Permit Application Status

B0200366


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0200366
Building Permit - Commercial
Certificate of Occupancy
KANSAS CITY DEVELOPMENT
CHANGE OF TENANT
CHANGE OF TENANT FINISH
03/13/2002
05/14/2002
11/10/2002
10/29/2002
Locations
Contacts
ALLEN CONSTRUCTION INC, ROBERT, Address:9700 WINDSOR DR  
KANSAS CITY DEVELOPMENT, Address:729 NE LAKEWOOD BLVD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/09/2002 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

Fire Department: Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

A Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the tenant space on the domestic water service line prior to any point of use.
Correction

Backflow prevention assembly (RPZ) will be placed inside the building on the domestic water service line prior to the suction unit.
Correction

Backflow prevention assembly (RPZ or a DC) will be placed inside the building on the domestic water line to isolate the x-ray processor.
Correction

Backflow prevention assembly (RPZ or a DC) will be placed inside the building on the domestic water line to isolate the model trimmer.
Correction

CA - The correct construction type for this building is V-B. The plans show it as III-B.
Correction

CA - 2000 IPC 917.1 - Air admittance valves are allowed only when is is structurally not feassible to install a hard pipe venting system and approved by the building official. Vent systems utilizing air admittance valves shall comply with this section. Individual-and branch-type air admittance valves shall conform to ASSE 1051. (As amended by the City of Lee's Summit.)
Correction

CA - Provide a wall detail for the interior walls.
Correction

CA - Provide a room finish schedule.
Correction

CA - Provide a door schedule.
Correction

CA - Provide an electrical panel detail.
Correction

CA - No medical gas systems are indicated on the plans. Will piped medical gas be used in this facility?
Correction

CA - Provide accessiblity details for the restrooms.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1003.2.10.4 - Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.
Correction

CA - 2000 IBC 1003.2.11 - The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

CA - 2000 IBC 1209.1 - In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

CA - 2000 IBC 1108.4 - Where kitchen, kitchenettes and wet bars are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC/ANSI A117.1.
Correction

Fire Department; Medical gases shall be stored in areas dedicated to the storage of such gases without other storage or uses. Where containers of medical gases in quantities greater than the permit amount are located inside buildings, they shall be in a 1-hour exterior room, a 1-hour interior room or a gas cabinet in accordance with Section 3006.2.1, 3006.2.2 or 3006.2.3.
Correction

Fire Department; Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Combustible debris, waste materials and trash shall not be burned on site.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IPC 403.2 - Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

CA - 2000 IPC 403.6 - Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. Public toilet facilities shall be located not more than one story above or below the space required to be provided with public toilet facilites and the path of travel to such facilities shall not exceed a distance of 500 feet.
Correction

CA - 2000 IPC 312.1 - Required tests. The permit holder shall make the applicable test prescribed in Sections 312.2 through 312.9 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the code official when the plumbing work is ready for tests. The equipment, material, power and labor necessary for the inspection and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. All plumbing system piping shall be tested with either water or air. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be submitted to final tests. The code official shall require the removal of any cleanouts if necessary to ascertain if the pressure has reached all parts of the system. Note: Testing of the plumbing system is not required to be witnessed by the Codes Administration Staff with the exception of gas piping.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $248.00 $248.00 Paid 05/14/2002
24 BLDG Plan Check Fees $18.20 $18.20 Paid 05/14/2002
25 Electrical Permit Fee $30.00 $30.00 Paid 05/14/2002
25 Plumbing Permit Fees $35.00 $35.00 Paid 05/14/2002
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 06/04/2002
Correction
Resolved
06/04/2002
APPROVED PLANS
Rough Electrical Inspection - Commercial Passed 07/09/2002
Correction
Resolved
07/09/2002
None
Rough Framing Inspection - Commercial Passed 07/09/2002
Correction
Resolved
07/09/2002
None
Rough Plumbing Inspection - Commercial Passed 07/09/2002
Correction
Resolved
07/09/2002
None
Above Ceiling Inspection Failed 09/11/2002
Correction
Corrective Action Required
09/11/2002
OPEN J-BOX SEVERAL OPEN J-BOX ABOVE CEILING
Correction
Corrective Action Required
09/11/2002
PLUMBING SUPPORT SUPPORT PLUMBING VENTS PER IPC CODE REQUIREMENTS
Correction
Corrective Action Required
09/11/2002
SUPPORT CAN LIGHTS SUPPORT WIRES REQUIRED ON CAN LIGHTS
Correction
Corrective Action Required
09/11/2002
RATED WALL THE SOUTH WALL IS SHOWN AS A 1 HR WALL FIRE SAFEING OR SOME KIND OF MATERIAL REQUIRED TO SEAL THE TOP OF THE WALL AT THE DECK
Correction
Corrective Action Required
09/11/2002
RETURN AIR AT TIME OF INSPECTION R00M 106,108, 110 AND 113 HAVE NO RETURN AIR
Above Ceiling Inspection Passed 09/13/2002
Correction
Resolved
09/13/2002
OPEN J-BOX
Correction
Resolved
09/13/2002
PLUMBING SUPPORT
Correction
Resolved
09/13/2002
SUPPORT CAN LIGHTS
Correction
Resolved
09/13/2002
RATED WALL
Correction
Resolved
09/13/2002
RETURN AIR
Occupancy Inspection - Codes Commercial Failed 10/14/2002
Correction
Corrective Action Required
10/14/2002
ADDRESS PROVIDE ADDRESS AT BOTH WEST EXTERIOR DOORS.
Occupancy Inspection - Codes Commercial Passed 10/29/2002
Correction
Resolved
10/29/2002
ADDRESS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home