Internal Plan Review (Res)
|
Approved
|
08/22/2000
|
10/29/2010
|
|
|
|
Correction
Codes Administration- All signage that provides emergency information or general circulation directions or identifies rooms and spaces shall comply with 4.28.2, 4.28.3, and 4.28.5. Tactile signage shall also comply with 4.28.4. ANSI A117.7-1986 Section 4.28.1
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
Codes Administration- Walls and permanent partitions of Type II-N buildings shall be of non-combustible materials. (UBC Section 1901)
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
Correction
Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
|
|
Correction
Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
|
|
Correction
Codes Administration- Glass shall meet the requirements of Chapter 54 of the 1991 Uniform Building Code when installed in locations considered specificly hazardous per Section 5406.(d).
|
|
Correction
Codes Administration- Toilet rooms shall be provided with a fully openable exterior window at least 3 square feet in area; or a vertical duct not less than 100 square inches in area for the first toilet facility, with 50 additional square inches for each additional facility; or a mechanically operated exhaust system shall be connected directly to the outside, and the point of discharge shall be at least 3 feet from openings into the building. (1991 Uniform Building Code, Section 705(b).
|
|
Correction
Codes Administration- Adequate combustion air shall be provided for the water heater if it is a gas appliance. (Room 27).
|
|
Correction
Codes Administration- The electrical panel is not shown in the plans submitted. Minimum clearances shall be maintained around the electrical panel(s). If the existing electrical service panel requires an upgrade, it is not included in this permit. A separate permit shall be obtained if the Codes Administration Department is not notified of such upgrade prior to issuance of this permit.
|
|
Correction
Codes Administration- Unless otherwise permitted or required by the dryer manufacturer's installation instructions and approved by the Building Official, domestic dryer moisture exhaust ducts shall not exceed a total combined horizontal and vertical length of 14 feet, including two 90-degree elbows. Two feet shall be deducted for each additional 90-degree elbow in excess of two. (UMC 1903(b). A minimum 4-inch diameter exhaust duct of approved materials is required.
|
|
Correction
Codes Administration- Please clarify if any of the new sinks located in rooms 5 or 8 will be used as hair sinks. If so, approved backflow prevention shall be installed.
|
|
Correction
Codes Administration- THIS PERMIT IS VALID FOR BUILDING AND ELECTRICAL ONLY. MECHANICAL AND PLUMBING WILL BE ISSUED AT A LATER DATE.
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
Correction
Fire Department- Dumpsters and containers with an individual capacity of 1.5 cubic yards (40.5 cubic feet) or more shall not be stored in buildings or placed within 5 feet of combustible walls, openings or combustible roof lines. (UFC Section 11.302.(b))
|
|
Correction
Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
|
|
Correction
Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
|
|
Correction
Fire Department- Exit illumination shall be provided and maintained in accordance with the Building Code. Exits shall be illuminated when the building or structure is occupied. Equipment providing emergency power for exit illumination and exit signs shall be maintained in an operable condition. (UFC Section 12.110)
|
|
Correction
Fire Department- When two or more exits from a story are required, exit signs shall be installed ar stair enclosure doors, horizontal exits and other required exits from the story. When two or more exits are required from a room or area, exit signs shall be installed at the required exits from the room or area and where otherwise necessary to clearly indicated the direction of egress. Exit signs shall be illuminated either internally or externally in accordance with the Building Code. Where emergency power supplies are required for exit illumination, exit signs shall be illuminated by emergency power. (UFC Section 12.111)
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
Correction
Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practical. Combustible debris, waste material and trash shall not be burned on site. (UFC Section 87.103.(e))
|
|
Correction
Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practicl. Combustible debris, waste material and trash shall not be burned on site. UFC Section87.103.(e)
|
|
Correction
Fire Department- During construction and alteration fire-resistive assemblies and construction shall be maintained in accordance with Section 10.602. and 10.602. UFC Section 87.104.(d)
|
|
|