Summary
B0100732
Building Permit - Commercial
Certificate of Occupancy
JUNIOR COLLEGE DISTRICT OF
ADDITION COMMERCIAL
BUILDING ADDITION
05/03/2001
07/18/2001
01/14/2002
11/27/2002
Locations
Contacts
JE DUNN CONSTRUCITON CO, Address:929 HOLMES  
JE DUNN CONSTRUCITON CO, Address:929 HOLMES  
JUNIOR COLLEGE DISTRICT OF, Address:3200 BROADWAY  
JUNIOR COLLEGE DISTRICT OF METRO KC MO, Address:3200 BROADWAY  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/30/2001 10/29/2010
Correction

PW - Indicate that street, storm sewers, sanitary sewers and waterlines shall be constructed in accordance with the City of Lee's Summit Design and Construction Manual, Ord. 3719.
Correction

PW - Indicate CG-1 concrete curb and gutter or an integral concrete sidewalk and curb with a vertical face at all edges of proposed parking areas and driveways, constructed in compliance with the City's standard detail SD-15 from City Ordinance No. 3719.
Correction

PW - Provide storm water calculations for the proposed system. These calculations should include the impact of the additional flow into the existing public storm sewer system. The storm calculations must be sized assuming the entire drainage area will be fully developed. A licensed Professional Engineer registered in the State of Missouri must sign and seal the storm water calculations.
Correction

PW - Provide a plan and profile for the storm sewer improvements.
Correction

Fire Department- The duct detectors when activated shall be received at the panel and alarm company as a trouble alarm. (UFC Section 10.503.)
Correction

Fire Department- A set of sprinkler plans and specifications bearing a State of Missouri licensed engineers seal, shall be submitted to the Fire Department for review and approval prior to construction (system modification). (1991 Uniform Fire Code, Section 10.503)
Correction

Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
Correction

Fire Department- Complete plans and specifications (bearing an State of Missouri architects /engineers seal) for fire alarm systems shall be submitted for review and approval prior to system installation. (UFC Section 14.103.(a))
Correction

Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
Correction

P & D - All exterior lighting, whether on poles or buildings, shall be of such types and so arranged that no light source is visible from adjacent properties and public right-of-way.
Correction

P & D - If exterior lighting is proposed, a lighting plan, including the manufacturer's specifications on all lights proposed must be submitted and approved by the Department of Planning & Development.
Correction

Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
Correction

Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

PW - Contact Public Works Inspection at 969-7450 to obtain necessary infrastructure permits and inspection fees prior to start of construction.
Correction

PW - Contact Public Works Inspection at 969-7450 24-hours prior to the anticipated commencement of construction.
Correction

PW - Contact Barton Reese, Erosion Control Specialist, at 969-7951 for erosion control installation approval and prior to land disturbance.
Correction

PW - Please submit three (3) sets of revised civil site plans to Public Works Engineering containing the information necessary to address the Water Utilities and the Public Works Engineering Departments comments.
Correction

PW - Provide a copy of the Land Disturbance Permit application and the required attachments to the Erosion Control Specialist prior to any land disturbance activities that are to occur prior to obtaining a building permit.
Correction

PW - Submit proposed contours.
Correction

Fire Department- When any portion of the facility or building protected is in excess of 300 feet from a water supply on a public street, as measured by an approved route around the exterior of the building, on-site fire hydrants and mains capable of supplying the adequate fire flow shall be provided. (UFC 10.401. as amended by LSMO Ord. 3772.)
Correction

Fire Department- Fire alarm systems; fire hydrant systems; fire-extinguishing systems, including automatic sprinklers and wet and dry standpipes; halon systems and other automatic fire-extinguishing systems shall meet the approval of the fire department as to installation and locations and shall be subject to acceptance testing and such periodic testing as required by the chief. NOTE: Acceptance testing may scheduled at least 48 hours in advance by calling 969-7343. UFC 10.503
Correction

Fire Department- Fire-protection or extinguishing system coverage, spacing and specifications shall be maintained accordance with recognized standards at all time. Such systems shall be extended, altered or augmented as necessary to maintain and continue protection whenever any building so equipped is altered, remondeled or added to. Additions, repairs, alterations and servicing shall be in accordance with recognized standards. UFC Section 10.504(a)
Correction

Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
Correction

Fire Department- Exit illumination shall be provided and maintained in accordance with the Building Code. Exits shall be illuminated when the building or structure is occupied. Equipment providing emergency power for exit illumination and exit signs shall be maintained in an operable condition. (UFC Section 12.110)
Correction

Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practical. Combustible debris, waste material and trash shall not be burned on site. (UFC Section 87.103.(e))
Correction

Fire Department- During construction fire department access shall be maintained and not obstructed. UFC Section 87.103.(b)
Correction

Fire Department- During construction required exit components shall be maintained. UFC Section 87.101.(c)
Correction

P & D - All access drives and parking areas shall be constructed with straight-back (Type CG-1) concrete curbing.
Correction

P & D - Parking lot lights shall be of the metal halide variety with a total cut-off of light at an angle of less than 90 degrees (measured from the vertical).
Correction

P & D - Parking, including curbs, must be installed prior to occupancy.
Correction

P & D - Sign permits must be obtained for all exterior business related signs prior to installation. All signs shall comply with the sign requirements outlined in Ord. 715, Sec. 350. Contact the Planning and Development Department at 816-969-7317 for details.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - If proposed, each accessible parking space shall be identified by a sign, mounted between 3 and 5 feet above the parking surface, at the head of the parking space. The sign shall be at least 12" x 18" in area and meet the requirements set forth in the manual on Uniform Traffic Control Devices, as referenced in Section 29-381 of the Lee's Summit General Code of Ordinances (sign type R7-8D)
Correction

P & D - All exterior trash storage containers shall be screened as shown on the approved site plan.
Correction

Codes Admin. - Per the 1991 Uniform Building Code, Section 3207 (c) the overflow drains must be independent of the roof drains.
Correction

Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $7,715.00 $7,715.00 Paid 07/18/2001
24 BLDG Plan Check Fees $148.55 $148.55 Paid 07/18/2001
25 Electrical Permit Fee $562.50 $562.50 Paid 07/18/2001
25 Mechanical Permit Fees $157.50 $157.50 Paid 07/18/2001
25 Plumbing Permit Fees $104.00 $104.00 Paid 07/18/2001
89 Sewer Tap Fees $120.00 $120.00 Paid 07/18/2001
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Above Ceiling Inspection Failed 02/20/2002
Correction
Partial Correction
02/20/2002
NONE HARD CEILING AREA OUTSIDE OF ROOM 122 OK TO HANG SHEETROCK
Miscellaneous Inspection Failed 02/22/2002
Correction
Corrective Action Required
02/22/2002
NONE OFFICE LOCKED SUPERVISIOR NOT ON SITE NO ACCESS TO BLUEPRINTS AREA REQUIRING UNKNOWN CALL FOR REINSPECTIOM
Rough Electrical Inspection - Commercial Passed 02/25/2002
Correction
Resolved
02/25/2002
J- BOX ROOMS 202Q, 202R, 202S, 202T, 202U, 202V, 202W, 202X, 208, 206
Rough Framing Inspection - Commercial Partial 02/25/2002
Correction
Partial Correction
02/25/2002
STUDS & DRYWALL ENTRY 223 : OK TO SHEETROCK [BOTH SIDES AS APPLICABLE]
All Rough Inspection - Commercial Failed 02/28/2002
Correction
Partial Correction
02/28/2002
SCREW PATTERN VESTABULE 223 - OK TO TAPE
Rough Framing Inspection - Commercial Partial 03/07/2002
Correction
Partial Correction
03/07/2002
CORRIDOR CORRIDOR 219 SCREW PATTERN APPROVED
Above Ceiling Inspection Failed 04/01/2002
Correction
Corrective Action Required
04/01/2002
PENETRATIONS & SUPPORTS 202,S,T,Q,U,V,W,X,206,210,205,27,209 RM 202R MISSING COVER - "J" BOX CORRIDOR 224 - LIGHTS SUPPORTED FROM MECH. DUCTS & MISC. PENETRATIONS - RATEDCORRIDOR EXISTING LIGHTS NOT SUPPORTED
Above Ceiling Inspection Partial 04/04/2002
Correction
Partial Correction
04/04/2002
NONE RMS 112/114 MISC PENETRATIONS TP CORRIDOR REQD TO BE SEALED RM 209/CORR 224 SEALING OF WALL/FLUTED DECK REQS SHT 102A RETURN AIR BOOTS REQD TO BE SUPPORTED OK TO LAY TILE SHT 102A/102B LEAVE ABOVE NOTED AREAS ACCESSIBLE
Above Ceiling Inspection Passed 04/09/2002
Correction
Resolved
04/09/2002
PENETRATIONS & SUPPORTS COR5IDOR 117 RMS 109,112,114,111,111A, 209
Above Ceiling Inspection Passed 04/09/2002
Correction
Resolved
04/09/2002
NONE
Above Ceiling Inspection Partial 04/19/2002
Correction
Partial Correction
04/19/2002
PENETRATIONS & SUPPORTS REMOVE SYSTEMS FROM SPRINKLER LINES 2ND FLOOR ADDITION
Above Ceiling Inspection Passed 04/22/2002
Correction
Resolved
04/22/2002
PENETRATIONS & SUPPORTS 2ND FLOOR APPROVED OK TO HANG TILE
Above Ceiling Inspection Passed 04/25/2002
Correction
Resolved
04/25/2002
None ROOM 118 OK TO INSTALLTILE
Foundation Inspection - Commercial Passed 05/20/2002
Correction
Resolved
05/20/2002
None ROOM 105 - APPROVED
Underground Plumbing Inspection - Commercial Passed 05/21/2002
Correction
Resolved
05/21/2002
None RM 105A
Rough Framing Inspection - Commercial Partial 05/22/2002
Correction
Partial Correction
05/22/2002
None LINE 8, ROOM 105A - APPROVED
Footing Inspection - Commercial Failed 05/23/2002
Correction
Corrective Action Required
05/23/2002
ALL READY POURED RM 105B ALREADY POURED EXCEPT APPROX. 5` ON EAST/WEST LINE ON SOUTH SIDE
Rough Framing Inspection - Commercial Partial 05/30/2002
Correction
Partial Correction
05/30/2002
None CHANGES TO DOORS 100 & 102-- APPROVED STEEL FRAMING TOILETS 125 & 225 APPROVED - CEILING FRAMING NOT STARTED. APPROVAL IS SUBJECT TO CHANGES BEING APPROVED BY PLANS EXAMINER.
Underground Plumbing Inspection - Commercial Partial 05/31/2002
Correction
Partial Correction
05/31/2002
PARTIAL UNDER-FLOOR PLUMBING APPROVED NEW DWV PIPING INSTALLED. OK TO COVER ROOM 125 EXSTG FLOOR SLAB REMOVED
Rough Plumbing Inspection - Commercial Partial 06/11/2002
Correction
Partial Correction
06/11/2002
None ROOMS - 125, 100D, 225, 202H APPROVED
Rough Electrical Inspection - Commercial Partial 06/11/2002
Correction
Partial Correction
06/11/2002
None ROOMS 100, A, B, C, D, 104 - INSTALL ADDITINAL OUTLET AT WEST WALL, 104A, 106, 106A ROOMS 202 F,G & H.
Rough Framing Inspection - Commercial Partial 06/11/2002
Correction
Resolved
06/11/2002
