Permit Application Status

B0000436


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0000436
Building Permit - Commercial
Final Completion
LEES SUMMIT 29197 L L C
ALTERATION COMMERCIAL
ADD MONGOLIAN COOKER AND HOOD
03/14/2000
05/24/2000
11/20/2000
12/18/2000
Locations
Contacts
YU MIN XIAO, Address:711 SE M-291 HWY  
LEES SUMMIT 29197 L L C, Address:605 W 47TH ST 100  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/10/2000 10/29/2010
Correction

Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
Correction

Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

Codes Administration- Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the Building Official. The Building Official, upon notification, shall make the requested inspections and shall either indicate that portion of the construction is satisfactory as completed, or shall notify the permit holder or an agent of the permit holder wherein the same fails to comply with this code. Any portions which do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the Building Official. (1991 Uniform Building Code, Section 305.(d).)
Correction

Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
Correction

Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
Correction

Fire Department- Installation of the hood and associated duct work shall comply with all requirements of the Uniform Building and Mechanical Codes, as indicated by Codes Administration.
Correction

Fire Department- The stove shall be overlapped by the hood on all sides by a minimum of 6 inches.
Correction

Fire Department- Supply air ducts that penetrate the continuously welded hood shell assembly and discharge into the hood shall have a fire actuated damper listed for such use, or be part of a listed exhaust hood. The actuation device for the hood shall have a temperature rating of 286 degrees F. . The drawings do not show a damper.
Correction

Codes Administration - All plumbing, mechanical and electrical work shall be performed in accordance with the codes adopted by the City of Lee's Summit.
Correction

Codes Administration - Provide two (2) sets of plans that can be easily read.
Correction

Fire Department- The drawings submitted do not accurately depict the installation of the hood system, and do not meet the requirements of the Uniform Mechanical Code or NFPA 96.
Correction

Fire Department- Fire-protection equipment and fire hydrants shall be clearly identified in a manner approved by the chief to prevent obstruction by parking and other obstructions. (UFC Section 10.105b)
Correction

Fire Department- Fire alarm systems; fire hydrant systems; fire-extinguishing systems, including automatic sprinklers and wet and dry standpipes; halon systems and other automatic fire-extinguishing systems shall meet the approval of the fire department as to installation and locations and shall be subject to acceptance testing and such periodic testing as required by the chief. NOTE: Acceptance testing may scheduled at least 48 hours in advance by calling 969-7343. UFC 10.503
Correction

Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
Correction

Fire Department- Approved fire suppression systems shall be provided for the protection of commercial food heat-processing equipment that produces grease laden vapors. The system installed to protect ventilating hoods and ducts and cooking appliances shall be installed to include cooking surfaces, deep fat fryers, griddles, upright broilers, charbroilers, range tops and grills. Protection shall also be provided for the enclosed plenum space within the hood above filters and exhaust ducts serving the hood. UFC 10.513
Correction

Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
Fees
Paid Fees Amount Paid Owing Date Paid
25 Electrical Permit Fee $15.00 $15.00 Paid 05/24/2000
25 Mechanical Permit Fees $21.50 $21.50 Paid 05/24/2000
25 Plumbing Permit Fees $39.00 $39.00 Paid 05/24/2000
89 Sewer Tap Fees $60.00 $60.00 Paid 05/24/2000
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home