Summary
B0200356
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
ALTERATION COMMERCIAL
REMODELING CAFETERIA
03/12/2002
05/07/2002
11/03/2002
09/09/2002
Locations
Contacts
THE WEITZ COMPANY, L.L.C., Address:9900 WEST 109TH ST, SUITE 230  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/08/2002 10/29/2010
Correction

CA - 2000 IBC 1003.3.1.9 - Panic and fire exit hardware. Each door in a means of egress from an occupancy of Group A or E having an occupant load of 100 or more and any occupancy of Group H-1, H-2, H-3 or H-5 shall not be provided with a latch or lock unless it is panic hardware of fire exit hardware.
Correction

CA - Indicate on the plans the types of materials to be used in the plumbing and electric roughs.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1003.2.2.5 - Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - 2000 IPC 403.6 - Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. Public toilet facilities shall be located not more than one story above or below the space required to be provided with public toilet facilites and the path of travel to such facilities shall not exceed a distance of 500 feet.
Correction

CA - 2000 IPC 608.16.1 - Beverage dispensers. The water supply connection to carbonated beverage dispensers shall be protected against backflow by a double check valve with an intermediate atmospheric vent conforming to ASSE 1012 or ASSE 1022. The double check valve with an intermediate atmospheric vent device and the piping downstream therefrom shall not be affected by carbon dioxide gas. Secondary protection in the form of a dual check valve conforming to ASSE 1032 shall be installed on the beverage-dispensing equipment.
Correction

CA - 2000 IPC 802.1.1 - Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an inderect waste pipe by means of an air gap.
Correction

CA - 2000 IPC 802.2 - All indirect waste piping shall discharge through an air gap or air break into a waste receptor or standpipe. Waste receptors and standpipes shall be trapped and vented and shall connect to the building drainage system. All indirect waste piping that exceeds 2 feet in developed length measured horizontally, or 4 feet in total developed length, shall be trapped.
Correction

CA - 2000 IPC 312.1 - Required tests. The permit holder shall make the applicable test prescribed in Sections 312.2 through 312.9 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the code official when the plumbing work is ready for tests. The equipment, material, power and labor necessary for the inspection and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. All plumbing system piping shall be tested with either water or air. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be submitted to final tests. The code official shall require the removal of any cleanouts if necessary to ascertain if the pressure has reached all parts of the system. Note: Testing of the plumbing system is not required to be witnessed by the Codes Administration Staff with the exception of gas piping.
Correction

Fire Department: Fire detection, alarm and extinguishing systems shall be maintained in an op-erative condition at all times, and shall be replaced or repaired where defective.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal.
Correction

Fire Department- Per a phone call with Kenneth Bonin of Weitz Co., The ceiling above the project will be lowered creating a void space between it and the roof deck. The balconies and existing openings from the second floor apartments overlooking the space will be walled off by John Knox Village.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

A double check detector check valve assembly is required on the fire service line.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

Fire Department- Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems (hoods), fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Trap primers need to have an approved air gap ftting.
Correction

CA - Provide the calculations used to determine the non-seperated uses as is indicated in the code analysis on sheet A01.
Correction

CA - The code analysis on sheet A01 shows the construction type to be II-C. It would actually be II-B.
Correction

CA - Per table 302.1.1 of the 2000 IBC, storage rooms larger than 100 square feet are required to be seperated by one-hour fire-resistive construction with no exception for sprinkler systems. This would apply to storage room 104.
Correction

CA - Provide an exiting plan for the first floor. As the alterations actually divides the dining/pool area into to seperate areas, I need to see how the exiting for the unaltered area is planned.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

Fire Department; Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Combustible debris, waste materials and trash shall not be burned on site.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

