Summary
B0001379
Building Permit - Commercial
Final Completion
DIL PETROLEUM INC
NEW COMMERCIAL
KING SUPER STORE PUMP ISLAND
07/31/2000
08/29/2000
02/25/2001
06/13/2001
Locations
Contacts
PETROLEUM EQUIPMENT INC. OF K.C., Address:1401 E 9TH ST  
DIL PETROLEUM INC, Address:1317 SW MARKET ST  
GG HOLDING LLC, Address:14433 MAPLE ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/27/2001 10/29/2010
Correction

Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
Correction

Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
Correction

Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

PLANNING & DEVELOPMENT - All development shall be in accordance with the approved site plan and all conditions in staff's letter, dated May 24, 2000.
Correction

PLANNING & DEVELOPMENT - Landscaping and/or screening shall be maintained in good condition. Plants which are not in sound growing condition or are dead shall be removed and replaced with a plant of the same species, variety or cultivator.
Correction

PLANNING & DEVELOPMENT - At the intersection of the street and the driveways, no obstruction shall interfere with the line of sight between a height of 2 feet and 8 feet above the adjoining street or driveway pavement, within the triangle of sight.
Correction

PW - Contact Public Works Inspection at 969-7450 prior to construction.
Correction

PW - Contact Barton Reese, Erosion Control Specialist, at 969-7951 for erosion control installation approval and prior to land disturbance.
Correction

PW - Please submit three (3) prints of revised civil site plans containing the information necessary to address the Water Utilities and the Public Works Engineering Departments.
Correction

Fire Department- Pressure testing of the tank (prior to installation) and piping shall be witnessed by the fire department. Contact the Fire Department Prevention Division at (816) 969-7424 to schedule an appointment 48 hours in advance of the test.
Correction

Fire Department- Guard posts meeting UFC specifications shall be installed to protect the kerosene dispenser from vehicular damage.
Correction

Codes Admin. - All new electrical installations must comply with the 1990 National Electric Code.
Correction

Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
Correction

Fire Department- A control shall be provided that will allow the pump to operate only when a dispensing nozzle is removed from its bracket or normal position with respecat to the dispensing unit and the switch on the dispensing unit is manually activated. This control shall also stop the pump when all nozzles have been returned, either to their brackets or to the normal nondispensing position. Electrical conditions shall also comply with the following: 1. A clearly labeled, manually operated pump master switch shall be provided in an approved location within 75 feet of, but not nearer than 15 feet to, any dispenser. Where such master switch is not visable from all dispensers, the location therof shall be indicated by approved signs, 2. Signs identifying the pump master switch shall be labeled EMERGENCY PUMP SHUTOFF, and 3. The master switch on all individual pump circuits switches shall be set in the "off" position before closing the motor vehicle fuel-dispensing station for buisness at any time.
Correction

Fire Department- A fire extinguisher with a minimum rating of 2-A.20-B:C shall be provided and located such that it is not more than 75 feet from any pump, dispenser or fill-pipe opening. UFC Section 79.908
Correction

Fire Department- Smoking and open flames shall be prohibited in areas used for fueling with or dispensing of Class I, II or II-A liquids. The motors of vehicles being fueled shall be stopped. Conspicuous signs prohibiting smoking, prohibiting dispensing into unproved containers, and requiring vehicle motors to be stopped during fueling operations shall be posted within sight of each customer being served. UFC Section 79.903.(d)
Correction

Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
Correction

Fire Department- Dispensing equipment shall comply with one of the following: (i) The amount of fuel being dispensed is limited in quantity by a preprogrammed card, (ii) Dispensing devices are programmed or set to limit uninterrupted fuel delivery to 25 gallons and require a manual action to resume continued delivery, or (iii) Product delivery hoses are equipped with alisted emergency breakaway device designed to retain liquid on both sides of the breakaway point. Such devices shall be installed and maintained in accordance with manufacturer's instructions. (1991 Uniform Fire Code, Section 79.903(f).2.C.)
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $62.00 $62.00 Paid 08/29/2000
24 BLDG Plan Check Fees $7.00 $7.00 Paid 08/29/2000
25 Electrical Permit Fee $15.00 $15.00 Paid 08/29/2000
25 Mechanical Permit Fees $28.00 $28.00 Paid 08/29/2000
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home