Internal Plan Review (Res)
|
Approved
|
08/16/2000
|
10/29/2010
|
|
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
Codes Administration- Exit doors shall be openable from the inside without the use of a key or special knowledge. (UBC Section 3304.(c))
|
|
Correction
Codes Administration- Toilet rooms shall be provided with a fully openable exterior window at least 3 square feet in area; or a vertical duct not less than 100 square inches in area for the first toilet facility, with 50 additional square inches for each additional facility; or a mechanically operated exhaust system shall be connected directly to the outside, and the point of discharge shall be at least 3 feet from openings into the building. (1991 Uniform Building Code, Section 705(b).
|
|
Correction
Codes Administration- The special inspector shall observe the work assigned for conformance, shall furnish inspection reports to the Codes Administration Department and the engineer or architect of record and shall submit a final signed report stating whether the work requiring special inspection was in conformance with the approved plans and applicable sections of this code. The final report shall be submitted prior to receiving a Certificate of Occupancy. (UBC Section 306.(c))
|
|
Correction
PW - Indicate the pavement design for the proposed parking areas and driveways. There will need to be improvements for the southeast pavement removal section.
|
|
Correction
PW - Provide proposed contours for the site improvements. The submittal had several node spots with descriptions. It also did not include information at the southwest entrance to be removed.
|
|
Correction
PW - Submit details for the north entrances including curb and pavement elevations.
|
|
Correction
PW - Provide documentation for the proposed access easement for the north properties.
|
|
Correction
Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
|
|
Correction
Codes Administration- Each circuit leading to or through a dispensing pump shall be provided with a switch or other acceptable means to disconnect simultaneously from the source of supply all conductors of the circuit, including the grounded conductor, if any. Single pole breakers utilizing handle ties shall not be permitted. (NEC, Art. 514.5).
|
|
Correction
Codes Administration- An approved seal shall be provided in each conduit run entering or leaving a dispenser or any cavities or enclosures in direct communication therewith. The sealing fitting shall be the first fitting after the conduit emerges from the earth, concrete, asphalt, etc. (NEC Art. 514-6(a).
|
|
Correction
Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
|
|
Correction
PLANNING & DEVELOPMENT - All landscaping, as shown on the approved plans, shall be installed by May 30, 2000 or prior to the receipt of a Certificate of Occupancy.
|
|
Correction
Codes Administration- Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the Building Official. The Building Official, upon notification, shall make the requested inspections and shall either indicate that portion of the construction is satisfactory as completed, or shall notify the permit holder or an agent of the permit holder wherein the same fails to comply with this code. Any portions which do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the Building Official. (1991 Uniform Building Code, Section 305.(d).)
|
|
Correction
PW - Contact Barton Reese, Erosion Control Specialist, at 969-7951 for erosion control installation approval and prior to land disturbance.
|
|
Correction
PW - Provide three (3) sets of civil site plans to Public Works Engineering upon approval.
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
Correction
Codes Administration- The engineer or architect in responsible charge of the structural design work shall include in the construction documents the special inspections required by UBC section 306 and other structural inspections required by the engineer or architect. (UBC Section 302.(c))
|
|
Correction
Codes Administration - It shall be unlawful for any person to engage in any business or manufacturing within the City without first having obtained a license therefor, paying the license fee, and registering the business or manufacturer with the Director of Finance or the Director's representative. (Lee's Summit Code of Ordinances, Section 28-24.) It is the general contractors responsiblity to make sure that all the trades on their project are licensed with the City of Lee's Summit.
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
Correction
Fire Department- A completed hazardous materials permit application shall be submitted to the Lee's Summit fire department. (UFC Section 4.103 and UFC Section 80.103.(a))
|
|
Correction
Fire Department- A control shall be provided that will allow the pump to operate only when a dispensing nozzle is removed from its bracket or normal position with respecat to the dispensing unit and the switch on the dispensing unit is manually activated. This control shall also stop the pump when all nozzles have been returned, either to their brackets or to the normal nondispensing position. Electrical conditions shall also comply with the following:
1. A clearly labeled, manually operated pump master switch shall be provided in an approved location within 75 feet of, but not nearer than 15 feet to, any dispenser. Where such master switch is not visable from all dispensers, the location therof shall be indicated by approved signs,
2. Signs identifying the pump master switch shall be labeled EMERGENCY PUMP SHUTOFF, and
3. The master switch on all individual pump circuits switches shall be set in the "off" position before closing the motor vehicle fuel-dispensing station for buisness at any time.
