Summary
B0200042
Building Permit - Commercial
Certificate of Occupancy
VILLE 36 INVESTMENT COMPANY LLC
NEW TENANT FINISH
NEW TENANT FINISH
01/10/2002
03/06/2002
09/02/2002
04/29/2002
Locations
Contacts
MARCO CONTRACTORS INC, Address:100 COMMONWEALTH DRIVE  
VILLE 36 INVESTMENT COMPANY LLC, Address:4740 ROANOKE PKWY  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/09/2002 10/29/2010
Correction

CA - All piping shall be supported in accordance with section 308 of the 2000 IPC.
Correction

CA - 2000 IPC - Drinking fountains shall conform to ASME A112.19.1, ASME A 112.19.2 or ASME A 112.19.9, and water coolers shall conform to ARI 1010. Where water is served in restaurants or where bottled water coolers are provided in other occupancies, drinking fountains shall not be required.
Correction

CA - 200 IPC 504.3 - A means of disconnecting an electric hot water supply system from its energy supply shall be provided in accordance with the 1999 National Electric Code. A seperate valve shall be provided to shut off the energy fuel supply to all other types of hot water supply systems.
Correction

A Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior the press unit.
Correction

Fire Department; Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not a high-hazard occupancy; and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit access shall not pass though a room which can be locked to prevent egress. IFC 1004.2.3
Correction

Fire Department; Valve supervision and water flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA72 or, when approved by the code official, shall sound an audible signal at a constantly attended location.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal.
Correction

Fire Department: Fire detection, alarm and extinguishing systems shall be maintained in an op-erative condition at all times, and shall be replaced or repaired where defective.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1004.2.3 - Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not a high hazard ocupancy; and provide a discernible path of agress travel to an exit. Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit access shall not pass through a room that can be locked to prevent egress. Means of egress from dwelling units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms.
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised when the number of sprinkler heads are 20 (twenty) or greater.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IPC 403.6 - Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. Public toilet facilities shall be located not more than one story above or below the space required to be provided with public toilet facilites and the path of travel to such facilities shall not exceed a distance of 500 feet.
Correction

CA - 2000 IPC 606.2 - Shutoff valves shall be installed in the following locations: 1. On the fixture supply to each plumbing fixture in other than one- and two-family residential occupancies, and other than in individual guestrooms that are provided with unit shutoff valves in hotels, motels, boarding houses and similar occupancies. 2. On the water supply line to each sillcock. 3. On the water supply pipe to each appliance or mechanical equipment.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

A note should be provided indicating a Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior to any point of use.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $143.00 $143.00 Paid 03/06/2002
24 BLDG Plan Check Fees $13.75 $13.75 Paid 03/06/2002
25 Electrical Permit Fee $84.00 $84.00 Paid 03/06/2002
25 Mechanical Permit Fees $60.00 $60.00 Paid 03/06/2002
25 Plumbing Permit Fees $25.00 $25.00 Paid 03/06/2002
89 Sewer Tap Fees $120.00 $120.00 Paid 03/06/2002
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Partial 03/19/2002
Correction
Partial Correction
03/19/2002
None IN WALL ELECTRICAL SUBSTANTIALLY COMPLETED OK TO COVER
Underslab Plumbing Inspection - Commercial Passed 03/19/2002
Rough Electrical Inspection - Commercial Partial 03/25/2002
Rough Electrical Inspection - Commercial Partial 03/29/2002
Rough Framing Inspection - Commercial Passed 03/29/2002
Rough Plumbing Inspection - Commercial Passed 03/29/2002
Gas Piping Inspection - Commercial Passed 04/11/2002
Gas Service Inspection - Commercial Passed 04/11/2002
Above Ceiling Inspection Partial 04/17/2002
Correction
Partial Correction
04/17/2002
None ABOVE CEILING SYSTEMS SAKES FLOOR ONLY SUBSTANTIALLY COMPLETED 1 SUPPORT LIGHTING STRIP FIXTURES OK TO LAY TILE AFTER HYDRO APPROVAL
Occupancy Inspection - Codes Commercial Passed 04/25/2002
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents