Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
10/07/2001
|
10/29/2010
|
|
|
|
Correction
Codes Administration- Lavatories shall be mounted with a clearance of at least 29 inches from the floor to the bottom of the apron. Knee and toe clearances shall comply with Fig. 31. (ANSI A117.1-1986, Section 4.19.2.1.)
|
|
Correction
Codes Administration- Hot water and drain pipes under lavatories or sinks shall be insulated or otherwise protected if they abut the clearance areas indicated in Fig. 31. There shall be no sharp or abrasive surfaces under lavatories or sinks. (ANSI A117.1-1986, Section 4.19.4.)
|
|
Correction
Codes Administration- Mirrors shall be mounted with the bottom edge of the reflecting surface no higher than 40 inches from the floor. (ANSI A117.1-1986, Section 4.19.6.)
|
|
Correction
Codes Administration- If the clear floor space allows only forward aproach to an object, the maximum high forward reach allowed shall be 48 inches and the minimum low forward reach shall be unobstructed and no less than 15 inches above the floor. If the high forward reach is over an obstruction, reach and clearances shall be as shown in Fig. 5(b). (ANSI A117.1-1986, Section 4.2.5.)
|
|
Correction
Codes Administration- If the clear floor space allows parallel approach by a person in wheelchair, the maximum high side reach allowed shall be 54 inches and the low side reach shall be no less than 9 inches above the floor. If the side reach is over an obstruction, the reach and clearances shall be as shown in Fig. 6(c). (ANSI A117.1-1986, Section 4.2.6.)
|
|
Correction
Codes Administration- All signage that provides emergency information or general circulation directions or identifies rooms and spaces shall comply with 4.28.2, 4.28.3, and 4.28.5. Tactile signage shall also comply with 4.28.4. ANSI A117.7-1986 Section 4.28.1
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
Codes Administration- All structures shall be designed to the requirements of 1991 Uniform Building Code, Uniform Mechanical Code, Uniform Plumbing Code, Uniform Fire Code and the 1990 National Electrical Code.
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
Correction
Codes Administration - This permit is for the alteration of an existing building only. No exterior changes may be made without prior approval.
|
|
Correction
Codes Administation - No open flame or welding will be allowed in the storage area.
|
|
Correction
Fire Department- Clarify what is to be stored in the storage area. ADDITIONAL REQUIREMENTS MAY APPLY.
|
|
Correction
Fire Department- Fire apparatus access roads shall have an unobstructed width of not less than 20 feet and an unobstructed vertical clearance of not less than 13 feet 6 inches. (UFC Section 10.204.(a))
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
Correction
Fire Department- Provide "Knox Box Entry System". When access to or within a structure or an area is unduly difficult because of secured openings or where immediate access is necessary for life-saving or firefighting purposes, the chief is authorized to require a key box to be installed in an accessible location. The key box shall be a type approved by the chief and shall contain keys to gain necessary access as required by the chief. (UFC 10.302)
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
Correction
Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
|
|
Correction
Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
|
|
Correction
Fire Department- Exit illumination shall be provided and maintained in accordance with the Building Code. Exits shall be illuminated when the building or structure is occupied. Equipment providing emergency power for exit illumination and exit signs shall be maintained in an operable condition. (UFC Section 12.110)
|
|
Correction
Fire Department- A completed hazardous materials permit application shall be submitted to the Lee's Summit fire department. (UFC Section 4.103 and UFC Section 80.103.(a))
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
Correction
Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practicl. Combustible debris, waste material and trash shall not be burned on site. UFC Section87.103.(e)
|
|
|