None ROOMS 202 F,G & H ROOMS 100,100A, B, C,D, 102, 102A, [102 RAISED PLATFORM] ROOMS 104, 104A, 106, 106A, 108, 110, [RAISED PLATFORMS 104 & 106] ROOMS 108, 110 & 110 A
Rough Electrical Inspection - Commercial Partial 06/13/2002
Correction
Partial Correction
06/13/2002
None COMPLETE EXCEPT FOR ROOM 110. FIVE [5] OUTLETS ON NORTH OF WEST WALL NOT INSTALLED. Rooms 108, 110 & 110A
Miscellaneous Inspection Partial 06/24/2002
Correction
Partial Correction
06/24/2002
RATED ASSEMBLY SCREW PATTERN ROOMS 100D 104 106 APPROVED
Rough Electrical Inspection - Commercial Partial 06/27/2002
Correction
Corrective Action Required
06/27/2002
None EL. ROUGH OK IN RM. 202E
Rough Framing Inspection - Commercial Partial 06/27/2002
Correction
Corrective Action Required
06/27/2002
None WALL FRAMING OK IN RM. 202E.
Above Ceiling Inspection Partial 06/27/2002
Correction
Corrective Action Required
06/27/2002
None ABOVE CEILING MECH. AND FIRETAPE OK TO COVER IN TOILET RM`S 125 AND 225.
Occupancy Inspection - Codes Commercial Failed 06/28/2002
Correction
Corrective Action Required
06/28/2002
None NOT READY
Above Ceiling Inspection Partial 07/03/2002
Correction
Partial Correction
07/03/2002
None Unisex restrooms 125 and 225 rated ceiling assemblies approved.
Above Ceiling Inspection Passed 07/12/2002
Correction
Resolved
07/12/2002
NONE room 105/105A approved
Above Ceiling Inspection Not Ready 07/12/2002
Correction
Corrective Action Required
07/12/2002
NOT READY CALL FOR INSPECTION WHEN READY
Above Ceiling Inspection Partial 07/15/2002
Correction
Resolved
07/15/2002
None ABOVE CEILING MECH. AND FIRETAPE OK TO COVER IN TOILET RM`S 125 AND 225.
Correction
Resolved
07/15/2002
NOT READY RMS 202 F,G,H,J - OKAY TO INSTALL TILE
Above Ceiling Inspection Partial 07/17/2002
Correction
Corrective Action Required
07/17/2002
Through Penetrations PENETRATION OF RATED WALL BY WRAPPED PIPE APPROX 10". OPPOSITE RMM203. CONTRACTOR STATES THIS WAS EXISTING. OK TO HANG TILE. Corridor 224 East,Side
Above Ceiling Inspection Partial 07/18/2002
Correction
Resolved
07/18/2002
None RMS 102, 102A, 100, 100A, 100B, 100C, 100D
Correction
Partial Correction
07/18/2002
Through Penetrations PENETRATION OF RATED WALL BY WRAPPED PIPE APPROX 10". OPPOSITE RM 203. CONTRACTOR STATES THIS WAS EXISTING. OK TO HANG TILE. Corridor 224 East,Side
Rough Electrical Inspection - Commercial Partial 07/19/2002
Correction
Resolved
07/19/2002
None RMS 100, A, B, C, D, 104,104A, 106, 106A ROOMS 202 F,G & H.
Correction
Resolved
07/19/2002
None EL. ROUGH OK IN RM. 202E
Above Ceiling Inspection Partial 07/19/2002
Above Ceiling Inspection Passed 07/24/2002
Correction
Resolved
07/24/2002
NONE 104/104A, 106/106A, 108, 110 OK TO START TILE SEAL PENETRATIONS AT CORRIDOR WALL STINGERS OK OK TO DEVICE OUT
Above Ceiling Inspection Partial 08/01/2002
Correction
Partial Correction
08/01/2002
Through Penetrations PENETRATION OF RATED WALL BY WRAPPED PIPE APPROX 10". OPPOSITE RM 203. CONTRACTOR STATES THIS WAS EXISTING. THIS STLL MUST BE FIREBLOCKED. OK TO HANG TILE. Corridor 224 East,Side
Correction
Resolved
08/01/2002
None RM 105 & CORRIDOR 119.
Miscellaneous Inspection Passed 08/09/2002
Correction
Resolved
08/09/2002
NONE
Occupancy Inspection - Codes Commercial Failed 08/09/2002
Correction
Corrective Action Required
08/09/2002
None COMPLY WITH FIRE DEPT REQS SEPERATE COVER PROVIDE SIGNAGE AT MUSIC ROOM DOOR/STORAGE DOOR COMPLETE FD ISSUES IN OFFICE 200 PACKAGE ROOM 107 NOT READY
Miscellaneous Inspection Passed 08/09/2002
Correction
Resolved
08/09/2002
RATED ASSEMBLY SCREW PATTERN ROOMS 100D 104 106 APPROVED
Occupancy Inspection - Codes Commercial Failed 08/14/2002
Correction
Corrective Action Required
08/14/2002
None FIRE DEPT ISSUES F.E. CABINETS MAG LOCK ISSUES
Above Ceiling Inspection Partial 08/14/2002
Correction
Partial Correction
08/14/2002
NONE > ROOM 107 ABOVE-CEILING APPROVED OK TO PLACE TILE
Occupancy Inspection - Codes Commercial Passed 11/26/2002
Correction
Resolved
11/26/2002
None
Occupancy Inspection - Codes Commercial Passed 11/27/2002
Correction
Resolved
11/27/2002
None Landscaping to be done by MCC
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.