Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
07/03/2001
|
10/29/2010
|
|
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
|
|
Correction
Codes Administration- Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvements. Permits shall be obtained prior to any work which requires permitting.
|
|
Correction
Codes Administration- The engineer or architect in responsible charge of the structural design work shall include in the construction documents the following: 1. Special inspections required by Section 306. 2. Other structural inspections required by the engineer or architect in responsible charge of the structural design work as required. (UBC Section 302.(b) & (c))
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
Correction
Codes Administration- The special inspector shall observe the work assigned for conformance, shall furnish inspection reports to the Codes Administration Department and the engineer or architect of record and shall submit a final signed report stating whether the work requiring special inspection was in conformance with the approved plans and applicable sections of this code. The final report shall be submitted prior to receiving a Certificate of Occupancy. (UBC Section 306.(c))
|
|
Correction
Codes Administration - Although Occupant Loads have been submitted, actual Occupant Loads and egress requirements cannot be determined until storefront/tenant finish information is submitted.
|
|
Correction
Codes Administration - The allowance for unlimited area via sprinklers is dependent upon the tenant finish spaces to be occupied with compatible use i.e. B-2 occupancy.
|
|
Correction
Plng & Dev. - Lighting - Provide the lighting specifications for the 16.01 light fixtures for cantilever lamp and wall pack and 16.04 light fixture on roof.
|
|
Correction
Plng&Dev. EIFS - CLarify the leader noted as EIFS?
Provide additional information regarding EIFS 1-6 and "P" Color Coating Systems P 1-6.
Locate leaders on the elevations relating to EIFS and "P" Color Coating system.
Provide color coating information for all dock doors and man doors.
|
|
Correction
Plng&Dev. - Correspondence - See correspondence dated 1/11/01 as to additional information required.
|
|
Correction
Water Utilities - Engineering plans for the water and sanitary sewer facilities, which will ultimately be owned and maintained by the City, must be submitted and approved by the Water Utilities Department.
|
|
Correction
Water Utilities - No occupancy permit will be issued prior to the substantial completion of the off-site water and sanitary sewer improvements.
|
|
Correction
Water Utilities - The fire service line to the building must be provided with an isolating valve at the public main. This valve installation must be provided with a valve post indicator to readily ascertain the operating position of the valve.
|
|
Correction
Water Utilities - Trench drains must not be connected to the sanitary sewer.
|
|
Correction
Water Utilities - All backflow prevention devices must be tested within thirty (30) days of installation. A note to this effect should be placed on the plans.
|
|
Correction
Water Utilities - The location of the Siamese connection for the Fire Department's use in supplying the internal fire suppression system must be approved by the Lee's Summit Fire Department. You are encouraged to contact Battalion Chief Jim Eden at 816/969-7424.
|
|
Correction
Water Utilities - It appears Bldg Mb is comprised of three (3) separate buildings. A separate domestic water meter installation and associated service line must be provided for each building.
|
|
Correction
Water Utilities - The two (2) fire service lines to these buildings must be provided with an isolating valve at the public main. Each of these valve installations must be provided with a valve post indicator to readily ascertain the operating position of the valve
|
|
Correction
Water Utilities - No bypass piping will be allowed on the domestic backflow prevention device. A parallel backflow prevention device may be placed on the proposed bypass piping if uninterrupted water service is required.
|
|
Correction
Water Utilities - The relief port and associated drain piping for the domestic backflow prevention device must be adequately sized.
|
|
Correction
Water Utilities - The relief vents (i.e. test cocks) on the domestic backflow prevention device must not be piped to the floor drain as noted.
|
|
Correction
Codes Administration - Although Occupant Loads have been submitted, actual Occupant Loads and egress requirements cannot be determined until storefront/tenant finish information is submitted.
|
|
Correction
Codes Administration - The allowance for unlimited area via fire sprinklers is dependent upon the tenant finish spaces to be occupied with compatible use i.e. B-2 Occupancies.
|
|
Correction
Fire Department- Standpipe systems shall be provided as set forth in Table 10.510-A. UFC 10.510b and as required by the fire department. Provide standpipe connections at the three exterior entrances to the hallways that intersect M-b.
|
|
Correction
Fire Department- Provide detail on fire department connection (FDC) on building M-b. Can the FDc be provided on the building?
|
|
Correction
Fire Department- Plan reviewed as a shell building only. Provide tenant finish plans for review.
|
|
Correction
Fire Department- Parking lots and fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be provided with a surface so as to provide all-weather driving capabilities. (UFC Section 10.204.(b))
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
Correction
Fire Department- Provide "Knox Box Entry System". When access to or within a structure or an area is unduly difficult because of secured openings or where immediate access is necessary for life-saving or firefighting purposes, the chief is authorized to require a key box to be installed in an accessible location. The key box shall be a type approved by the chief and shall contain keys to gain necessary access as required by the chief. (UFC 10.302)
|
|
Correction
Fire Department- The duct detectors when activated shall be received at the panel and alarm company as a trouble alarm. (UFC Section 10.503.)
|
|
Correction
Fire Department- A set of sprinkler plans and specifications bearing a State of Missouri licensed engineers seal, shall be submitted to the Fire Department for review and approval prior to construction (system modification). (1991 Uniform Fire Code, Section 10.503)
|
|
Correction
Fire Department- Fire alarm systems; fire hydrant systems; fire-extinguishing systems, including automatic sprinklers and wet and dry standpipes; halon systems and other automatic fire-extinguishing systems shall meet the approval of the fire department as to installation and locations and shall be subject to acceptance testing and such periodic testing as required by the chief. NOTE: Acceptance testing may scheduled at least 48 hours in advance by calling 969-7343. UFC 10.503
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
Correction
Fire Department- All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised when the number of sprinkler heads are one-hundred or more. Valve supervision and water-flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote station or proprietary supervising station as defined by national standards. UFC 10.508
|
|
Correction
Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
|
|
Correction
Fire Department- Exit illumination shall be provided and maintained in accordance with the Building Code. Exits shall be illuminated when the building or structure is occupied. Equipment providing emergency power for exit illumination and exit signs shall be maintained in an operable condition. (UFC Section 12.110)
|
|
Correction
Fire Department- If building alteration adversely effects exit illumination, exit illumination shall be provided and maintained in accordance with the Building Code. UFC Section 12.110.(A).
|
|
Correction
Fire Department- Complete plans and specifications (bearing an State of Missouri architects /engineers seal) for fire alarm systems shall be submitted for review and approval prior to system installation. (UFC Section 14.103.(a))
|
|
Correction
Codes Administration - This building permit is issued subject to all applicable provisions of the "First Amended and Restated Tax Increment Financing Contract Between the City of Lee's Summit, Missouri and R.E.D. Capital Holdings of Lee's Summit, LLC for the I-470 and 350 Highway Tax Increment Financing Plan" (Contract), recorded with the Jackson County Department of Records at book and page number 2001I000086411 (1-77). Pursuant to Section 8(a) of the Contract, the City will not issue certificates of occupancy for structures within the Redevelopment Area - Project 1, as defined in the Contract, until a certificate of substantial completion for all of the Phase 1 Public Project Improvements, as defined in the Contract, has been issued by the City pursuant to the provisions of the City's Design and Construction Manual.
|
|
Correction
PW - Applicant shall conform to all provisions of the memorandum of understanding dated 12-19-2000 between R.E.D. Capital and the City of Lee's Summit.
|
|
|