Receive Public Works Approval
Occupancy Inspection - Codes Commercial Failed 08/26/2003
Correction
Partial Correction
08/26/2003
Receive Planning & Development Approval Landscape
Correction
Resolved
08/26/2003
See Below
Correction
Resolved
08/26/2003
See below
Correction
Resolved
08/26/2003
See below
Correction
Resolved
08/26/2003
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Passed 12/01/2003
Correction
Resolved
12/01/2003
Receive Planning & Development Approval
All Rough Inspection - Commercial Passed 12/04/2003
Correction
Resolved
12/04/2003
PLATFORM 138 ROUGH-IN FRAMING & ELECTRICAL PER A4.2 & SDE1 REV 12/3
Correction
Resolved
12/04/2003
IN-WALL SYSTEMS PARTIAL ALSO MULTIPURPOSE RM 139 W WALL. FRAMING, ELECTRICAL, & PLUMBING IN ALL DESIGNATED AREA WALLS OK TO COVER WHEN READY. WALLS @ CL F.1 & D.8 & NO EXCLUD'G MULTIPURPOSE 139
Correction
Resolved
12/04/2003
IN-WALL SYSTEMS PARTIAL AND N & S WALLS OF MP RM 139 OK TO COVER ALL ABOVE WHEN READY ROOMS 105, 106, 107, 108, 109, 109A, 109B, 112, 113
Correction
Resolved
12/04/2003
IN-WALL SYSTEMS PARTIAL IN ALL DESIGNATED AREA WALLS OK TO COVER WHEN READY: SOUTH WALLS OF 146:40 SOMETHING; 145:OVER 50; 144:CORRIDOR; 142:KITCHEN; 143:MECH EQUIPMENT. WEST WALLS OF 141:PANTRY; 142A:JAN; 143:MECH EQUIPMENT; EAST WALL OF 139:M-P RM FROM (E) TO (H). FRAMING, ELECTRICAL PLUMBING SYSTEMS
Correction
Resolved
12/04/2003
None KITCHEN WALLS FRAM. , ELECT., PLUM. OK TO ROCK.
Sewer Service Inspection Passed 12/04/2003
Correction
Resolved
12/04/2003
Permit
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home