Summary
B0101758
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
BASEBALL NORTH CONCESSION/RESTROOMS
10/11/2001
11/14/2001
05/13/2002
01/28/2003
Locations
Contacts
MERIT GENERAL CONTRACTING, Address:950 KANSAS AV  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/09/2002 10/29/2010
Correction

WU - All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816- 969-7636) within 30 days from the date installed.
Correction

CA - Submit the truss package prior to erection of the trusses for review and approval.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - 2000 IBC 1704.1.2 - Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and the registered design professional in responsible charge prior to the completion of that phase of the work. A final report of inspections documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted periodically at a frequency agreed upon by the permit applicant and the building official prior to the start of work.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department; Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Combustible debris, waste materials and trash shall not be burned on site.
Correction

Fire Department; Dumpsters and containers with an individual capacity of 1.5 cubic yards (40.5 cubic feet) or more shall not be stored in buildings or placed within 5 feet of combustible walls, openings or combustible roof eave lines.
Correction

Fire Derpartment; When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,187.00 $1,187.00 Paid 11/14/2001
24 BLDG Plan Check Fees $39.75 $39.75 Paid 11/14/2001
25 Electrical Permit Fee $919.62 $919.62 Paid 11/14/2001
25 Mechanical Permit Fees $36.50 $36.50 Paid 11/14/2001
25 Plumbing Permit Fees $159.00 $159.00 Paid 11/14/2001
89 Sewer Tap Fees $900.00 $900.00 Paid 11/14/2001
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Plumbing Inspection - Commercial Partial 03/15/2002
Correction
Partial Correction
03/15/2002
TYPE YOUR OWN TEXT IN-WALL ROUGH DWV & WATER CENTRAL CHASE
Underground Plumbing Inspection - Commercial Partial 03/22/2002
Correction
Partial Correction
03/22/2002
WATER LINES TO D.F.'s: PARTIAL PER A/E CHANGE DOC ON-SITE, 3/4" HDPE IN LIEU OF COPPER; METALLIC TRACER TAPE; 18" BURY PER A/E BASEBALL BLDG TO FIELDS E & N
Underground Electrical Inspection - Commercial Failed 03/27/2002
Correction
Corrective Action Required
03/27/2002
UNSATISFACTORY REPAIR FEEDER CABLE CONDUIT RUNNING FROM PANELS IN RM 103 EAST TO FIELDS BB5-BB8. 3" LOCATION 4/C.5. CONDUIT WAS DAMAGED EARLIER; NOW BEING REPAIRED. E.C. 4MAN STATES CABLE INTEGITY HAS BEEN VERIFIED BY MEG TEST. CONDUIT REPAIR NOT APPROVED. NOT WATER TIGHT. FEEDER CABLE CONDUIT NORTH BASEBALL CONCESSION
Underground Plumbing Inspection - Commercial Passed 03/29/2002
Correction
Resolved
03/29/2002
None Water supplies.
Correction
Resolved
03/29/2002
WATER LINES TO D.F.'s: PARTIAL PER A/E CHANGE DOC ON-SITE, 3/4" HDPE IN LIEU OF COPPER; METALLIC TRACER TAPE; 18" BURY PER A/E BASEBALL BLDG TO FIELDS E & N
Underground Electrical Inspection - Commercial Failed 04/04/2002
Correction
Corrective Action Required
04/04/2002
UPDATE: CONDUIT REPAIR EARLIER CONDUIT REPAIR HAS BEEN ENCASED. HOWEVER, FLEX CONDUIT HAS SUBSEQUENTLY BEEN BROKEN 24" WEST OF ENCASEMENT. *** DUE TO POSSIBLE DAMAGE, CABLES MUST BE INSPECTED AND APPROVED PRIOR TO COVERING THIS NEWLY REQUIRED REPAIR *** BASEBALL NO. BLDG SAME AS 3/27/02 REPORT
Underground Electrical Inspection - Commercial Failed 04/04/2002
Correction
Corrective Action Required
04/04/2002
CABLE SHEATHS DAMAGED 2' W. OF ENCASEMENT
Underground Electrical Inspection - Commercial Passed 04/05/2002
Correction
Resolved
04/05/2002
UPDATE: CONDUIT REPAIR EARLIER CONDUIT REPAIR HAS BEEN ENCASED. HOWEVER, FLEX CONDUIT HAS SUBSEQUENTLY BEEN BROKEN 24" WEST OF ENCASEMENT. *** DUE TO POSSIBLE DAMAGE, CABLES MUST BE INSPECTED AND APPROVED PRIOR TO COVERING THIS NEWLY REQUIRED REPAIR *** BASEBALL NO. BLDG SAME AS 3/27/02 REPORT
Correction
Resolved
04/05/2002
CABLE SHEATHS DAMAGED PULLING SURFACE DAMAGE TO JACKET DOES NOT APPEAR TO AFFECT INTEGRITY OF CONDUCTORS. BROKEN SECTION OF FLEX CONDUIT HAS BEEN REPLACED W/ SPLIT RIGID CONDUIT. E.C. IS TO DIG & CLEAN AROUND THIS AREA; THEN ENCASE W/ CONCRETE. OK TO PROCEED W/ ENCASEMENT. 2' W. OF ENCASEMENT
Correction
Resolved
04/05/2002
UNSATISFACTORY REPAIR FEEDER CABLE CONDUIT RUNNING FROM PANELS IN RM 103 EAST TO FIELDS BB5-BB8. 3" LOCATION 4/C.5. CONDUIT WAS DAMAGED EARLIER; NOW BEING REPAIRED. E.C. 4MAN STATES CABLE INTEGITY HAS BEEN VERIFIED BY MEG TEST. CONDUIT REPAIR NOT APPROVED. NOT WATER TIGHT. FEEDER CABLE CONDUIT NORTH BASEBALL CONCESSION
Above Ceiling Inspection Failed 04/17/2002
Correction
Corrective Action Required
04/17/2002
Complete water supply.
Correction
Corrective Action Required
04/17/2002
TYPE YOUR OWN TEXT CONNECT TRUSSES TO STEEL ANGLES AT TOWER WALL.
Above Ceiling Inspection Passed 04/24/2002
Correction
Resolved
04/24/2002
Complete water supply.
Correction
Resolved
04/24/2002
TYPE YOUR OWN TEXT
Electrical Service Inspection Passed 04/30/2002
Correction
Resolved
04/30/2002
NONE>> RELEASE SERVICE ONE GROUND CONNECTION YET TO BE COMPLETED. E.C. HAS MATERIAL ON ORDER. 1600 AMP MAIN DISCONNECT DRWG SHEETS E-BN.1- .5
Underslab Plumbing Inspection - Commercial Passed 01/27/2003
Foundation Inspection - Commercial Passed 01/27/2003
Rough Electrical Inspection - Commercial Passed 01/27/2003
Occupancy Inspection - Codes Commercial Passed 01/27/2003
Underslab Electrical Inspection - Commercial Passed 01/27/2003
Rough Framing Inspection - Commercial Passed 01/27/2003
Rough Plumbing Inspection - Commercial Partial 01/27/2003
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home