Summary
B0200230
Building Permit - Commercial
Certificate of Occupancy
CP DEER BROOK PLAZA LLC
CHANGE OF TENANT
CHANGE OF TENANT FINISH
02/19/2002
04/15/2002
10/12/2002
08/29/2002
Locations
Contacts
PURDUM CONSTRUCITON, Address:400 E. RED BRIDGE RD,STE. 106  
CP DEER BROOK PLAZA LLC, Address:3400 COLLEGE BLVD STE 195  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/18/2002 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - Service outlets must be placed within 25' of all equipment per 1999 NEC, Section210-63.
Correction

CA - Clarify what type of wiring method will be used.
Correction

CA - The correct occupancy classification for this tenant space is B per the 2000 International Building Code.
Correction

CA - The correct type of constuction for this tenant space is V-B per the 2000 International Building Code.
Correction

CA - Clarify what the adjacent occupancies are if any.
Correction

Fire Department: Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal.
Correction

Fire Department: Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department; Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Combustible debris, waste materials and trash shall not be burned on site.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IPC 312.1 - Required tests. The permit holder shall make the applicable test prescribed in Sections 312.2 through 312.9 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the code official when the plumbing work is ready for tests. The equipment, material, power and labor necessary for the inspection and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. All plumbing system piping shall be tested with either water or air. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be submitted to final tests. The code official shall require the removal of any cleanouts if necessary to ascertain if the pressure has reached all parts of the system. Note: Testing of the plumbing system is not required to be witnessed by the Codes Administration Staff with the exception of gas piping.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

The existing backflow prevention assembly must be shown on plumbing plans.
Correction

Backflow prevention assembly will be placed inside the building on the domestic water service line prior to any point of use.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $752.00 $752.00 Paid 04/15/2002
24 BLDG Plan Check Fees $32.50 $32.50 Paid 04/15/2002
25 Electrical Permit Fee $160.00 $160.00 Paid 04/15/2002
25 Mechanical Permit Fees $82.50 $82.50 Paid 04/15/2002
25 Plumbing Permit Fees $188.00 $188.00 Paid 04/15/2002
89 Sewer Tap Fees $270.00 $270.00 Paid 04/15/2002
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 04/24/2002
Correction
Resolved
04/24/2002
None APPROVED IF ON-SITE DRAWINGS COINCIDE WITH APPROVED DRAWINGS.
Miscellaneous Inspection Partial 05/09/2002
Correction
Partial Correction
05/09/2002
None IN-WALL APPROVED EXCEPT FOR OFFICE 152.
Miscellaneous Inspection Passed 05/15/2002
Correction
Resolved
05/15/2002
None IN-WALL ELECTRIC, FRAMING & TOP ROUGH APPROVED. ABOVE CEILING MECHANICAL APPROVED.
Rough Electrical Inspection - Commercial Partial 05/28/2002
Correction
Partial Correction
05/28/2002
None PHASE I SVC. PANEL RELOCATION APPROVED.
Rough Mechanical Inspection - Commercial Partial 06/04/2002
Correction
Partial Correction
06/04/2002
Terminate thermostat conductors - office 160.
Correction
Partial Correction
06/04/2002
Terminate duct connectors at drop-in diffusers
Rough Electrical Inspection - Commercial Partial 06/04/2002
Correction
Partial Correction
06/04/2002
None PHASE I SVC. PANEL RELOCATION APPROVED.
Correction
Partial Correction
06/04/2002
None COMPLETE JUNCTION BOX ABOVE REAR EXIT CORRIDOR. OK TO DROP TILE IN OPEN AND OTHER OFFICES AND RESTROOMS.
Occupancy Inspection - Codes Commercial Failed 06/07/2002
Correction
Corrective Action Required
06/07/2002
SEE TEXT 1163 AND 1165 SPACES ONLY NO OTHER SCOPE OF WORK INSPECTED 1. EGRESS SIGNAGE TO BE INSTALLED AT WEST ASPECT 2. RELABEL/REMOVE NONUTILIZED ADDRESS NUMBERS FRONT/REAR 3. REMOVE SLIDE BOLT REAR DOOR 4. COMPLETE RESTROOM FIXTURES
Correction
Partial Correction
06/07/2002
Receive Fire Department approval COMPLETE SPRINKLER AND ALARM REQUIREMENTS
Rough Electrical Inspection - Commercial Partial 06/21/2002
Correction
Partial Correction
06/21/2002
None PHASE II APPROVED.
Rough Framing Inspection - Commercial Partial 06/21/2002
Correction
Partial Correction
06/21/2002
None PHASE II APPROVED.
Above Ceiling Inspection Partial 06/28/2002
Correction
Partial Correction
06/28/2002
None Rough mechanical approved.
Above Ceiling Inspection Partial 07/19/2002
Correction
Partial Correction
07/19/2002
None Rough mechanical approved.
Correction
Corrective Action Required
07/19/2002
Remove or cover insulation facing.
Correction
Corrective Action Required
07/19/2002
Stop installing/bringing in furniture.
Occupancy Inspection - Codes Commercial Failed 07/23/2002
Correction
Corrective Action Required
07/23/2002
SEE TEXT 1153 AND 1161 SPACES ONLY NO OTHER SCOPE OF WORK INSPECTED 1. RELABEL/REMOVE NONUTILIZED ADDRESS NUMBERS FRONT/REAR 2. REMOVE SLIDE BOLT REAR DOOR 3. COMPLETE RESTROOM FIXTURES
Correction
Partial Correction
07/23/2002
Receive Fire Department approval COMPLETE SPRINKLER AND ALARM REQUIREMENTS COMPLETE EGRESS REQUIREMENTS
Rough Electrical Inspection - Commercial Partial 08/02/2002
Correction
Partial Correction
08/02/2002
None PHASE III APPROVED.
Above Ceiling Inspection Passed 08/19/2002
Correction
Resolved
08/19/2002
None Rough mechanical approved.
Correction
Resolved
08/19/2002
None PHASES I - III APPROVED.
Occupancy Inspection - Codes Commercial Failed 08/23/2002
Correction
Resolved
08/23/2002
SEE TEXT
Correction
Corrective Action Required
08/23/2002
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Passed 08/27/2002
Correction
Resolved
08/27/2002
Receive Fire Department approval
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home