Internal Plan Review (Res)
|
Approved
|
12/13/2000
|
10/29/2010
|
|
|
|
Correction
Codes Administration- A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
Codes Administration- Separate permits shall be obtained for individual tenant spaces prior to any alterations being performed.
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
Correction
Codes Administration- Provide a complete truss package designed and sealed by an engineer licensed in the State of Missouri. The package shall include the design specifications and details on the design, installation, bracing and fastening of the trusses. Two packages for each building type shall be provided to the Codes Administration Department for approval prior to installation.
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
Correction
Codes Administration- Exit doors shall be openable from the inside without the use of a key or special knowledge. (UBC Section 3304.(c))
|
|
Correction
Codes Administration- Except within individual dwelling units, guest rooms and sleeping rooms, exits shall be illuminated at any time the building is occupied with light having intensity of not less than 1 foot-candle at floor level. The power supply for exit illumination shall normally be provided by the premises' wiring system. In the event of its failure, illumination shall be automatically provided from an emergency system for group I, Division1.1 and 1.2 occupancies and for all other occupancies where the exiting system serves an occupant load of 100 or more. Emergency systems shall be supplied from storage batteries or an on-site generator system and the system shall be installed in accordance with the requirements of the Electrical Code. (1991Uniform Building Code, Section 3313.(a) & (b).)
|
|
Correction
Codes Administration- Glass shall meet the requirements of Chapter 54 of the 1991 Uniform Building Code when installed in locations considered specificly hazardous per Section 5406.(d).
|
|
Correction
PW - Contact Public Works Inspection at 969-7450 prior to construction.
|
|
Correction
PW - Contact Barton Reese, Erosion Control Specialist, at 969-7951 for erosion control installation approval and prior to land disturbance.
|
|
Correction
PW - Effective July 1, 2000, provide a copy of the land disturbance permit and the required attachments to the Erosion Control Specialist prior to any land disturbance activities.
|
|
Correction
Water Utilities - Please provide Fire Hydrant Assembly detail.
|
|
Correction
Water Utilities - Domestic water service must have a RPZ backflow prevention assembly installed and tested before CO.
|
|
Correction
Codes Administration- Exterior walls shall have fire resistance and opening protection as set forth in Table No. 5-A, Part III, and in accordance with such additional provisions as are set forth in Part IV and Part VII. Distances shall be measured at right angles from the property line. The above provisions shall not apply to walls at right angles to the property line. (1991 Uniform Building Code, Section 504.(d).)
The west exterior wall shall be one hour as it's location is less than 20 feet to the property line.
|
|
Correction
Codes Administration- GENERAL NOTE: Buildings or portions thereof where persons are employed shall be provided with at least one water closet. Separate facilities shall be provided for each sex when the number of employees exceeds four. (UBC Section 705.(c)).
Each tenant space has the capacity to accomodate more than four employees. Should the spaces have more than four employees occupying a space, a second restroom will be required.
|
|
Correction
Codes Administration - This plan review was performed assuming that this structure will house B-2 occupancies. Should a different occupancy type occupy a tenant space additional provisions may be required.
|
|
Correction
Codes Administration- Draft stops shall be installed in attics, mansards, overhangs, false fronts set out from walls and similar concealed spaces of buildings having uses other than dwellings or hotels so that the area between draft stops does not exceed 3,000 square feet and the greatest horizontal dimension does not exceed 60 feet. 1991 Uniform Building Code Section 2516.(f)4B(iii)
Indicate locations and proposed contruction detail for draft stops.
|
|
Correction
PLANNING & DEVELOPMENT - Revised manufacturer's specifications indicating the type of fixture, wattage and mounting height shall be submitted to the Department of Planning and Development prior to the issuance of building permits.
|
|
Correction
PLANNING & DEVELOPMENT - All development shall be in accordance with the approved site plan and all conditions in staff's letter to the City Council, dated May 31, 2000.
|
|
Correction
PLANNING & DEVELOPMENT - All landscaping, as shown on the approved plans, shall be installed by November 30, 2000 or prior to the receipt of a Certificate of Occupancy.
|
|
Correction
PLANNING & DEVELOPMENT - A sidewalk is required along 4th Street.
|
|
Correction
PLANNING & DEVELOPMENT - A 100% opaque screen, consisting of masonry piers and wood slats, shall be provided along the west property line, as shown on the approved site plan.
|
|
Correction
PLANNING & DEVELOPMENT - The trash enclosure shall be constructed of a masonry material to match the building and the gates shall be constructed of a prefinished steel gauge panel of a compatible color to the building.
|
|
Correction
Fire Department- Parking lots and fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be provided with a surface so as to provide all-weather driving capabilities. (UFC Section 10.204.(b))
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
Correction
Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
Correction
Codes Administration- Materials exposed within ducts or plenums shall have a flame-spread index of not more than 25 and a smoke-developed rating of not more than 50 when tested in accordance with the test for Surface Burning Characteristics of Building Materials, U.B.C. Standard No. 42-1. 1991 Uniform Mechanical Code Section 1002.b.
|
|
|