| Review Type |
Outcome |
Est. Completion Date |
Completed |
|
Internal Plan Review (Res)
|
Approved
|
12/16/2000
|
10/29/2010
|
|
|
|
|
|
Correction
Codes Administration- A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
|
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
|
Correction
Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
|
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
|
Correction
Water Utilities - Domestic water service must have a RPZ backflow preventer install and tested before CO.
|
|
|
Correction
Water Utilities - Fire line backflow preventer(s) must be tested before CO and Fire Department testing.
|
|
|
Correction
Codes Administration - Provide 4 sets of the plumbing and mechanical plans for review and approval.
|
|
|
Correction
Codes Administration - Provide information on the elevator from the manufactor prior to installation.
|
|
|
Correction
Codes Administration - The elevator shall be inspected by an individual certified to perform such inspection in the state of Missouri. A member of the City of Lee's Summit inspection division shall be present to witness the inspection.
|
|
|
Correction
Codes Administration - The minimum stairway width shall be determined as specified in Section 3303 (b), but shall not be less than 44 inches except as specified herein. Stairways serving an occupant load of 49 or less shall not be less than 36 inches in width. (1991 Uniform Building Codes, Section (b).)
|
|
|
Correction
Codes Administration - Provide a discription of the work to be performed and the equipment to be used. This information is to aid in determining occupancy seperation requirements.
|
|
|
Correction
Codes Administration - Except when usable space under the stairs is prohibited by Section 3309 (f), the walls and soffits of the enclosed space shall be protected on the enclosed side as required for one-hour fire-resistive construction. (1991 Uniform Building Code, Section 3306 (i).)
|
|
|
Correction
Codes Administration - Explain why the exit alcove 104 is not constructed as a rated corridor and the door schedule shows door 109a as a rated door.
|
|
|
Correction
Codes Administration - Explain why an occupancy seperation is between the office area and the parts area but there is not one between the shop area and the customer service area and the second floor office area.
|
|
|
Correction
Codes Administration - Is corridor 108 a rated corridor or are the walls part of an occupancy seperation. The door schedule shows the doors to this area to be 1 hour rated and a corridor only requires them to be 20 minute.
|
|
|
Correction
Codes Administration - Provide the penetration assemblies used in the fire-rated assemblies.
|
|
|
Correction
Codes Administration - Provide the assemblies used for the wall to wall and wall to ceiling joints.
|
|
|
Correction
Codes Administration - Provide the fire-rated floor/ceiling assembly to be used in the rated corridors.
|
|
|
Correction
Fire Department- If not already provided, an alarm bell with strobe light shall be mounted directly above the fire department connection (fdc). The bell/strobe shall activate upon water flow in the sprinkler system equivalent to or greater than that of one sprinkler head.
|
|
|
Correction
Codes Administration - Room 207 located on the second floor will be utilized as a training room and not a conference room.
|
|
|
Correction
Codes Administration - Only a men's locker room is shown to be provided at this time. Additional facilities may be required to accomodate women if they are employeed in this area.
|
|
|
Correction
Codes Administration - Where the fire-resistive covering on columns is exposed to injury from moving vehicles, the handling of merchandise or other means, it shall be protected in an approved manner. (1991 Uniform Building Code, Section 4303 (b).5.)
|
|
|
Correction
Fire Department- Fire-protection equipment and fire hydrants shall be clearly identified in a manner approved by the chief to prevent obstruction by parking and other obstructions. (UFC Section 10.105b)
|
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
|
Correction
Fire Department- Provide "Knox Box Entry System". When access to or within a structure or an area is unduly difficult because of secured openings or where immediate access is necessary for life-saving or firefighting purposes, the chief is authorized to require a key box to be installed in an accessible location. The key box shall be a type approved by the chief and shall contain keys to gain necessary access as required by the chief. (UFC 10.302)
|
|
|
Correction
Fire Department- The duct detectors when activated shall be received at the panel and alarm company as a trouble alarm. (UFC Section 10.503.)
|
|
|
Correction
Fire Department- Fire alarm systems; fire hydrant systems; fire-extinguishing systems, including automatic sprinklers and wet and dry standpipes; halon systems and other automatic fire-extinguishing systems shall meet the approval of the fire department as to installation and locations and shall be subject to acceptance testing and such periodic testing as required by the chief. NOTE: Acceptance testing may scheduled at least 48 hours in advance by calling 969-7343. UFC 10.503
|
|
|
Correction
Fire Department- Fire-protection or extinguishing system coverage, spacing and specifications shall be maintained accordance with recognized standards at all time. Such systems shall be extended, altered or augmented as necessary to maintain and continue protection whenever any building so equipped is altered, remondeled or added to. Additions, repairs, alterations and servicing shall be in accordance with recognized standards. UFC Section 10.504(a)
|
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
|
Correction
Fire Department- All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised when the number of sprinkler heads are one-hundred or more. Valve supervision and water-flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote station or proprietary supervising station as defined by national standards. UFC 10.508
|
|
|
Correction
Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
|
|
|
Correction
Fire Department- A completed hazardous materials permit application shall be submitted to the Lee's Summit fire department. (UFC Section 4.103 and UFC Section 80.103.(a))
|
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
|
Correction
Fire Department- During construction fire department access shall be maintained and not obstructed. UFC Section 87.103.(b)
|
|
|
|