Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
04/29/2002
|
10/29/2010
|
|
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
P&D - Accessible Parking
|
|
Correction
P&D - Screening of Mechanical Equipment
|
|
Correction
PW - Contact Public Works Inspection at 969-7450 to obtain necessary infrastructure permits and inspection fees prior to start of construction.
|
|
Correction
PW - Contact Public Works Inspection at 969-7450 24-hours prior to the anticipated commencement of construction.
|
|
Correction
PW - Contact Barton Reese, Erosion Control Specialist, at 969-7951 for erosion control installation approval and prior to land disturbance.
|
|
Correction
PW - Please submit three (3) sets of revised civil site plans to Public Works Engineering containing the information necessary to address the Water Utilities and the Public Works Engineering Departments comments.
|
|
Correction
PW - Provide a copy of the Land Disturbance Permit application and the required attachments to the Erosion Control Specialist prior to any land disturbance activities that are to occur prior to obtaining a building permit.
|
|
Correction
PW - Resubmit the storm water calculations. They should include the inlet/outlet control conditions.
|
|
Correction
PW - Provide the correct fall across inverts as described in Article IV Section B. 11. c. of City Ordinance No. 3719. This ordinance requires a minimum fall for the invert through the structures of 0.2 feet for straight flow through the structures, or 0.5 feet fall for all other types of flow (bends more than 22.5 deflection angle, multiple lines entering, enlargement transition, etc.).
|
|
Correction
PW - Provide a concrete low flow channel for the detention area.
|
|
Correction
PW - Indicate CG-1 concrete curb and gutter or an integral concrete sidewalk and curb with a vertical face at all edges of proposed parking areas and driveways, constructed in compliance with the City's standard detail SD-15 from City Ordinance No. 3719.
|
|
Correction
PW - Resubmit the storm sewer pipe schedule. There is conflicting pipe lengths with the storm sewer plan and profile.
|
|
Correction
WU - Any public fire hydrant should be painted optic yellow and a private fire hydrant should be painted optic yellow on the the barrell with a bright silver bonnet.
|
|
Correction
WU - The location of the Fire Department Connection (FDC) must be shown on the site plan.
|
|
Correction
WU - All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816- 969-7636) within 30 days from the date installed.
|
|
Correction
WU - Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
|
|
Correction
WU - All purposed hose bibb connections must have an approved (vacuum breaker) backflow preventer.
|
|
Correction
Codes Admin. - All ramps located in an accessible route of travel must comply with the 1991 Uniform Building Code, Chapter 33 and 1986 ANSI A 117.1.
|
|
Correction
Codes Admin. - Identify how the gas piping will be supported. Provide a detail.
|
|
Correction
Codes Admin. - Doors numbered 135-B and 128-A must be on a fusilbe link. These doors must close when needed to complete the occupancy seperation required by code. Please Clarify.
|
|
Correction
Fire Department- Fire-protection equipment and fire hydrants shall be clearly identified in a manner approved by the chief to prevent obstruction by parking and other obstructions. (UFC Section 10.105b)
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
Correction
Fire Department- Provide "Knox Box Entry System". When access to or within a structure or an area is unduly difficult because of secured openings or where immediate access is necessary for life-saving or firefighting purposes, the chief is authorized to require a key box to be installed in an accessible location. The key box shall be a type approved by the chief and shall contain keys to gain necessary access as required by the chief. (UFC 10.302)
|
|
Correction
Fire Department- A fire hydrant painted yellow is required to be located within 50 feet of the fire department connection to the sprinkler system. (UFC 10.401.)
|
|
Correction
Fire Department- When fire protection, including fire apparatus access roads and water supplies for fire protection, is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction. UFC 10.502
|
|
Correction
Fire Department- The duct detectors when activated shall be received at the panel and alarm company as a trouble alarm. (UFC Section 10.503.)
