Summary
B0001029
Building Permit - Commercial
Certificate of Occupancy
HSM WDC PINETREE LLC
CHANGE OF TENANT
TENANT FINISH
06/01/2000
06/29/2000
12/26/2000
09/06/2000
Locations
Contacts
JANTSCH & SLAGGIE ARCHITECTS, Address:208 DELAWARE  
HSM WDC PINETREE LLC, Address:12700 HILLCREST RD STE 125  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/28/2000 10/29/2010
Correction

Codes Administration- All signage that provides emergency information or general circulation directions or identifies rooms and spaces shall comply with 4.28.2, 4.28.3, and 4.28.5. Tactile signage shall also comply with 4.28.4. ANSI A117.7-1986 Section 4.28.1
Correction

Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
Correction

Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
Correction

Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
Correction

Codes Administration- Walls and permanent partitions of Type II-N buildings shall be of non-combustible materials. (UBC Section 1901)
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
Correction

Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
Correction

Codes Administration- Exit doors from a Group A Occupancies having an occupant load of 50 or more shall not be provided with a latch or lock unless it is panic hardware. (1991 Uniform Building Code, Section 3317.(d).)
Correction

Fire Department- The door depicted on sheet A1 (item 6) shall have a sign or lettering placed on it stating "THIS DOOR BLOCKED". The letters shall be a minimum of 6" in height with a 3/4" stroke. UFC 10.304 (c).
Correction

Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC. A minimum of one extinguisher for ever 3000 square feet is required. An additional fire extinguisher will be required. (5 lb.). (UFC Section 10.505.(a))
Correction

Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. Additional numbers will be required on the rear door of the occupancy. (UFC Section 10.301.(a))
Correction

Codes Administration- Buildings or portions thereof where persons are employed shall be provided with at least one water closet. Separate facilities shall be provided for each sex when the number of employees exceeds four. (UBC Section 705.(c)) A fully accessible restroom shall be provided and designated a mens restroom.
Correction

Codes Administration- The type of construction shall be II-N. Sheet A1 indicates type of construction as V-N.
Correction

Codes Administration- The plumbing system shall be vented by a minimum of one (1) three (3) inch vent. The plumbing riser diagram indicates a 2 inch vent. Per Section 504(a)--revised per City Ordinance.
Correction

Codes Administration- If the front door located in room 106 is not going to be used as an exit, it shall be made not to appear like a door or exit. (Remove door push or pull or "disguise" so that the door does not appear as an exit or door).
Correction

Codes Administration- The exit sign located in room 106 shall be moved further to the north of the space so that it clearly indicates direction of egress. (Away from door not being used).
Correction

Codes Administration- The lavatory shall be mounted with a clearance of at least 29 inches from the floor to the bottom of the apron. Knee and toe clearances shall be maintained in accordance with ANSI 117.1-1986.
Correction

Codes Administration- The drinking fountain shall be located so that it may be used by women and men. The current location is not appropriate.
Correction

Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
Correction

Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
Correction

Fire Department- During construction fire department access shall be maintained and not obstructed. UFC Section 87.103.(b)
Correction

Fire Department- During construction required exit components shall be maintained. UFC Section 87.101.(c)
Correction

Fire Department- During construction and alteration fire-resistive assemblies and construction shall be maintained in accordance with Section 10.602. and 10.602. UFC Section 87.104.(d)
Correction

Codes Administration- Materials exposed within ducts or plenums shall have a flame-spread index of not more than 25 and a smoke-developed rating of not more than 50 when tested in accordance with the test for Surface Burning Characteristics of Building Materials, U.B.C. Standard No. 42-1. 1991 Uniform Mechanical Code Section 1002.b.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $377.00 $377.00 Paid 06/29/2000
24 BLDG Plan Check Fees $26.25 $26.25 Paid 06/29/2000
25 Electrical Permit Fee $130.00 $130.00 Paid 06/29/2000
25 Mechanical Permit Fees $34.50 $34.50 Paid 06/29/2000
25 Plumbing Permit Fees $111.00 $111.00 Paid 06/29/2000
89 Sewer Tap Fees $120.00 $120.00 Paid 06/29/2000
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home