1003.2.10.1 Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $2,702.00 $2,702.00 Paid 05/07/2002
24 BLDG Plan Check Fees $65.00 $65.00 Paid 05/07/2002
25 Electrical Permit Fee $115.00 $115.00 Paid 05/07/2002
25 Mechanical Permit Fees $106.00 $106.00 Paid 05/07/2002
25 Plumbing Permit Fees $246.00 $246.00 Paid 05/07/2002
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Partial 05/13/2002
Correction
Partial Correction
05/13/2002
None BANQUET ROOM NRTH WALL ONLY North
Underslab Plumbing Inspection - Commercial Partial 05/13/2002
Correction
Partial Correction
05/13/2002
None P1 - DINING ROOM - APPROVED. SUBMIT "AS BUILT" TO SHOW CHANGE.
Rough Framing Inspection - Commercial Partial 05/13/2002
Correction
Partial Correction
05/13/2002
None BANQUET WALLS, MINUS GLASSNBLOCK SECTION North
Rough Electrical Inspection - Commercial Partial 05/15/2002
Correction
Partial Correction
05/15/2002
IN-WALL ROUGH, PARTIAL IN-WALL IN ROOMS 106; 107; 110; 111; 113; 114; 115; 116; 118; 119; 120. IN-WALL COMPLETE IN THESE ROOMS THROUGHOUT DINING & BANQUET AREA EXCEPT SWITCH BANK @ E. WALL RM 117. MC STRANDED CABLE METALLIC BOXES
Underslab Plumbing Inspection - Commercial Partial 05/16/2002
Correction
Partial Correction
05/16/2002
None P1 SANITARY LINES APPROVED
Sewer Service Inspection Partial 05/23/2002
Correction
Partial Correction
05/23/2002
None 4" LINE OF SDR26 - 39` IN LENGTH. STARTING APPROXIMATELY 10` FROM FOUNDATION WALL & APPROXIMATELY 20` SHORT OF GREASE PIT SITE. [MIDDLE SECTION] APPROVED - COVER AT OWN RISK
Sewer Service Inspection Partial 05/28/2002
Correction
Partial Correction
05/28/2002
None APPROVED - EXCEPT FOR,TWO [2] UNDERGROUND FERNOCO TYPE FITTINGS.
Sewer Service Inspection Passed 05/29/2002
Correction
Resolved
05/29/2002
None
Underslab Electrical Inspection - Commercial Partial 05/30/2002
Correction
Partial Correction
05/30/2002
None CONDUIT SUFFICIENT FOR REQUIRMENTS OF SHEET E3. Kitchen
Rough Framing Inspection - Commercial Partial 05/30/2002
Correction
Partial Correction
05/30/2002
None BANQUET WALLS, MINUS GLASS BLOCK SECTION. 5-30-02 - SOFFIT IN BANQUET RM APPROVED - OK TO SHEETROCK SOFFIT. North
Rough Electrical Inspection - Commercial Partial 05/30/2002
Correction
Partial Correction
05/30/2002
None CAN LIGHTS APPROVED OKAY TO SHEETROCK SOFFIT IN BANQUET RM & CEILING IN LOUNGE BANQUET ROOM, LOUNGE SOFFIT
Above Ceiling Inspection Not Ready 06/03/2002
Correction
Corrective Action Required
06/03/2002
NOT READY NO INSPECTION DONE. CALL FOR REINSPECTION.
Above Ceiling Inspection Not Ready 06/04/2002
Correction
Corrective Action Required
06/04/2002
NOT READY
Above Ceiling Inspection Failed 06/05/2002
Correction
Corrective Action Required
06/05/2002
Framing SOFFIT AROUND PERIMETER RM 106 & 113 & 130 - BUILT WITH SPACING OF 2` OC VICE 16" AS PLANS REQUIRE. HAVE ENGINEER SUBMIT CHANGE REQUEST TO CITY PLANS EXAMINER. DO NOT SHEETROCK. 105,106,109,117,118 131,1
Correction
Corrective Action Required
06/05/2002
Electrical SUBMIT CHANGES ON "AS BUILT" - SWITCHES FROM SOUTH WALL ROOM 105 TO 117 & ROOM SPLIT INTO TWO [2] CIRCUITS 105,106,109,117,118
Correction
Resolved
06/05/2002
Mechanical 105, 106, 109,117,118
Rough Electrical Inspection - Commercial Partial 06/13/2002
Correction
Resolved
06/13/2002
None CAN LIGHTS COMPLETED EXCEPT FOR LAST LIGHT ON CIRCUIT IN HALLWAY 112 HALLWAY 110
Above Ceiling Inspection Failed 06/18/2002
Correction
Resolved
06/18/2002
None ROOM 115 - & CAN LIGHTS ON EAST/WEST SIDE.
Rough Framing Inspection - Commercial Failed 06/19/2002
Correction
Corrective Action Required
06/19/2002
NOT PER BLUEPRINTS FRAMING NOT ACCORDING TO APPROVED PLANS. THIS HAS IMPACTED WORK DONE BY OTHER TRADES. SUBMIT CHANGES TO CITY PLANS EXAMINER. Kitchen, Rm108,122,129
Above Ceiling Inspection Partial 06/20/2002
Correction
Resolved
06/20/2002
Framing 105,106,109,117,118 131, 103
Correction
Resolved
06/20/2002
Electrical SUBMIT CHANGES ON "AS BUILT" - SWITCHES FROM SOUTH WALL ROOM 105 TO 117 & ROOM SPLIT INTO TWO [2] CIRCUITS 105,106,109,117,118
Rough Framing Inspection - Commercial Partial 06/20/2002