|
|
Correction
Fire Department- A set of sprinkler plans and specifications bearing a State of Missouri licensed engineers seal, shall be submitted to the Fire Department for review and approval prior to construction (system modification). (1991 Uniform Fire Code, Section 10.503)
|
|
Correction
Fire Department- Fire alarm systems; fire hydrant systems; fire-extinguishing systems, including automatic sprinklers and wet and dry standpipes; halon systems and other automatic fire-extinguishing systems shall meet the approval of the fire department as to installation and locations and shall be subject to acceptance testing and such periodic testing as required by the chief. NOTE: Acceptance testing may scheduled at least 48 hours in advance by calling 969-7343. UFC 10.503
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
Correction
Fire Department- All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised when the number of sprinkler heads are one-hundred or more. Valve supervision and water-flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote station or proprietary supervising station as defined by national standards. UFC 10.508
|
|
Correction
Fire Department- Dumpsters and containers with an individual capacity of 1.5 cubic yards (40.5 cubic feet) or more shall not be stored in buildings or placed within 5 feet of combustible walls, openings or combustible roof lines. (UFC Section 11.302.(b))
|
|
Correction
Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
|
|
Correction
Fire Department- A completed hazardous materials permit application shall be submitted to the Lee's Summit fire department. (UFC Section 4.103 and UFC Section 80.103.(a))
|
|
Correction
Fire Department- The chief is authorized to require warning signs for the purpose of pointing out the hazards of storing flammable liquids. UFC Section 79.109.(a)
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
Correction
Codes Administration- Erosion control shall be provided in conformance with Article VIII, Section VIII(c) & (d) and details 48 and 48A of the City of Lee's Summit Design and Construction Manual. Erosion control devices shall be installed and maintained during all phases of the construction process. Failure to provide or maintain erosion control may result in an issuance of a stop work order which is authorized by Article I, Section XXIV.
|
|
Correction
Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
Correction
P&D - Site Plan Approval - This approval is for the first phase only including the 44,487 sq ft office warehouse building and associated parking only. The future building and associated parking/site improvements require a final site plan to be submitted and approved prior to any future building permit being issued.
|
|
Correction
P&D - Parking Waiver
|
|
Correction
P&D - FAA approval required.
|
|
Correction
P&D - Horizontal Offsets -
|
|
Correction
P&D - Colors
|
|
Correction
P&D - Screening of loading and parking area.
|
|
Correction
P&D - Adjacent Right of Way information
|
|
Correction
P&D - Parking
|
|
Correction
Fire Department- Electrical service in the H3 rooms and to the spray booths and ovens shall be in accordance wth UFC Article 45 and the Electrical Code.
|
|
Correction
Fire Department- The spray booths used for spray application of flammable finishes shall be installed and maintained in accordance with Uniform Fire Code, Article 45. Details on the ventilation for the booths and ovens shall be provided to Codes Administration and the Fire Department for review. When required interlocks shall be provided. Fire suppression shall also be extended into the booths. Please provide specification information on the booths for review.
|
|
Correction
Fire Department- Standpipes (hose connections) shall be provided at doors 100, 127A, 127C, 128E and 135E.
The standpipes can be part of the automatic sprinkler system. All valves shall be 2 1/2 inch NST.
|
|
Correction
Fire Department- Complete plans and specifications for fire alarm systems shall be submitted for review and approval prior to system installation. (UFC Section 14.103.(a))
|
|
Correction
Fire Department- An interior door is recommended from the sprinkler room to the interior space. If a door is provided, the standpipe connection that was originally needed at door 128 E may be relocated to the sprinkler room.
|
|
Correction
Fire Department- The rooms designated as H3 occupancies shall be constructed per UBC. The storage of flammable and combustible liquids in these rooms shall comply with UFC Article 79.
|
|
Correction
Codes Admin. - All plumbing, mechanical and electrical penetrations through occupancy seperation walls must be properly fire stopped. Provide details for these penetrations if applicable.
|
|
Correction
PW - Provide a pipe flared-end section with a toewall at the detention outlet.
|
|
|