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
PW - Indicate CG-1 concrete curb and gutter or an integral concrete sidewalk and curb with a vertical face at all edges of proposed parking areas and driveways, constructed in compliance with the City's standard detail SD-15 from Ordinance No. 3719. The most recent submittal indicated two conflicting details.
|
|
Correction
Codes Administration- Provide details for electrical and roof drainage for the canopy.
|
|
Correction
Codes Administration- All signage that provides emergency information or general circulation directions or identifies rooms and spaces shall comply with 4.28.2, 4.28.3, and 4.28.5. Tactile signage shall also comply with 4.28.4. ANSI A117.7-1986 Section 4.28.1
The restroom shall be identified with a unisex handicap accessible sign in accordance with this requirement.
|
|
Correction
Codes Administration- Marine or motor vehicle fuel-dispensing stations including canopies and supports over pumps shall be of noncombustible, fire-retardant wood or of one-hour fire-resistive construction. The new conopy shall be one-hour construction within 20 feet of the property line. (Section 702.C).
|
|
Correction
Codes Administration- The proposed layout of the restroom does not have the minimum 5 foot turning radius required for accessibility. A revised layout shall be submitted to Codes Administration for review.
|
|
Correction
Codes Administration- It is Codes Administrations understanding that:
1) A perimeter stud wall will be constructed with insulation and sheetrock, as the existing conditions had sheetrock directly applied to the block wall with no insulation.
2) All interior partions shown in the plans submitted are new construciton, and non-loadbearing.
3) All roof top mechanical equipment is being relocated. There is no new equipment that will be installed as indicated in the plans submitted.
4) The north and west exterior doors are new, and the south doors are existing.
|
|
Correction
Codes Administration- The convenience store construction is type III-N, which allows wood partitions within exterior walls of noncombustible materials.
|
|
Correction
Fire Department- Access requirements per the approved site plan must be completed prior to receiving certificate of occupancy.
|
|
Correction
PLANNING & DEVELOPMENT - Revised elevations of the trash enclosure shall be submitted. The enclosure gates shall be constructed of a compatibly color coated steel gauge panel.
PLANNING & DEVELOPMENT - A revised Tree Protection Worksheet shall be submitted to and approved the Department of Planning and Development prior to the issuance of a building permit.
|
|
Correction
PLANNING & DEVELOPMENT - The issuance of the permit shall not constitute approval of any sign shown on the site plan or building elevations. Sign permits shall be obtained for all signs prior to installation.
|
|
Correction
PLANNING & DEVELOPMENT - Revised elevations of the rooftop screening shall be submitted. The elevations shall include the material and color of the proposed screen. These screens shall be coordinated with the appearance of the building.
|
|
Correction
Fire Department- Installation of and utilization of the proposed fuel pumps shall be in compliance with Article 79 of the Uniform Fire Code. Inspections of the installation process may be scheduled at least 48 hours in advance with Fire Prevention by calling 816-969-7343.
|
|
Correction
Fire Department- Smoking and open flams shall be prohibited in the areas used for fueling with or dispensing of Class I, II, or III-A liquids. Conspicuous signs prohibiting smoking, dispensing into unapproved containers, and requiring vehicles to be stopped during fueling operations shall be posted within sight of each customer being served. UFC 79.903(d).
|
|
Correction
Water Utilities- The placement of the new monument sign in the SE corner of the property should take into conideration the location of the existing water main.
|
|
Correction
Water Utilities- A reduced pressure backflow preventer is required on main water service line. Backflow prevention device must be tested before C of O.
|
|
Correction
Water Utilities- Easements need to be provided for water & sanitary sewer.
|
|
Correction
Codes Administration- Metal portions of dispensing pumps, metal raceways, metal jacketed cables and all noncurrent carrying metal parts of electric equipment, regardless of voltage, shall be grounded as provided in Article 250. (1990 NEC, Art.514-7).
|
|
Correction
PLANNING & DEVELOPMENT - All development shall be in accordance with the approved site plan.
|
|
Correction
PW - Contact Public Works Inspection at 969-7450 prior to construction.
|
|
Correction
Fire Department- Parking lots and fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be provided with a surface so as to provide all-weather driving capabilities. (UFC Section 10.204.(b))
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
Correction
Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
|