Correction
Resolved
06/20/2002
NOT PER BLUEPRINTS CMU WALL SUBSTITUTION APPROVED ALL TRADE WORK IN FURRED ATEAS APPROVED OK TO COVER Kitchen, Rm108,122,129
Correction
Partial Correction
06/20/2002
None
Above Ceiling Inspection Partial 06/24/2002
Correction
Resolved
06/24/2002
NOT READY
Correction
Resolved
06/24/2002
NOT READY
Correction
Partial Correction
06/24/2002
None LOBBY ONLY ABOVE CEILING SYSTEMS OK TO COVER LOBBY
Above Ceiling Inspection Partial 07/16/2002
Correction
Resolved
07/16/2002
None RM 106/107 OK TO LAY TILE
Above Ceiling Inspection Partial 08/16/2002
Correction
Resolved
08/16/2002
None LOBBY
Correction
Partial Correction
08/16/2002
None KITCHEN, EXCEPT DRY STORAGE, TOILET, ELECTRICAL & CONNECTING VESTIBULE.
Above Ceiling Inspection Partial 08/19/2002
Correction
Partial Correction
08/19/2002
None KITCHEN, EXCEPT DRY STORAGE, TOILET, ELECTRICAL & CONNECTING VESTIBULE. 8-19-02 NOT COMPLETED. WILL INSPECTMDURING FINAL.
Above Ceiling Inspection Passed 08/20/2002
Correction
Resolved
08/20/2002
None
Occupancy Inspection - Codes Commercial Failed 08/20/2002
Correction
Corrective Action Required
08/20/2002
EXIT SIGNAGE INSTALL EXIT SIGN AT RESIDENCE HALLWAY (NORTH) LEADING INTO FOYER.
Correction
Corrective Action Required
08/20/2002
OCCUPANT LOAD SIGNAGE POST OCCUPANT LOAD SIGNAGE IN ROOMS 105, 106 & 107.
Correction
Corrective Action Required
08/20/2002
KITCHEN INCOMPLETE COMPLETE KITCHEN WORK. KITCHEN NOT FULLY INSPECTED AS NOT COMPLETED. KITCHEN APPROVED TO STOCK. KITCHEN NOT TO BE USED FOR FOOD PREPARATION UNTIL APPROVED. HOOD AND EQUIPMENT HAS NOT BEEN TESTED.
Correction
Corrective Action Required
08/20/2002
Receive Fire Department approval UNDER SEPARATE COVER
Correction
Corrective Action Required
08/20/2002
Receive Water Utilities Approval SUBMIT ALL BACKFLOW TEST REPORTS TO WATER UTILITIES.
Above Ceiling Inspection Passed 08/20/2002
Correction
Resolved
08/20/2002
None RECEIVED E-MAIL FROM MARK DUNNING. AREAS INSPECTED AND APPROVED
Underslab Plumbing Inspection - Commercial Passed 08/21/2002
Correction
Resolved
08/21/2002
None
Underslab Electrical Inspection - Commercial Passed 08/21/2002
Correction
Resolved
08/21/2002
None Kitchen
Rough Framing Inspection - Commercial Passed 08/21/2002
Correction
Resolved
08/21/2002
None
Rough Plumbing Inspection - Commercial Passed 08/21/2002
Rough Mechanical Inspection - Commercial Passed 08/21/2002
Rough Electrical Inspection - Commercial Passed 08/21/2002
Correction
Resolved
08/21/2002
None BANQUET ROOM NRTH WALL ONLY North
Correction
Resolved
08/21/2002
IN-WALL ROUGH, PARTIAL IN-WALL IN ROOMS 106; 107; 110; 111; 113; 114; 115; 116; 118; 119; 120. IN-WALL COMPLETE IN THESE ROOMS THROUGHOUT DINING & BANQUET AREA EXCEPT SWITCH BANK @ E. WALL RM 117. MC STRANDED CABLE METALLIC BOXES
Correction
Resolved
08/21/2002
None CAN LIGHTS APPROVED OKAY TO SHEETROCK SOFFIT IN BANQUET RM & CEILING IN LOUNGE BANQUET ROOM, LOUNGE SOFFIT
Above Ceiling Inspection Passed 08/21/2002
Occupancy Inspection - Codes Commercial Failed 08/21/2002
Correction
Resolved
08/21/2002
OCCUPANT LOAD SIGNAGE
Correction
Corrective Action Required
08/21/2002
KITCHEN INCOMPLETE INDIRECT WASTE LINES SHALL TERMINATE ABOVE THE FLOOD LEVEL RIM OF FLOOR SINKS A MINIMUM OF 1 INCH. (SINK ALONG WEST WALL/SINK ADJACENT TO SODA DISPENSER/THREE COMPARTMENT SINK)
Correction
Corrective Action Required
08/21/2002
HOOD SYSTEMS SEAL HOLES IN EXISTING HOOD SYSTEM RE-WELD NEW HOODS WEST PANEL TO HOOD EXHAUST TROUGH (WELD NOT COMPLETED) MOVE LIGHT SWITCH FROM UNDER WEST HOOD TO DIFFERENT WALL OR WIRE SO THAT WHEN SUPPRESSION SYSTEM ACTIVATES, POWER IS TERMINATED.
Correction
Resolved
08/21/2002
EXIT SIGNAGE
Occupancy Inspection - Codes Commercial Passed 09/06/2002
Correction
Resolved
09/06/2002
KITCHEN INCOMPLETE
Correction
Resolved
09/06/2002
Receive Fire Department approval UNDER SEPARATE COVER
Correction
Resolved
09/06/2002
Receive Water Utilities Approval SUBMIT ALL BACKFLOW TEST REPORTS TO WATER UTILITIES.
Correction
Resolved
09/06/2002
HOOD SYSTEMS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home